ABB Installation Products 755LR-L0300 600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable…
UPC: 075114197601
Contact for Pricing
Call (262) 252-1600 or email [email protected] for pricing and availability.
Overview
- Rated 600 Amps, 35kV for medium-voltage systems
- Supports cable insulation diameters from 1.180" to 1.465"
- Includes insulated plug, cap, stud, lug, and cable adapter
- Compatible with compressed stranded (350 kcmil), compacted solid (400 kcmil), or 185 mm² compact conductors
- Aluminum compression lug for low-resistance, high-reliability connections
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 350 kcmil , 400 kcmil |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 1.180 inch to 1.465 inch |
Special Features | 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected Using Standard Hand Tools and Equipment in a De-energized State. Optional Accessories allow Visible External Separation, By-Pass, Isolation, Dead-Ending, Grounding, and Testing as well as Adding Taps, Surge Arrestors, and Fault Current Indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

756LR-M0300-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold-Shrinkable Jacket Seal Included.
755LR-L0270
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
755LR-K0330-S
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. 200ECS Cold-Shrinkable Jacket Seal Included.
755LR-K0350-S
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 600 /Compacted Solid 600. 200ECS Cold-Shrinkable Jacket Seal Included.
755LR-L0260
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
755LR-L0240
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
755LR-K2270
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.Frequently Asked Questions
Is the 755LR submersible?
Yes, the 755LR features a fully shielded, fully submersible molded rubber housing.
What is the continuous current rating of the 755LR?
The 755LR has a continuous current rating of 600 Amps.
What is the maximum operating voltage for 755LR?
The maximum phase-to-ground operating voltage for the 35kV class is 21.1kV.
What insulation diameters does the 755LR support?
The 755LR supports insulation diameters ranging from 0.760 inches to 2.120 inches.
What conductor sizes are compatible with 755LR?
It is compatible with #2 AWG to 1250 kcmil for aluminum and copper conductors.
What is the 755LR product used for?
The 755LR is designed to provide fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What insulation diameters does the 755LR support?
The 755LR supports insulation diameters ranging from 0.760 inches to 2.120 inches.
What is the 755LR product used for?
The 755LR is designed to provide fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What conductor sizes are compatible with 755LR?
It is compatible with #2 AWG to 1250 kcmil for aluminum and copper conductors.
What is the maximum operating voltage for 755LR?
The maximum phase-to-ground operating voltage for the 35kV class is 21.1kV.
How to Install 755/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and connection of 755LR and 775LR Deadbreak Elbow Connectors on 35kV class systems, including cable preparation, crimping, and mating procedures. Ensure all apparatus are de-energized before beginning installation.
Estimated time: 2h
Tools needed:
Wire strippers, Knife or utility blade, Wire brush, Crimping tool, Torque wrench, Hotstick, Suitable voltage sensing device
Supplies needed:
755LR or 775LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack, Crimp chart, Grounding wire (min. No. 14 AWG Copper), Suitable grounding connector, HV insulated cap(s) or connector(s)
- Safety First & Initial Inspection
Ensure all apparatus are de-energized before starting. Inspect all package contents for completeness and damage. Verify all components fit properly with the cable and mating products. Have all required tools ready and maintain cleanliness throughout the procedure. This product must be installed by competent personnel trained in high voltage electrical safety practices.
- Position Cable and Cut
Position the cable in its final assembled location, allowing sufficient slack for elbow removal. If using concentric neutral cable, unwind the neutral wires. Precisely cut the cable 1-3/4” (45mm) from the centerline of the mating product.
- Clean Cable Jacket
Clean the outer jacket of the cable thoroughly for a distance of 24” (610mm) from the cut end.
- Prepare Cable for Termination
Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield to the specific dimensions shown in the diagrams for your cable type (e.g., non-jacketed concentric neutral, jacketed shield wires, flat metallic tape shield, fabric tape shield, or longitudinally corrugated shield). Refer to the provided illustrations for precise measurements and tape marker placement.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and lubricate the cable insulation, always working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Carefully remove any protruding cable insulation by cutting it flush with the end of the cable adapter. Ensure you do not cut or nick the cable adapter or the conductor. Verify the exposed conductor length is between 4-3/8” to 4-3/4” (111mm-121mm); if the measurement is outside this range, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it. Measure the 'Check Dimension' (which must be less than 7”/178mm) before crimping. Crimp the compression lug according to the instructions supplied with the lug. After crimping, wipe off all excess inhibitor from the lug and cable adapter surface. Verify the distance from the end of the compression lug to the cable adapter is between 6-7/8” to 7-5/8” (175mm-194mm); if not, redo the assembly.
- Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter by pushing it until it cannot advance further. Confirm the cable adapter remains flush with the tape marker. Reposition the cable adapter if necessary, then remove the tape marker.
- Prepare and Connect to Mating Product
Remove any protective caps from both the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud (supplied with the elbow) into it. Clean and lubricate both the elbow and the mating part with the provided lubricant, ensuring all surfaces remain clean. WARNING: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED.
- Push Elbow onto Mating Part
Push the elbow firmly onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite End of Elbow (if applicable)
Clean and lubricate the mating part intended for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part to the specifications provided in its own instructions.
- Install Insulating Plug (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap onto the elbow and push down firmly until it snaps securely into place.
- Ground the Cable Shield
Insert one end of a grounding wire (minimum No. 14 AWG Copper) through the grounding eye and twist it to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; refer to instructions for your grounding device or use an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (Recommended)
CAUTION: For 600amp L-Kits, ensure all components are tightened to the specified torque per plug connector instructions. To test for voltage, remove the test point cap using a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device and is NOT directly connected to the conductor. Use only a suitable sensing device designed for separable connectors with capacitive test points, following its manufacturer’s directions. Do not use conventional voltage measuring equipment. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means, as contamination or incorrect equipment can lead to false readings. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it securely on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.