ABB Installation Products 655LRTPFB-N5410 600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, Cable Insulation Diameter 0.675 inch to…
UPC: 783786343577
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating, 15kV maximum phase-to-ground voltage
- Bi-metal compression lug for high conductivity and corrosion resistance
- Accommodates 1000 kcmil compressed stranded conductors
- Cable insulation diameter range: 0.675" to 0.785"
- Deadbreak Stick-Op design enables safe hotstick installation and disconnection
Specifications
Amperage Rating | 600 to 200 A |
Application | Connect 600 Amp interface to 200 Amp Loadbreak Tap |
Color | Black |
Conductor Range | 1000 kcmil |
Connection Type | Compression Lug |
Current Rating | 600 A |
Enclosure | Yes, EPDM Rubber |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Bi-Metal |
Series | Deadbreak Stick-Op Connector Kit |
Size | 0.675-0.785 inches (Insulation Diameter) |
Special Features | Reducing Tap Plug 600 to 200 Amps. Provides an External Visible Break by Hotstick Removal of the Elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Stick Op Reducing Tap Plug Connector |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.2500 L |
Package Weight (Metric) | 3.7420 kg |

K656CYP0410P0410P041
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, with 3 X ( Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. )
K655LRTP-L0330
600 Amp, 25kV, Stick-Op Connector Kit. Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K655LRTP-N0380
600 Amp, 25kV, Stick-Op Connector Kit. Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
675LRTPA3
900 Amp, 15kV, Stick-OP Loadbreak Reducing Tap Plug. 600AT assembly tool required for operation and/or installation of Stick-OP. 900 Amp rating requires copper current carrying connector compenents and copper conductor cable.
K655LRTP-P0410-DRG
600 Amp, 25kV, Stick-Op Connector Kit with Insulated Cap. Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000.
656LRTP-J0300
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
655LRTPFB-M5380-DRG
600 Amp, 15KV, Stick Op Connector Kit, Fixed Bolt, Insulating Cap, Stick Op Load Break Reducing Tap Plug, Elbow Housing, Cable Adapter and Threaded Lug, Cable Insulation Diameter 1.370 inch to 1.630 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K655LRTP-L0320-DRG
600 Amp Elbow Connector, Stick Op Connector Kit, 25KV, Dead Break, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 450 /Solid 500/550.How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 655/675LR and K655/K675LR deadbreak elbow connectors, including cable preparation, component assembly, and grounding procedures for high voltage systems.
Estimated time: 1h 30m
Tools needed:
Hotstick, Wire brush, Crimping tool, Suitable sensing device (for capacitive test points), Wire strippers, Torque wrench
Supplies needed:
Lubricant (supplied with elbow), Threaded stud (if supplied with elbow), Wire (minimum No. 14 AWG Copper), Suitable connector (for grounding wire), Silicone lubricant, Compression Lug, Cable Adapter, Elbow, Insulating Plug (if applicable), Protective caps (to be removed)
- De-energize Apparatus and Inspect Components
DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Do not touch or move energized products in the work area. Inspect all package contents to ensure they are complete and undamaged. Verify all components for proper fit with the cable and/or mating products. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit.
- Prepare the Cable
Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent back concentric neutral wires. Follow the specific instructions for your cable type (e.g., 20MA/21MA grounding device, 600ECS Jacket Cable Seal, UNISHIELD*/LEAD SHEATH with 10TL adapter, or JACKETED/NON-JACKETED cable). Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield to the specified dimensions (e.g., 9-3/4”, 10-3/4”, 12-3/4” from the tape marker, as per cable type diagrams). Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back.
- Install Cable Adapter and Compression Lug
Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Remove any protruding cable insulation by cutting it even with the end of the cable adapter, ensuring not to cut or nick the adapter or conductor. The exposed conductor length must be between 4-1/4” to 4-9/16” (108mm-116mm); otherwise, redo the assembly. For copper conductors, fully insert into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert into the compression lug. Measure the 'Check Dimension' before crimping (this dimension must be less than 6-3/8”); otherwise, redo the assembly. Crimp the compression lug according to its supplied instructions. Wipe all excess inhibitor from the lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter after crimping must be between 6-3/8” to 7-1/8” (162mm-181mm); otherwise, redo the assembly.
- Install the Elbow and Connect Mating Products
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further, ensuring the cable adapter remains flush with the tape marker. Reposition the cable adapter if necessary, then remove the tape marker. DANGER: Do not connect or disconnect mating products while energized, and do not energize while disconnected. Remove protective caps from both the elbow and the mating part. Hand tighten the threaded stud (if supplied with the elbow) into the mating part if it's not already equipped. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean. Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part. Clean and lubricate the mating part for the opposite end of the elbow, then insert it into the elbow. Engage the threads, hand tighten, and torque the mating part according to its supplied instructions. If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow, pushing until it snaps into place.
- Ground the Cable Shield
Insert one end of a wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded; follow instructions supplied with a grounding device, or use an alternate method if no device is present. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable. CAUTION: When constructing 600amp L-Kits, ensure each component is tightened to the specified torque per instructions provided.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line with the assembly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for separable connectors manufactured with capacitive test points to determine if the cable is energized, following the meter manufacturer's directions. Contamination, moisture, dirt, or using the wrong measuring equipment can provide a false 'no voltage' indication on an energized elbow. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.