ABB Installation Products 35PCJ1P1380 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786634774
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV voltage rating
- Single-piece housing for simplified installation
- Accommodates cable insulation diameter: 1.725" - 1.935"
- Designed for 750 AWG stranded aluminum conductors
- ABB Installation Products quality
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 750 kcmil |
Connection | Compression |
Insulation | Yes |
Material | Aluminum |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | Style 1 |
Size | 15-3/4 inch long |
Size | 1.725 inch to 1.935 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.4000 L |
Package Weight (Metric) | 1.5420 kg |

35PCJ1P1380-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Conductor. Conductor Size AWG Stranded 750. Cold-Shrinkable Jacket Seal Included.
15PCJ1G1240
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
15PCJ1K2300
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 350.
15PCJ1M1380
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 750.
15PCJ1G1230
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
25PCJ1L1300
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 350.
15PCJ1L2330
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 500.Frequently Asked Questions
What are the installation applications for PCJ power cable joints?
PCJ power cable joints provide a permanent, fully shielded, fully submersible splice for direct-burial, underground vault, and overhead applications.
What is the BIL impulse withstand for 35 kV class?
For the 35 kV class, the BIL impulse withstand is 300 kV (1.2 x 50 μsec. wave).
What is the overall length of a 35PCJ1QX joint?
The 35PCJ1QX joint has an overall length (Dimension A) of 15 3/4 inches.
How do I order a transition joint for different cable sizes?
When constructing a catalog number for a transition joint, list the larger connector first and the smaller connector second.
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are only suitable for splicing copper conductors to copper conductors and should not be used on aluminum conductors.
Can aluminum and copper conductors be spliced together?
Yes, kits with aluminum compression connectors are suitable for splicing aluminum to aluminum or aluminum to copper conductors.
What are the current ratings for PCJ power cable joints?
The continuous current rating is equal to that of the cable rating. The short-time current rating is equal to the cable rating up to 35 kA.
What is the phase-to-ground voltage for 35 kV class?
The phase-to-ground voltage for the 35 kV class is 20.2 kV.
What safety standards do PCJ joints meet?
The shield design meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
What is the pull force rating for the interlock?
The pin-and-socket interlock of the PCJ power cable joints is designed to withstand a pull force of up to 500 lb.
How to Install the 15/25/35PCJ1,NPQ Straight Joint
This guide provides detailed instructions for installing the 15/25/35PCJ1,NPQ straight joint, a permanent, fully shielded, and submersible joint for wire shielded cables. Ensure all apparatus are de-energized before beginning installation to prevent serious or fatal injury.
Estimated time: 3h
Tools needed:
Cable cutting tool, Cable stripping tool, Wire-brush, Crimping tool, T&B WT3D tool (for 35kV only)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Connector (user supplied, for grounding wires), DELTECt Cable ties (for 35kV ONLY), No. 14 AWG copper wire or equivalent (if shield wires are smaller than #14 AWG)
- Safety and Initial Inspection
Ensure all apparatus are de-energized during installation or removal of parts. Inspect the package contents to ensure they are complete and undamaged. Verify all components fit properly with the cable and/or mating products. Gather all required tools and maintain cleanliness throughout the procedure.
- Prepare Cables for Joint Centerline
Overlap both cables and cut them to 12 inches (305mm) from the center line of the joint. This will ensure sufficient length of shield wires to be able to rejoin over the joint. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and that of Cable 2 to 21 inches (530mm). Fold back the shield wires. Finally, cut both cables at the center line of the joint.
- Prepare Cable 1 and Store Housing
Taper the edge of Cable 1 at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1 up to the shield wires.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both cables. DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR. Refer to the 'X' and 'Y' dimensions provided in the document's diagram for precise removal lengths based on conductor size (e.g., 2 1/2 inches for 500-750 MCM conductor 'X', 6 1/4 inches for 'Y').
- Install the Splice
If conductors are aluminum, wire-brush them and immediately insert them into the splice. Check the dimension against the 'Max Check Before' table; if it exceeds, redo the assembly. Crimp the splice following the recommendations provided with it. Wipe off all excess inhibitor where applicable. Check the distance between cable insulations; if it exceeds the 'Max Check After' dimension, redo the assembly. Remove any sharp protrusions or burrs generated during crimping and ensure all metal chips/filings are removed from the splice and joint assembly area.
- Lubricate Cables for Housing
Clean the cables where indicated in the diagram. Lubricate the cables in the direction of the arrows to provide a build-up or ramp of lubricant at the edge of the insulation shield.
- Position Joint Housing
Slide the housing into its final position. Ensure proper positioning by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield.
- Install 35kV Cable Ties (If Applicable)
For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance. Begin by installing the outer ties approximately 1/4 inch (6mm) from the edge of the splice, then install the second ties approximately 1/4 inch (6mm) from the first with an offset of the locking heads. Use a T&B WT3D tool (not included) to tighten and trim off the extra material of the ties.
- Complete Grounding and Jacket Reconstruction
Remove the yellow pin from the joint grounding eye and discard it. Retrain the shield wires and secure them to the ends of the joint as shown in the diagram. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket (where applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.