ABB Installation Products 35PCJ1H1240 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786037933
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV Voltage Rating
- Single-Piece Housing Design
- Insulation Diameter Range: 0.850" - 1.050"
- For Aluminum Conductors (AWG 1/0 Stranded / 2/0 Solid)
- ABB Installation Products
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1/0 STR AWG , 2/0 SOL AWG |
Connection | Compression |
Insulation | Yes |
Material | Aluminum |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Size | 0.850 inch to 1.050 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

35PCJ1K1240
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
35PCJ1H1230
35kV Power Cable Joint Style 1, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
15PCJ1K1310
15kV Power Cable Joint Style 1, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum compression lug. Conductor Size AWG or kcmil, Compressed Stranded 400 /Compacted Solid 450 /mmSquared Compact 240.
35PCJ1J1240-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Cold-Shrinkable Jacket Seal Included.
35PCJ1L1300-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 350. Cold-Shrinkable Jacket Seal Included.
35PCJ1P1410-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000. Cold-Shrinkable Jacket Seal Included.
15PCJ2H1270-F1240
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
69TCJS4-5-4Q
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 4, Housing Size 5, - 4QFrequently Asked Questions
Where are Elastimold PCJ power cable joints manufactured?
Elastimold PCJ power cable joints are assembled and 100% factory tested in Albuquerque, New Mexico, USA.
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for copper-to-copper connections only and should not be used on aluminum conductors.
What type of connector is included for aluminum conductors?
Kits for aluminum conductors include an aluminum compression connector suitable for splicing aluminum-to-aluminum or aluminum-to-copper conductors.
Can PCJ joints be used for direct-burial applications?
Yes, PCJ power cable joints provide a permanent, fully shielded, fully submersible splice suitable for direct-burial, underground vault, and overhead applications.
What standards do PCJ power cable joints meet?
The shield design meets IEEE 592 standard, and connectors meet ANSI 119.4 Class A and Class 3 ratings. Electrical ratings meet IEEE 404.
What are the two styles of PCJ power cable joints?
Style 1 is for straight splicing of two similar cables. Style 2 uses separate cable adapters for transition splicing between two different cable sizes.
What types of cables are compatible with PCJ joints?
PCJ joints work with copper or aluminum conductors up to 1250 kcmil, UD cable with concentric neutral, extruded insulation shielding, fabric-tape shielded, or lead-jacketed cables.
What voltage classes are available for PCJ power cable joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for copper-to-copper connections only and should not be used on aluminum conductors.
What types of cables are compatible with PCJ joints?
PCJ joints work with copper or aluminum conductors up to 1250 kcmil, UD cable with concentric neutral, extruded insulation shielding, fabric-tape shielded, or lead-jacketed cables.
How to Install the 35PCJ1 Series Straight Joint
This guide provides step-by-step instructions for the permanent, fully shielded, and submersible installation of the 35PCJ1 series straight joint for wire shielded cables, connecting aluminum to aluminum or aluminum to copper conductors.
Estimated time: 2h
Tools needed:
Wire strippers, Knife or Deburring tool, Wire brush (if aluminum conductors), Crimping tool, Cable tie tool (T&B WT3D tool for 35kV applications)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Connector (user supplied, for grounding wires), Grounding wire (#14 AWG copper or equivalent, if needed), DELTECt Cable ties TYD5135 (for 35kV applications), Cleaning supplies
- Perform Safety Checks and Initial Inspection
Before starting, ensure all apparatus is de-energized. Inspect the package contents for completeness and damage, and verify all components are compatible with the cable and mating products. This product should only be installed by competent personnel trained in good safety practices involving high voltage electrical equipment.
- Prepare Cables for Joint Installation
Overlap both cables and cut them to 12 inches (305mm) from the joint centerline. Remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires and then cut both cables at the joint centerline.
- Prepare Cable 1 and Store Joint Housing
Taper the edge of Cable 1's insulation shield from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Carefully slide the joint housing onto Cable 1, positioning it up to the shield wires.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both cables according to the specified dimensions (refer to the document's 'X' and 'Y' measurements). Exercise extreme caution to avoid cutting or nicking the cable insulation or conductor.
- Install and Prepare the Splice
If conductors are aluminum, wire-brush them thoroughly before immediately inserting them into the splice. Crimp the splice following its provided recommendations. Wipe off any excess inhibitor. Remove any sharp protrusions or burrs generated during crimping. Clean the cables where indicated and lubricate to create a ramp of lubricant at the edge of the insulation shield.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, ensuring proper placement by observing and equalizing the deformation of the joint ends. For 35kV ONLY: Install two DELTECt Cable ties on each end, 1/4 inch from the splice edge and 1/4 inch from the first tie with offset locking heads (use T&B WT3D tool). Remove the yellow pin from the grounding eye. Retrain and secure shield wires to joint ends. Insert one shield wire from each cable (if #14 AWG or larger) through the joint grounding eye; otherwise, use #14 AWG copper wire. Connect joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.