ABB Installation Products 10-TL-JAB Tape and Lead - Shield Adapter, Cable Accessory, Insulation 1.285 to 1.395 inches
UPC: 783786656615
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Designed for tape-insulated shielded cables (UniShield, flat metallic tape shield)
- Accommodates cable outer diameters from 1.285 to 1.395 inches
- Ensures reliable EMI shielding and electrical insulation
- Compatible with ELASTIMOLD distribution products for secure connections
- Does not provide grounding; grounding methods must be implemented separately
Specifications
Application | Used to Mate and Install the Cable to an Elastimold Product |
Connection | Slide-On |
Material | EPDM-Rubber |
Size | Cable Insulation Diameter 1.285 to 1.395 inches |
Size | 1.285 to 1.395 inches |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Shield Adapter |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 0.2000 L |
Package Weight (Metric) | 0.0910 kg |

K675TBC
15/25kV, 900 Amp, Deadbreak Bushing for In-Air Applications (Pad-Mounted or Vault-Type or Submersible Transformers or Switchgear). One Factory installed 5/8-11 UNC-2A Stud included, other Stud must be Purchased Separately. Overall Length 13.75 inch, Diameter 4.50 inch. Molded Epoxy with Stainless Steel Flange. Boot and Collar.Frequently Asked Questions
What is the 10TL-W Unishield Cable adapter?
The 10TL-W is a 15kV Unishield Cable adapter. The 'W' code is determined by the insulation diameter of the Unishield cable.
How do I select the correct 10TL-W cable adapter?
Select the 'W' letter code from the provided table based on the Unishield cable's insulation diameter. This determines the full part number, such as 10TL-W.
What insulation diameter does 10TL-JAB support?
The 10TL-JAB adapter supports Unishield cables with an insulation diameter from 1.285 to 1.395 inches (32.6 to 35.4 mm).
What is the voltage rating of the 10TL-W adapter?
The 10TL-W Unishield Cable adapter is designed for 15kV applications.
What is the 10TL-W Unishield Cable adapter?
The 10TL-W is a 15kV Unishield Cable adapter. The 'W' code is determined by the insulation diameter of the Unishield cable.
How do I select the correct 10TL-W cable adapter?
Select the 'W' letter code from the provided table based on the Unishield cable's insulation diameter. This determines the full part number, such as 10TL-W.
What insulation diameter does 10TL-JAB support?
The 10TL-JAB adapter supports Unishield cables with an insulation diameter from 1.285 to 1.395 inches (32.6 to 35.4 mm).
What is the voltage rating of the 10TL-W adapter?
The 10TL-W Unishield Cable adapter is designed for 15kV applications.
What is the 10TL-W Unishield Cable adapter?
The 10TL-W is a 15kV Unishield Cable adapter. The 'W' code is determined by the insulation diameter of the Unishield cable.
How do I select the correct 10TL-W cable adapter?
Select the 'W' letter code from the provided table based on the Unishield cable's insulation diameter. This determines the full part number, such as 10TL-W.
How to Install the 10TL Adapter for Flat Metallic Tape Shielded Cable
This guide provides detailed instructions for installing the 10TL adapter with Elastimold distribution products on flat metallic tape shielded cables, including cable preparation, adapter placement, and grounding procedures. Ensure all apparatus is de-energized before starting.
Estimated time: 1h
Tools needed:
Knife, Rag, Approved safety solvent, Soldering iron, Wire strippers, Measuring tape or ruler
Supplies needed:
10TL Adapter housing, Lubricant (DO NOT SUBSTITUTE), PVC insulating electrical tape (3/4 inch wide), Vinyl plastic electrical tape, #14 AWG (2.08mm²) wire, Grounding lead, Elastimold distribution product (to be installed with adapter), Electrical insulating tape
- Prepare for Installation and De-energize Circuit
Before beginning, ensure all apparatus is de-energized. Check the package contents for completeness and inspect all components for proper fit with the cable and mating products. Have all required tools ready and maintain cleanliness throughout the procedure. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices.
- Remove Cable Outer Jacket
Refer to the Elastimold product instructions for the semiconductive shield removal dimension (typically Step 2). Remove the cable's outer jacket a distance of 2 inches (51mm) more than this specified dimension.
- Remove Metallic Tape
Remove the metallic tape to a point 3/4 inch (19mm) from the edge of the remaining outer jacket.
- Remove Semiconducting Tape
Remove the semiconducting tape to a point 1 inch (25mm) from the edge of the remaining outer jacket.
- Apply Tape Retainer and Marker
Wrap 1-1/2 to 2 turns of 3/4 inch (19mm) wide PVC insulating electrical tape over the semiconducting and metallic tapes, 1/2 inch (13mm) from the edge of the outer jacket, to serve as a tape retainer. Then, wrap 2 turns of vinyl plastic electrical tape over the outer jacket, 1 inch (25mm) from its edge, to serve as a tape marker.
- Clean and Lubricate Cable and Adapter
Clean the outer jacket and thoroughly clean the insulation to remove all traces of semiconducting residue. Use a rag soaked with an approved safety solvent, wiping from the end of the cable toward the outer jacket. Lubricate the prepared cable and the inside of the 10TL adapter with the supplied lubricant.
- Slide Adapter onto Cable
Slide the 10TL adapter onto the cable using a forward, side-to-side twisting motion until it is flush with the tape marker. The step on the adapter will serve as a marker for assembling the Elastimold product.
- Install Elastimold Product
Install the associated ELASTIMOLD distribution product by following its specific installation instructions. After installation, a maximum gap of 1/8 inch (3mm) between the Elastimold product and the step on the adapter is permissible.
- Remove Tape Marker and Ground Metallic Shielding
Remove the tape marker from the cable after the Elastimold product is assembled. Approximately 2 inches (51mm) back from the end of the adapter, remove the outer jacket for a distance of 1-1/2 inches (38mm). Using #14 AWG (2.08mm²) wire and a grounding lead, fasten the grounding lead to the metallic shielding tape by making several wraps with the #14 AWG wire. Solder the ground lead to the metallic tape, avoiding excessive heat to prevent cable damage. After soldering, wrap the soldered area with electrical insulating tape, overlapping each cable jacket by approximately 1-1/2 inches (38mm).
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.