Best Practices for 24V Power Distribution and Control Cabinet Wiring in Industrial Automation

2026-04-26

· Gross Automation

· 7 min read

Case Studies
uncertainty-about
risk-of
lack-of

Case Study: Best Practices for 24V Power Distribution and Control Cabinet Wiring in Industrial Automation

In industrial automation, reliable 24V DC power distribution is critical to maintaining system uptime and preventing costly failures. This case study explores a common challenge faced by automation engineers: powering multiple distributed control cabinets from a single 24V/40A power supply while minimizing voltage drop and ensuring safety. We will walk through the problem, the approach taken, the solution implemented, and the measurable results, referencing best practices and specific products from leading manufacturers.


Problem: Voltage Drop and Wiring Challenges in a Distributed 24V/40A System

A mid-sized manufacturing plant was upgrading its automation system to improve process control and reduce downtime. The plant’s main control panel housed a high-quality 24V/40A DC power supply (Socomec USDBPA40ET-D), which needed to feed power to five smaller, remote control cabinets distributed across the production floor.

Key Pain Points

  • Voltage Drop: The plant’s automation engineers were concerned about voltage drop along the 24V lines feeding the remote cabinets. The longest cable run was approximately 50 feet one-way, and at 40A, even a small voltage drop could cause PLCs and sensors to malfunction.
  • Cable Sizing Uncertainty: There was confusion over what wire gauge to use for the 24V power lines. Using undersized cables risked overheating and voltage drop, while oversized cables increased cost and installation difficulty.
  • Wiring Topology: The existing wiring plan daisy-chained the smaller cabinets from one another, resulting in uneven voltage distribution and potential reliability issues.
  • Safety and Compliance: The plant needed to ensure wiring met NEC and NFPA 79 standards for industrial control panels, including proper conductor ampacity and insulation types.

Approach: Applying Best Practices for 24V/40A Power Distribution

The engineering team adopted a systematic approach based on industry guidelines and standards to address these challenges.

Step 1: Calculating Proper Wire Cross-Section

The team began by calculating the voltage drop using the formula:

[ V_{drop} = \frac{2 \times L \times I \times R}{1000} ]

Where:

  • (L) = one-way cable length in feet (50 ft)
  • (I) = current (40A)
  • (R) = resistance of the conductor in ohms per 1000 ft

Using copper wire resistance values from NEC tables:

  • 8 AWG copper wire has a resistance of approximately 0.64 Ω/1000 ft
  • 6 AWG copper wire has a resistance of approximately 0.40 Ω/1000 ft

Calculations:

  • For 8 AWG:

[ V_{drop} = \frac{2 \times 50 \times 40 \times 0.64}{1000} = 2.56V ]

  • For 6 AWG:

[ V_{drop} = \frac{2 \times 50 \times 40 \times 0.40}{1000} = 1.6V ]

Given a 3% voltage drop limit on 24V (0.72V), both 8 AWG and 6 AWG exceeded the limit at 50 feet. The team realized that to meet the 3% drop recommendation, either the cable length must be reduced or wire gauge increased.

Decision: Use 6 AWG wire for all 24V/40A runs exceeding 25 feet to minimize voltage drop and heat buildup.

Step 2: Designing a Star Wiring Topology

To avoid the pitfalls of daisy-chaining, the team designed a star topology:

  • The main panel housed a power distribution block (ABB Electrification USDBB06D50) to split the 40A supply into individual branch circuits.
  • Each remote cabinet received its own dedicated 6 AWG pair from the main panel.
  • Individual circuit protection (fuses or breakers) was installed for each branch to isolate faults.

Step 3: Selecting Wire Type and Installation Practices

  • The team specified stranded copper wire with MTW insulation, compliant with NEC and NFPA 79, for flexibility and vibration resistance.
  • 24V DC wiring was physically separated from AC mains wiring inside wireways to reduce electromagnetic interference (EMI).
  • Cable routing was planned to minimize length and avoid sharp bends.

Step 4: Considering Remote Sensing and Local Power Supplies

  • The Socomec USDBPA40ET-D power supply supported remote sensing lines, which were connected to the far end of the longest cable run to compensate for voltage drop.
  • For one particularly distant cabinet (~75 feet), the team installed a local 24V/10A power supply (Carlo Gavazzi SPD24101) to feed high-current devices locally, reducing load on the main supply line.

Solution: Implementing the Power Distribution System

The team procured the following components from Gross Automation:

  • Main Power Supply: Socomec USDBPA40ET-D, 24V/40A DIN rail power supply, known for robustness and remote sensing capability.
  • Power Distribution Blocks: ABB USDBB06D50 for centralized power splitting.
  • Wiring: 6 AWG stranded copper MTW wire for all main 24V lines.
  • Local Supplies: Carlo Gavazzi SPD24101 for remote cabinet power.
  • Circuit Protection: LS Electric S202UDC-Z16 miniature circuit breakers for branch circuit protection.

Installation Highlights

  • Each remote cabinet was fed by a dedicated 6 AWG pair from the main panel distribution block.
  • Remote sensing cables (thin gauge) ran alongside power cables to the farthest cabinets.
  • All wiring was neatly routed and labeled per UL 508A panel standards.
  • The team used cable ties and wire ducts to maintain separation and reduce EMI.

Results: Reliable, Safe, and Compliant 24V Power Distribution

After commissioning, the plant observed:

  • Stable Voltage at Remote Cabinets: Voltage measurements confirmed less than 0.7V drop at the farthest cabinet under full load, meeting the 3% target.
  • No Control System Failures: PLCs, sensors, and actuators operated reliably without resets or communication errors.
  • Improved Safety and Compliance: The wiring met NEC Article 310 ampacity requirements and NFPA 79 insulation standards, passing third-party inspection.
  • Simplified Troubleshooting: The star topology and individual circuit protection made fault isolation straightforward.
  • Scalability: The modular design allowed easy addition of new cabinets by extending from the main distribution block.

Practical Guidelines for Your 24V/40A Power Distribution

Based on this case study and industry best practices, here are actionable recommendations:

1. Determine Wire Gauge Based on Ampacity and Voltage Drop

  • Use 6 AWG stranded copper wire for 24V DC lines carrying 40A over distances greater than 25 feet.
  • For shorter runs (<25 feet), 8 AWG may suffice but verify voltage drop.
  • Calculate voltage drop using:

[ V_{drop} = \frac{2 \times L \times I \times R}{1000} ]

and keep it below 3% (0.72V for 24V).

2. Use a Star Wiring Topology with Power Distribution Blocks

  • Avoid daisy-chaining smaller control cabinets.
  • Install a power distribution block (e.g., ABB USDBB06D50) in the main panel.
  • Run individual power pairs from the main panel to each remote cabinet.
  • Provide individual fuses or breakers (LS Electric S202UDC-Z16) for each branch.

3. Choose Proper Wire Type and Installation Practices

  • Use stranded copper wire with MTW or THHN insulation for flexibility and compliance.
  • Physically separate 24V DC wiring from AC mains wiring to reduce EMI.
  • Route cables carefully, avoiding sharp bends and excessive length.

4. Employ Remote Sensing and Local Power Supplies When Needed

  • Use power supplies with remote sensing (like Socomec USDBPA40ET-D) to compensate for voltage drop.
  • For very long distances, consider local 24V power supplies (Carlo Gavazzi SPD24101) near the load.
  • Parallel conductors can be used if single large cables are impractical.

5. Follow Applicable Standards

  • NEC Article 310 for conductor ampacity.
  • NEC Table 250.122 for grounding conductor sizing.
  • UL 508A for industrial control panel wiring and protection.
  • NFPA 79 for insulation and wiring methods.

Conclusion

Proper sizing and wiring of 24V DC power lines in industrial automation are essential to system reliability and safety. This case study demonstrates that for a 24V/40A system feeding multiple distributed control cabinets:

  • Selecting the correct wire gauge (6 AWG for longer runs) prevents excessive voltage drop and overheating.
  • Employing a star wiring topology with power distribution blocks ensures stable voltage and easy maintenance.
  • Using stranded copper wire with appropriate insulation and separating DC from AC wiring reduces EMI and meets standards.
  • Leveraging remote sensing and local power supplies further enhances voltage stability.

For your next industrial automation project, trust Gross Automation to supply high-quality power supplies like the Socomec USDBPA40ET-D, power distribution blocks from ABB, and circuit protection devices from LS Electric. Our technical experts can help you design and source the right components to optimize your 24V power distribution system.


Ready to optimize your 24V power distribution? Contact Gross Automation today for expert guidance and premium industrial automation products.



Quick Answers from Products

What is the input voltage range for the SPD series power supplies?

The SPD series power supplies have a universal AC input full range of 90-264VAC. They can also accept a DC input range of 120-375VDC.

From: SPD24181 by Carlo Gavazzi

How is the SPD series power supply mounted?

The power supply is designed for DIN rail mounting, specifically on 7.5 or 15mm rails.

From: SPD24101 by Carlo Gavazzi

What are the dimensions of the SPD series power supply?

The dimensions are 90mm (3.60 in) in length, 22.5mm (0.89 in) in width, and 114mm (4.49 in) in depth.

From: SPD24101 by Carlo Gavazzi
Categories

How-To Guides

36

Comparisons

2

Troubleshooting

4

Buying Guides

6

Case Studies

4

General

19


Need More Help?

Our automation experts are ready to assist you.

Contact Support