ABB Low Voltage Drives ACS550-U1-08A8-4+K451+L502 ACS550 AC Drive, 3-380-480V In, 5HP, 8.8A, Type 1/IP21, 1.1 overload, Advanced, 14.5 x…
Alternate Item Number: 3AUA0000012782
UPC: 662348049655
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 5HP (3.7 kW) power rating with 8.8A output current
- Input voltage range: 380-480V (3-phase)
- Type 1/IP21 enclosure for dust and splash protection
- DeviceNet fieldbus and pulse encoder input for advanced motion control
- Compact 14.5 x 4.9 x 8.3 in wall-mountable design
- 1.1 overload capacity for reliable operation under transient loads
- ABB Drive composer Pro software for easy commissioning and monitoring
Specifications
Connection Type | DeviceNet, Pulse Encoder |
Control Panel | Advanced |
Current Rating | 8.8A |
Frame Size | R1 |
Input Phase | 3-Phase |
IP Rating | IP21 |
Mounting Type | Wall |
NEMA Rating | Type 1 |
Options | DeviceNet Pulse encoder |
Output Current | 8.8 |
Output Phase | 3-Phase |
Poles | 3-Phase |
Series | ACS550 |
Size | 14.5 x 4.9 x 8.3 in |
UL Type | 1 |
Voltage | 480 |
Voltage Range | 380-480 |
Voltage Rating | 380-480 VAC |
Voltage Rating | 380-480V |
Package Dimensions (L x W x H) | 8.3 in x 4.9 in x 14.5 in |
Package Dimensions (L x W x H) | 21.082 cm x 12.446 cm x 36.83 cm |
Package Weight (Imperial) | 14.300 L |
Package Weight (Metric) | 6.487 kg |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the frequency range for motor connection?
The motor connection frequency range is from 0 to 500 Hz.
What is the acceleration and deceleration time range?
Acceleration and deceleration times can be programmed from 0.1 to 1800 seconds.
Does the drive have built-in serial communication capabilities?
Yes, the drive has built-in RS 485 serial communication with the Modbus RTU protocol.
What is the maximum relative humidity allowed for operation?
The relative humidity must be lower than 95%, without condensation.
What is the power and voltage range for ABB standard drives?
The drives support 3-phase power with ranges including 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What is the auxiliary voltage provided by the drive?
The drive provides an auxiliary voltage of 24 V DC ±10% with a maximum current of 250 mA.
What is the operating ambient temperature range for the drives?
The drives operate in ambient temperatures between 15 to 40°C (5 to 104°F), with derating required from 40 to 50°C (104 to 122°F).
What types of analog inputs are available?
The drives offer two analog inputs that can accept voltage signals (0-10V) or current signals (0-20mA).
How many digital inputs are available and what are their specifications?
There are six digital inputs that accept 12V to 24V DC with a maximum delay of 5 ms ± 1ms.
What are the specifications for the relay outputs?
Three relay outputs are available with a maximum switching voltage of 250V AC/30V DC and a maximum switching current of 6A.