nVent T430646G400 T-Series Mid-Size Outdoor without Heat T43, 6000BTU 460V, Lt Gray, Steel
UPC: 783510231361
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 6000 BTU/hr cooling capacity for mid-size enclosures
- Operates from -40°F to 131°F (-40°C to 55°C)
- 460V, 1PH, 50/60Hz power input with 14A starting current
- Dimensions: 43" H x 15.75" W x 10.9" D (1092 x 400 x 279 mm), 125 lb weight
- 460V power requirement suitable for industrial applications
- Reliable mechanical thermostat on enclosure side of the unit
- Dual condenser-side air movers for performance redundancy
- Painted galvanized sheet-metal or stainless steel cover for rugged factory and outdoor environments
- Easy-mount flanges for simple installation
- Every unit functionally tested before shipping
Specifications
Amperage Rating | 2.3 A |
Application | Power Distribution; Controls and Drives |
Btu Rating | 6,600 |
Color | Lt Gray |
Color | Light Gray |
Color Code | RAL 7035 |
Depth | 277 mm |
Depth | 10.9 in |
Finish | Powder Coated |
Frequency Rating | 50/60 Hz |
Height | 1,092 mm |
Height | 43 in |
Material | Mild Steel |
Material | Steel |
Max Current | 2.3 A |
Model | T43 |
NEMA Rating | 4 Watertight |
Nominal Capacity Btu/h | 6,600 Btu/h |
Nominal Capacity Watts | 1,934 W |
Nominal Voltage | 460 V |
Number Of Phases | 1 |
Operating Temperature | -40-131 |
Operating Temperature | -40-55 |
Phase | 1 |
Power | 1934 W |
Product Family | T-Series |
Protection Rating | NEMA Type 4 |
Remote Access Control | No |
Series | T-Series |
Thickness | 1.21 mm |
Thickness | 18 ga |
Type | Air Conditioners |
Voltage AC | 400-460 V |
Voltage Rating | 460 V |
Weight | 151 lb |
Weight | 57 kg |
Width | 400 mm |
Width | 15.75 in |
Package Dimensions (L x W x H) | 20.75 IN x 13.75 IN x 44.75 IN |
Package Dimensions (L x W x H) | 52.705 cm x 34.925 cm x 113.665 cm |
Package Weight (Imperial) | 151.000 L |
Package Weight (Metric) | 68.494 kg |
Frequently Asked Questions
What voltage does the T430646G400 require?
It operates on 460V, single-phase, 50/60Hz power.
What is the operating temperature range?
The unit functions from -40°F to 131°F (-40°C to 55°C).
What is the weight of the T430646G400?
The unit weighs 125 lb (57 kg).
What is the cooling capacity of the T430646G400?
The unit provides 6000 BTU/hr of cooling at 95°F ambient temperature.
What refrigerant does the T430646G400 use?
The air conditioner uses R-134A refrigerant with a 36 oz charge.
What is the thermostat setting?
The factory-set thermostat is 80°F (27°C).
What are the enclosure protection ratings?
Internal loop is IP56 and external loop is IP34 rated.
What is the airflow capacity?
External loop airflow is 535 CFM and internal loop is 493 CFM at 60Hz.
How to Install the T430646G400 Air Conditioner
This guide provides step-by-step instructions for installing the T430646G400 air conditioner, including mounting, wiring, and initial setup.
Estimated time: 45m
Tools needed:
Screwdriver, Wrench, Wire strippers, Multimeter
Supplies needed:
Mounting screws, Gasket kit, Drain tube
- Inspect the air conditioner
Check for any visible damage and ensure the unit is functioning properly before installation. Connect to a power supply and run the unit for 5-10 minutes to verify operation.
- Prepare the mounting area
Using the cutout dimensions provided in the manual, prepare the air 'IN' and 'OUT' openings, and the mounting bolt hole pattern on the enclosure.
- Install gaskets
Use the gasket kit provided to install gaskets on the air conditioner in the specified locations to ensure a proper seal.
- Mount the air conditioner
Secure the air conditioner to the enclosure using the mounting screws provided. Use the 'EZ' mount tabs to hold the unit in place while securing it.
- Connect the power supply
Refer to the nameplate for electrical requirements and connect the power cord to a properly grounded power supply. Ensure the circuit is fused appropriately.
- Route the drain tube
Ensure the drain tube is routed without kinks and on a continuous downward slope to prevent overflow of the condensate drain pan.
- Adjust the thermostat
Remove the nylon plug from the thermostat and use a screwdriver to set the desired temperature. Turn clockwise for cooler temperatures and counterclockwise for warmer.
- Verify installation
After installation, power on the unit and check for proper operation. Ensure that both the evaporator and condenser fans are running and that there is airflow.
Frequently Asked Questions about nVent
What industries and applications are nVent products used for?
nVent products are engineered for critical infrastructure and industrial applications across multiple demanding sectors. Key markets include Construction, Data Centers, Defense, Healthcare, Mining, Oil & Gas Refineries, Power Plants, Rail/Transit, Renewable Energy, Security, Ship Building, Steel Mills, Telecom, and Utilities. Their solutions are designed to withstand extreme environmental conditions, with temperature ranges from -55°C to 105°C and specialized features like UV resistance, oil resistance, and flame resistance.
What environmental ratings do nVent products have?
nVent enclosures feature comprehensive environmental ratings, including UL 508A, CSA, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications. They are rated IEC 60529 IP66, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments. These products operate effectively in temperatures ranging from -40°F to 266°F, with enhanced UV inhibitors for outdoor weathering and oil-resistant gaskets for superior sealing.
What accessories are available for nVent products?
nVent offers a comprehensive range of accessories across multiple product lines, including EMC accessories like bonding cable clamps and strain reliefs, inline accessories such as lock inserts and mounting brackets, CONCEPT accessories including panel conversion kits and rack-mount angles, and seismic accessories for specialized mounting requirements. Key accessory categories include grounding kits, DIN rail mounting solutions, panel supports, handles, and various mounting hardware compatible with different enclosure types.
What certifications and standards do nVent products comply with?
nVent products meet critical international certifications including UL (United States), CSA (Canada), CE (European Community), and EAC (Russia). Our products are designed to comply with rigorous industrial standards such as NEMA enclosure ratings, IEC 60529 IP ratings, and international safety standards across multiple industrial markets including oil & gas, power, manufacturing, and infrastructure.
What is nVent's warranty policy?
nVent offers a standard 18-month warranty from invoicing date for most automation products, covering defects in workmanship and materials. The warranty requires proper transportation, handling, storage, and installation within specified environmental conditions. Warranty coverage includes repair or replacement at nVent's discretion, with certain conditions such as authorized service repairs and operation within designed capacity limits.
What technical support does nVent offer?
nVent offers comprehensive technical support through multiple global contact centers across North America, South America, Europe, Middle East, India, and Asia. Customers can reach technical experts by phone at regional numbers, with the North American headquarters in Minneapolis, MN providing primary support at +1.763.421.2240. Additionally, nVent provides online support resources through their website, including CAD drawing downloads and an 'Ask The Expert' feature to assist with product technical inquiries.