Contact for Pricing
Overview
- 50W, 80W, 200W, 300W, 400W and 600W models available
- Provides freeze protection down to -76 F / -60 C
- Conductive and Convection heating types available
- 50W and 80W models can be mounted directly to manifolds, measuring or analyzing instruments, control valves, and similar equipment
- 200W, 300W, 400W, 600W models are finned heaters that heat the area by transferring the heat from the heater to surrounding air, creating a convection current
- Two thermostat options available with a 50 F / 10 C or 68 F / 20 C set point
Specifications
Application | Hazardous Environments |
Color | Black |
Depth | 2.4 in |
Depth | 61 mm |
Finish | Anodized |
Height | 12.8 in |
Height | 325 mm |
Material | Aluminum |
Nominal Capacity Watts | 300 W |
Nominal Voltage | 115 V |
Series | HL HEATER SL |
Type | Heaters |
Voltage AC | 110-265 V |
Voltage Rating | 115 V |
Voltage Rating | 110-265 VAC or VDC |
Weight | 5.65 kg |
Weight | 13.9 lb |
Width | 229 mm |
Width | 9 IN |
Package Dimensions (L x W x H) | 22.8 IN x 11.1 IN x 4.2 IN |
Package Dimensions (L x W x H) | 57.912 cm x 28.194 cm x 10.668 cm |
Package Weight (Imperial) | 13.900 L |
Package Weight (Metric) | 6.305 kg |
How to Install the DAHHL300AC Heater
This guide provides step-by-step instructions for installing and wiring the DAHHL300AC heater in hazardous locations.
Estimated time: 45m
Tools needed:
Screwdriver, Wire strippers, Multimeter
Supplies needed:
Mounting screws, Terminal connectors
- Mount the heater
Secure the heater to the unistrut using the four M6 bolts provided in the mounting kit. Ensure the fins are positioned vertically for effective convection.
- Connect the wiring
Install the connection cable into the customer-supplied junction box, ensuring to observe the permissible bending radius of 5 times the outside cable diameter. Use a cable gland or ½ NPT conduit as required.
- Ground the heater
Connect the ground terminal to ensure potential equalization. Use a suitable circuit breaker for protection, and ensure compliance with local electrical codes.
- Power on the heater
Once all connections are secure, turn on the heater. Be aware that the startup current may be 3 to 5 times greater than the nominal current for the first few seconds.
- Verify operation
Use a multimeter to check the voltage and current to ensure they are within the specified limits. Monitor the heater for proper operation.
Frequently Asked Questions about nVent
What industries and applications are nVent products used for?
nVent products are engineered for critical infrastructure and industrial applications across multiple demanding sectors. Key markets include Construction, Data Centers, Defense, Healthcare, Mining, Oil & Gas Refineries, Power Plants, Rail/Transit, Renewable Energy, Security, Ship Building, Steel Mills, Telecom, and Utilities. Their solutions are designed to withstand extreme environmental conditions, with temperature ranges from -55°C to 105°C and specialized features like UV resistance, oil resistance, and flame resistance.
What environmental ratings do nVent products have?
nVent enclosures feature comprehensive environmental ratings, including UL 508A, CSA, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications. They are rated IEC 60529 IP66, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments. These products operate effectively in temperatures ranging from -40°F to 266°F, with enhanced UV inhibitors for outdoor weathering and oil-resistant gaskets for superior sealing.
What accessories are available for nVent products?
nVent offers a comprehensive range of accessories across multiple product lines, including EMC accessories like bonding cable clamps and strain reliefs, inline accessories such as lock inserts and mounting brackets, CONCEPT accessories including panel conversion kits and rack-mount angles, and seismic accessories for specialized mounting requirements. Key accessory categories include grounding kits, DIN rail mounting solutions, panel supports, handles, and various mounting hardware compatible with different enclosure types.
What certifications and standards do nVent products comply with?
nVent products meet critical international certifications including UL (United States), CSA (Canada), CE (European Community), and EAC (Russia). Our products are designed to comply with rigorous industrial standards such as NEMA enclosure ratings, IEC 60529 IP ratings, and international safety standards across multiple industrial markets including oil & gas, power, manufacturing, and infrastructure.
What is nVent's warranty policy?
nVent offers a standard 18-month warranty from invoicing date for most automation products, covering defects in workmanship and materials. The warranty requires proper transportation, handling, storage, and installation within specified environmental conditions. Warranty coverage includes repair or replacement at nVent's discretion, with certain conditions such as authorized service repairs and operation within designed capacity limits.
What technical support does nVent offer?
nVent offers comprehensive technical support through multiple global contact centers across North America, South America, Europe, Middle East, India, and Asia. Customers can reach technical experts by phone at regional numbers, with the North American headquarters in Minneapolis, MN providing primary support at +1.763.421.2240. Additionally, nVent provides online support resources through their website, including CAD drawing downloads and an 'Ask The Expert' feature to assist with product technical inquiries.