Contact for Pricing
Overview
- Seams are continuously welded and ground smooth
- Body stiffeners in larger enclosures for extra rigidity
- Body flange trough excludes liquids and contaminants
- Heavy-duty lifting eyes anchor into reinforced top
- Concealed, easy-to-remove hinges
- Heavy-duty 3-point latching mechanism operated by padlocking handle on all doors
- Order panels separately
- Data pocket is high-impact thermoplastic
- Oil-resistant door gasket
- Bonding provision on door
Specifications
Application | Arc Flash Safety;Controls and Drives;Power Distribution |
Body Thickness | 11 ga |
Body Thickness | 3.04 mm |
Body Thickness | 16 ga |
Cable Entry | No |
Color | Gray |
Color | ANSI 61 Gray;Gray |
Color Code | ANSI 61 |
Conductive Panel | A84PM40G |
Connection | Yes |
Cubic Capacity | 47 in3 |
Cubic Capacity | 770193.7 mm3 |
Cutout Type | No Cutout |
Depth | 613 mm |
Depth | 24.13 |
Depth | 613 |
Door Thickness | 14 ga |
Door Thickness | 2.66 mm |
Door Thickness | 12 ga |
Finish | Powder Coating |
Finish | Powder Coated |
Height | 84.13 |
Height | 2,137 |
Height | 2,137 mm |
Insulation | False |
Insulation | No |
Material | Mild Steel |
Mounting | Free Standing |
NEMA Rating | Type 4, 12, 3R |
NEMA Rating | 12;3R;4 |
Number Of Outlet | 1 |
Painted Panel | A84PM40 |
Panel Size | 72.00 x 33.75 in |
Panel Size | 1829 x 857 mm |
Protection Rating | NEMA Type 4 |
Size | 84.13 x 39.76 x 24.13 inch |
Type | Mild Steel Freestanding Industrial Enclosures |
Weight | 402.4 lb |
Width | 39.76 |
Width | 1,010 |
Width | 1,010 mm |
Package Dimensions (L x W x H) | 84 IN x 40 IN x 24 IN |
Package Dimensions (L x W x H) | 213.36 cm x 101.6 cm x 60.96 cm |
Package Weight (Imperial) | 402.400 L |
Package Weight (Metric) | 182.529 kg |

BX4
Sealable and transparent protective covers BX4 and non-removable BX4-CA to protect the devices against accidental contact.
LT20D-NEW
1/2 Inch, 90 Degree, Two-Piece Liquidtight Non-Metallic Fitting, UL E32447, Temperatures up to 107 Degrees C, Nitril Rubber O-Ring, PVC, Grey
LN43DA
1/2 Inch, Straight, One-Piece Liquidtight Non-Metallic Fitting, CSA, UL E32447, Temperatures up to 60 Degrees C, PVC, Grey
LH38
Cord Grip with NPT Threads, Locknut Included, NPT Thread Size 3/8 Inch, Cable Range 0.181 Inch/4.6mm to 0.312 Inch/7.9mm, Hole Clearance 0.670 Inch/17.0mm, Thread Length 0.53 Inch/13.5mm, IP68 Rating, Nylon, BlackFrequently Asked Questions
What are the dimensions of the AU84X4024RLP enclosure?
The enclosure has a height of 84.13 inches, a width of 39.76 inches, and a depth of 24.13 inches.
What material is the AU84X4024RLP enclosure made of?
The enclosure is constructed from mild steel with a powder-coated gray finish.
What industry standards does the AU84X4024RLP enclosure meet?
It meets UL 508A Listed, Type 4, 12, 3R; cUL Listed per CSA C22.2 No. 94; NEMA Type 4, 12, 3R; IEC 60529, IP66; and IEC 62208, IK10 Impact Rating.
What is the weight of the AU84X4024RLP enclosure?
The enclosure weighs 402.4lb.
What type of latching mechanism does the enclosure feature?
It features a heavy-duty 3-point latching mechanism operated by a padlocking handle on all doors.
Are panels included with the AU84X4024RLP enclosure?
No, panels must be ordered separately for this enclosure.
What is the body and door thickness of this enclosure?
The body thickness is 11ga and the door thickness is 12ga.
Can this enclosure be used outdoors?
Yes, the Universal Free-Stand Enclosure is designed for both indoor and outdoor use.
How to Safely Handle and Install a Hoffman Enclosure
This guide provides instructions for safely handling and installing Hoffman enclosures, emphasizing precautions to prevent injury and equipment damage.
Estimated time: 1h
Tools needed:
Forklift, Overhead lifting device, Slings with hooks or shackles, Chain or strap (3000 lb-rated)
Supplies needed:
ROLL•A•LIFT™ or similar device (for some models)
- Read Safe Handling Requirements
Before moving or installing the enclosure, read and follow all precautions in the Large Enclosure Safe Handling Requirements manual that accompanied the enclosure. Ensure the route is clear of obstructions and workers are at a safe distance.
- Prepare for Forklift Handling
Ensure the forklift operator is trained and authorized. Know the safe lifting capabilities of the equipment and verify it can handle the enclosure's weight and size by checking the product label and nameplate data. Position enclosures far back on the forks with the load against the carriage/mast, tilting the load backward towards the mast.
- Secure Enclosure for Forklift Transport
If using a forklift, secure the enclosure to the forklift mast before moving. For some models, insert a 3000 lb-rated chain or strap through the eye bolts provided on top of the enclosure and fasten securely to the forklift mast assembly. Ensure sufficient tension to prevent tipping. Do not use chains or straps for lifting, only for preventing tipping.
- Move Enclosure with Forklift
Start and stop the forklift slowly and gradually. Drive slowly with the forks carried as low to the ground as possible. Have a person assist the forklift operator at a safe distance to guide the enclosure.
- Prepare for Overhead Lifting
If using overhead lifting, attach rigging to the eye bolts, ensuring the angle between lifting cables and the vertical does not exceed 45 degrees. Use slings with adequate load-rated hooks or shackles. Ensure the load rating of the lifting device and rigging is sufficient for the enclosure's weight.
- Perform Overhead Lift
Select or adjust rigging lengths to compensate for any unequal weight distribution and to support the enclosure in an upright position. Do not allow the angle between lifting cables and the vertical to exceed 45 degrees.
- Position Enclosure
Carefully position the enclosure on the forks or with the lifting device, ensuring the load is stable and secure. Avoid contacting fixed objects during transport. Lift the enclosure only the minimum distance necessary to clear the floor or for transport.
Frequently Asked Questions about nVent
What industries and applications are nVent products used for?
nVent products are engineered for critical infrastructure and industrial applications across multiple demanding sectors. Key markets include Construction, Data Centers, Defense, Healthcare, Mining, Oil & Gas Refineries, Power Plants, Rail/Transit, Renewable Energy, Security, Ship Building, Steel Mills, Telecom, and Utilities. Their solutions are designed to withstand extreme environmental conditions, with temperature ranges from -55°C to 105°C and specialized features like UV resistance, oil resistance, and flame resistance.
What environmental ratings do nVent products have?
nVent enclosures feature comprehensive environmental ratings, including UL 508A, CSA, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications. They are rated IEC 60529 IP66, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments. These products operate effectively in temperatures ranging from -40°F to 266°F, with enhanced UV inhibitors for outdoor weathering and oil-resistant gaskets for superior sealing.
What accessories are available for nVent products?
nVent offers a comprehensive range of accessories across multiple product lines, including EMC accessories like bonding cable clamps and strain reliefs, inline accessories such as lock inserts and mounting brackets, CONCEPT accessories including panel conversion kits and rack-mount angles, and seismic accessories for specialized mounting requirements. Key accessory categories include grounding kits, DIN rail mounting solutions, panel supports, handles, and various mounting hardware compatible with different enclosure types.
What certifications and standards do nVent products comply with?
nVent products meet critical international certifications including UL (United States), CSA (Canada), CE (European Community), and EAC (Russia). Our products are designed to comply with rigorous industrial standards such as NEMA enclosure ratings, IEC 60529 IP ratings, and international safety standards across multiple industrial markets including oil & gas, power, manufacturing, and infrastructure.
What is nVent's warranty policy?
nVent offers a standard 18-month warranty from invoicing date for most automation products, covering defects in workmanship and materials. The warranty requires proper transportation, handling, storage, and installation within specified environmental conditions. Warranty coverage includes repair or replacement at nVent's discretion, with certain conditions such as authorized service repairs and operation within designed capacity limits.
What technical support does nVent offer?
nVent offers comprehensive technical support through multiple global contact centers across North America, South America, Europe, Middle East, India, and Asia. Customers can reach technical experts by phone at regional numbers, with the North American headquarters in Minneapolis, MN providing primary support at +1.763.421.2240. Additionally, nVent provides online support resources through their website, including CAD drawing downloads and an 'Ask The Expert' feature to assist with product technical inquiries.