The TCI KDRI42LV is a 3-phase input line inductor from the KDR Series, designed for industrial power quality management. Rated at 690V AC and 192A, it supports motors up to 200HP, making it ideal for high-power industrial applications. This open-style inductor features a low impedance design to mitigate harmonics and regulate voltage, ensuring efficient power delivery and reduced electrical stress on equipment. Manufactured in Germany under TCI’s rigorous standards, the KDRI42LV is UL recognized for compliance with safety and performance requirements. Its compact design and open-style mounting make it suitable for integration into existing control panels or machinery. The inductor’s robust construction and precise electrical ratings provide reliable operation in demanding environments, including manufacturing, mining, and heavy machinery sectors.
  • Rated for 690V AC, 192A, supporting motors up to 200HP
  • 3-phase input design for industrial power quality management
  • Open-style mounting for flexible integration into control panels
  • Low impedance design reduces harmonics and regulates voltage
  • UL recognized for compliance with safety and performance standards

Specifications

Connection Type
3-phase
Current Rating
192 A
Mounting Type
Open-style
Series
KDR
Voltage Rating
690 V
KDR, 690V, 200A, 200HP

KDRI32PV

KDR, 690V, 200A, 200HP
KLR, 690V, 200A, 200HP

KLR200ECBV

KLR, 690V, 200A, 200HP
KLR, 690V, 200A, 200HP

KLR200DCBV

KLR, 690V, 200A, 200HP
KDR, 690V, 160A, 150HP

KDRI31PV

KDR, 690V, 160A, 150HP
KDR, 575V, 192A, 200HP

KDRI42LC4

KDR, 575V, 192A, 200HP
KDR, 575V, 192A, 200HP

KDRI42LE3R

KDR, 575V, 192A, 200HP
KDR, 575V, 192A, 200HP

KDRJ41HE3R

KDR, 575V, 192A, 200HP
KDR, 575V, 192A, 200HP

KDRJ41HC5

KDR, 575V, 192A, 200HP
KDR, 575V, 192A, 200HP

KDRJ41HE01

KDR, 575V, 192A, 200HP
KLR, 690V, 160A, 150HP

KLR160DCB4V

KLR, 690V, 160A, 150HP
KLR, 690V, 160A, 150HP

KLR160DCBV

KLR, 690V, 160A, 150HP
KDR, 575V, 200A, 200HP

KDRI32PC4

KDR, 575V, 200A, 200HP

Frequently Asked Questions

What is the voltage and HP range for KDR line reactors?

KDR line reactors are available for voltages from 208 V to 690 V and power ratings from 0.25 HP to 1250 HP.

What types of impedance are available for KDR line reactors?

KDR line reactors are available in Ultra Low, Low, and High Impedance options.

What is the operating temperature range for KDR line reactors?

The ambient temperature range for KDR line reactors is -40°C to 40°C enclosed.

Can KDR line reactors be used on the input and output of a VFD?

Yes, KDR line reactors are constructed to be used on both the input and output of a VFD.

What are the benefits of using KDR line reactors with VFDs?

KDR line reactors help reduce harmonics, protect drives from voltage spikes, and extend motor service life by minimizing insulation stress.

What agency approvals do KDR line reactors have?

KDR line reactors are UL Listed and have cULus agency approvals.

What is the warranty for KDR line reactors?

KDR line reactors come with a lifetime warranty for the life of the drive with which the reactor is installed.

What is the short-term overload rating for KDR line reactors?

KDR line reactors can tolerate 200% rated I for a maximum of 3 minutes.

At what altitude can KDR line reactors operate without derating?

KDR line reactors can operate up to 2,000 m (6,000 ft) without derating.

What is the minimum inductance at 110% and 150% load?

The minimum inductance is 95% L at 110% load and 80% L at 150% load.

Frequently Asked Questions about TCI

What environmental ratings do TCI products have?

TCI products feature robust environmental ratings across multiple standards, including UL 508A Type 1, 2, 3, 4, 4X, 12, and 13; CSA Type 1, 2, 3, 4, 4X, 12, and 13; and NEMA Type 1, 2, 3, 4, 4X, 12, and 13. Additionally, they meet IEC 60529 IP66 standards, providing exceptional protection against dust, water, and corrosive environments with operating temperatures ranging from -40°C to 130°C.

What industries and applications are TCI products used for?

TCI products are engineered for critical applications across multiple industrial sectors, including HVAC, metals manufacturing, elevators and escalators, marine and shipping, food processing, pulp and paper, and underground construction. Their TorqueDrive Series offers specialized solutions for diverse load types such as fans, pumps, compressors, conveyors, hoists, winders, and synchronized positioning applications, with specific product lines designed for high-performance environments requiring precise torque control, energy efficiency, and robust environmental resistance.

What are the main product lines offered by TCI?

TCI offers four primary product lines: Harmonic Solutions, Motor Protection Solutions, Power Factor Correction Solutions, and High Frequency Noise Solutions. These comprehensive product lines include advanced technologies like HarmonicGuard® Active and Passive Filters, MotorGuard™ Sine Wave Output Filters, PF Guard Capacitor Banks, and KRF 3-Phase EMC Power Line Filters designed for industrial automation and electrical system optimization.

What are the key features of TCI products?

TCI products feature advanced harmonic mitigation solutions including HarmonicGuard® Active and Passive Filters, specialized line and load reactors, and power factor correction technologies. Key capabilities include integrated EMC design, high-endurance capacitors capable of handling 190% rated current, and solutions specifically engineered for harmonically-rich industrial environments like manufacturing facilities, water treatment plants, and facilities with variable frequency drives.

What certifications and standards do TCI products comply with?

TCI products are certified to meet critical North American standards including UL (Underwriters Laboratories) and CSA (Canadian Standards Association) certifications. Our products comply with rigorous safety and performance requirements for industrial automation equipment, with UL Listed Product and Recognized Component classifications ensuring high-quality manufacturing and reliability across multiple industrial applications.

What is TCI's warranty policy?

TCI offers a Limited Warranty policy that requires customers to obtain a Return Material Authorization (RMA) number before returning any products. Returns must be submitted within 30 days of the initial return request to TCI's Germantown, Wisconsin facility. All returned goods are subject to inspection, and restocking charges may apply. Customers should contact TCI's Customer Service for specific warranty details and return instructions.

What communication protocols do TCI products support?

TCI products support a comprehensive range of industrial communication protocols, including PROFIBUS DP V1, PROFINET with dual port, EtherNet/IP with dual port, CANopen, and Modbus RTU. These protocols enable flexible network integration, high-performance communication, and seamless connectivity with major PLC systems across diverse industrial automation environments.

What accessories are available for TCI products?

TCI offers a comprehensive range of communication and bus accessories for industrial automation systems. Key accessories include communication terminal boards (CTB810, CTB811), horizontal and vertical bus extenders (cHBX01L/R, HBX01L/R, VBX01T/B), and bus terminators (TER800, TER810). These accessories support connection, power distribution, and signal integrity for HN800 and CW800 device networks, enabling flexible and robust system configurations.

How are TCI products typically installed?

TCI products are typically installed by trained, manufacturer-certified technicians following a comprehensive commissioning process. Installation involves critical steps including work environment inspection, electrical installation checks, internal and external equipment verification, system power-up, and comprehensive operational testing. Authorized installation personnel ensure compliance with industry standards, complete factory acceptance tests, and provide a conformity certificate to guarantee safe and reliable system integration.