Overview

The TCI HGP0050AW1S0000 is a passive harmonic filter engineered to mitigate harmonic distortion in 480 VAC, 3-phase industrial electrical systems operating at 50 HP and 60 Hz. This unit is part of the HGP series, designed for direct installation in standard industrial environments where power quality is critical. The filter reduces unwanted harmonics, improving power delivery reliability and extending the operational lifespan of connected equipment such as motors, drives, and transformers. With a NEMA Type 1 enclosure, the HGP0050AW1S0000 is suitable for indoor installations requiring protection against solid foreign objects. It operates at 65 amps with a reactive power rating of 15 kVar and a power loss of 550 watts, ensuring efficient harmonic mitigation without excessive energy waste. The filter is configured for standard voltage distortion correction and does not include an integrated contactor, making it a straightforward solution for harmonic mitigation in industrial applications. Compatible with 3-phase systems, this filter is optimized for use in manufacturing, processing, and other industrial facilities where power quality directly impacts equipment performance and longevity.
  • 480 VAC, 3-phase, 50 HP, 60 Hz operation
  • 65 amps, 15 kVar reactive power rating, 550 watts power loss
  • NEMA Type 1 enclosure for indoor protection against solid objects
  • Passive harmonic filter for standard voltage distortion correction
  • No integrated contactor; standalone harmonic mitigation solution

Specifications

Frequency
60 Hz
Poles
3 Phase
Series
HGP
Voltage Rating
480 VAC
HGP, 480V, 100HP, 3 Phase

HGP0100AW0S0000

HGP, 480V, 100HP, 3 Phase
HGP, 240V, 50HP, 3 Phase

HGP0050BW0C1000

HGP, 240V, 50HP, 3 Phase
HGP, 208V, 60HP, 3 Phase

HGP0060DW1C1000

HGP, 208V, 60HP, 3 Phase
HGP, 600V, 60HP, 3 Phase

HGP0060CW0C0000

HGP, 600V, 60HP, 3 Phase
HGP, 240V, 60HP, 3 Phase

HGP0060BW3C1000

HGP, 240V, 60HP, 3 Phase
HGP, 240V, 50HP, 3 Phase

HGP0050BW3C1000

HGP, 240V, 50HP, 3 Phase
HGP, 240V, 25HP, 3 Phase

HGP0025BW3C1000

HGP, 240V, 25HP, 3 Phase
HGP, 480V, 40HP, 3 Phase

HGP0040AW0C0000

HGP, 480V, 40HP, 3 Phase

Frequently Asked Questions

What is the THID performance of the HGP filter?

The HGP filter limits total harmonic current distortion to less than 5% at full load and less than 8% at 30% load.

What voltage options are available for the HGP filter?

The filter is available for 208, 240, 480, 600 VAC at 60Hz and 380-415 VAC at 50Hz.

What is the SCCR rating for the HGP filter?

The HGP filter has a true 100 kA SCCR rating, ensuring IEEE-519 2022 compliance.

What are the communication options for the HGP filter?

The filter supports Modbus RTU over RS485 and EtherNet/IP for communication and data analytics.

What voltage and frequency options are available for the HGP filter?

The filter supports 208, 240, 480, 600 VAC at 60Hz and 380-415 VAC at 50Hz.

What is the efficiency of the HGP filter?

The efficiency of the HGP filter is greater than 99%.

What is the overload capability of the HGP filter?

The filter can handle 200% of its current rating for 3 minutes.

What agency approvals does the HGP filter have?

The HGP filter is cULus Listed, RoHS compliant, and FCC compliant.

What enclosure options are available for the HGP filter?

Available enclosure options include Open Chassis, UL Type 1, UL Type 3R, and UL Type 12.

What is the humidity limit for the HGP filter?

The HGP filter can operate in humidity up to 95% non-condensing.

Frequently Asked Questions about TCI

What environmental ratings do TCI products have?

TCI products feature robust environmental ratings across multiple standards, including UL 508A Type 1, 2, 3, 4, 4X, 12, and 13; CSA Type 1, 2, 3, 4, 4X, 12, and 13; and NEMA Type 1, 2, 3, 4, 4X, 12, and 13. Additionally, they meet IEC 60529 IP66 standards, providing exceptional protection against dust, water, and corrosive environments with operating temperatures ranging from -40°C to 130°C.

What industries and applications are TCI products used for?

TCI products are engineered for critical applications across multiple industrial sectors, including HVAC, metals manufacturing, elevators and escalators, marine and shipping, food processing, pulp and paper, and underground construction. Their TorqueDrive Series offers specialized solutions for diverse load types such as fans, pumps, compressors, conveyors, hoists, winders, and synchronized positioning applications, with specific product lines designed for high-performance environments requiring precise torque control, energy efficiency, and robust environmental resistance.

What are the main product lines offered by TCI?

TCI offers four primary product lines: Harmonic Solutions, Motor Protection Solutions, Power Factor Correction Solutions, and High Frequency Noise Solutions. These comprehensive product lines include advanced technologies like HarmonicGuard® Active and Passive Filters, MotorGuard™ Sine Wave Output Filters, PF Guard Capacitor Banks, and KRF 3-Phase EMC Power Line Filters designed for industrial automation and electrical system optimization.

What are the key features of TCI products?

TCI products feature advanced harmonic mitigation solutions including HarmonicGuard® Active and Passive Filters, specialized line and load reactors, and power factor correction technologies. Key capabilities include integrated EMC design, high-endurance capacitors capable of handling 190% rated current, and solutions specifically engineered for harmonically-rich industrial environments like manufacturing facilities, water treatment plants, and facilities with variable frequency drives.

What certifications and standards do TCI products comply with?

TCI products are certified to meet critical North American standards including UL (Underwriters Laboratories) and CSA (Canadian Standards Association) certifications. Our products comply with rigorous safety and performance requirements for industrial automation equipment, with UL Listed Product and Recognized Component classifications ensuring high-quality manufacturing and reliability across multiple industrial applications.

What is TCI's warranty policy?

TCI offers a Limited Warranty policy that requires customers to obtain a Return Material Authorization (RMA) number before returning any products. Returns must be submitted within 30 days of the initial return request to TCI's Germantown, Wisconsin facility. All returned goods are subject to inspection, and restocking charges may apply. Customers should contact TCI's Customer Service for specific warranty details and return instructions.

What communication protocols do TCI products support?

TCI products support a comprehensive range of industrial communication protocols, including PROFIBUS DP V1, PROFINET with dual port, EtherNet/IP with dual port, CANopen, and Modbus RTU. These protocols enable flexible network integration, high-performance communication, and seamless connectivity with major PLC systems across diverse industrial automation environments.

What accessories are available for TCI products?

TCI offers a comprehensive range of communication and bus accessories for industrial automation systems. Key accessories include communication terminal boards (CTB810, CTB811), horizontal and vertical bus extenders (cHBX01L/R, HBX01L/R, VBX01T/B), and bus terminators (TER800, TER810). These accessories support connection, power distribution, and signal integrity for HN800 and CW800 device networks, enabling flexible and robust system configurations.

How are TCI products typically installed?

TCI products are typically installed by trained, manufacturer-certified technicians following a comprehensive commissioning process. Installation involves critical steps including work environment inspection, electrical installation checks, internal and external equipment verification, system power-up, and comprehensive operational testing. Authorized installation personnel ensure compliance with industry standards, complete factory acceptance tests, and provide a conformity certificate to guarantee safe and reliable system integration.