Contact for Pricing
Overview
- Output: 48 VDC at 5 A (240 W)
- Input: 115/230 VAC, single-phase, 47-63 Hz
- DIN rail mounting for compact panel integration
- Overload and short-circuit protection
- High efficiency with low heat dissipation
Specifications
Amperage Rating | 3.8 AMP |
Application | Industrial Control, Process Control, Machine Control, Building Automation, Instrumentation |
Brand Name | SolaHD |
Cable Size | 16 - 10 AWG Solid AWG |
Efficiency | 88 PCT |
Enclosure | Nema 4X, IP66/67 |
Environmental Conditions | 110 RH Humidity Range PCT |
Frequency Rating | 50/60/400 HZ |
Fuse Rating | Non-Replicable Internal Fuse |
Height | 1.8 IN |
Length | 6.54 IN |
Material | Metal Housing |
Mounting | Chassis with tabs |
Number Of Receptacles | 2 |
Phase | 1 |
Receptacle Configuration | Input/3 Pole Male - Output 4 Pole Female |
Special Features | IP66/67 Versatile/NEMA 4X Rated, 24 Vdc, 115/230 Vac, 3.8A Nominal Current, Listed power supply for stand-alone applications, Can be mounted in any orientation without limitation, Universal input, High ambient temperature up to 60oC without derating, DC OK Green LED. |
Standard | cULus Listed Ind. Control Equipment, E61379, ITE, E137632, UL 508, CSA C22.2 No. 107.1, UL 60950-1/CSA C22.2 No. 60950-1, 2nd Edition, UL Recognized Component Haz. Loc. E234790; CE Low Voltage Directive IEC/EN60950-1, 2nd Edition, RoHS Compliant |
Type | SCP-X Extreme Environment Series |
Voltage Rating | 24 Vdc |
Wattage | 95 WAT |
Width | 5.33 IN |
Package Dimensions (L x W x H) | 7.5 IN x 7 IN x 4 IN |
Package Dimensions (L x W x H) | 19.05 cm x 17.78 cm x 10.16 cm |
Package Weight (Imperial) | 3.300 L |
Package Weight (Metric) | 1.497 kg |

3085
Super-Safeway® Multiple Outlet Box, Extended Depth, 2-Sided, F2 (1/2") Cord Grip Body, with Flip Lids for (2) Duplex Not Included
ACS380-040S-07A2-4
ACS380 AC Drive, 3-380-480V In, 3HP, 6A, Type OPEN, 1.5 overload, Integrated, HxWxD 6.69x2.76x7.52 in, Module
1SNK705010R0000
Combine high performance with compact dimensions: - 1000 V AC / DC IEC 600 V UL, - Opt for the best marking visibility thanks to the up-front, flat marker zone, which lets you mark up to eight digits or increase the font size.
XT2NU3090BFF000XXX
C.BREAKER TMAX XT2N 125 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 90 I3=450...900 A
NNC75X75WH2
The NNC75X75WH2 Halogen-Free Wide Slot Wiring Duct is used to route, protect, and manage wires near sensitive electronic equipment and in environments where heat resistance or public safety is a concern. UL 94 flame class of V-0 with a UL recognized continuous-use temperature up to 95 C (203 F). Halogen-Free, Polyphenylene Oxide (PPO). Mounting holes provided. 2.85" x 2.97" (72.4 mm x 75.4 mm) and 6.6' (2 m) long. Cover included. Color White. 5 pieces per package.Frequently Asked Questions
What is the nominal output voltage of the SDN 5-48-100P?
The nominal output voltage is 48 Vdc, adjustable from 35.8 to 52 Vdc.
What is the input voltage range for the SDN 5-48-100P?
The AC input range is 85-132/176-264 Vac, with auto-select 115/230 Vac nominal. A DC range of 210-375 Vdc is also supported, though not UL listed.
What is the operating temperature range for the SDN 5-48-100P?
The unit operates at full power from -10°C to +60°C. It can operate up to 70°C with linear derating to half power.
Can the SDN 5-48-100P be used in parallel operation?
Yes, the SDN 5-48-100P supplies will not be damaged with parallel operation.
What type of mounting is supported for the SDN 5-48-100P?
It supports simple snap-on mounting to DIN TS35/7.5 or TS35/15 rail systems. Optional chassis mounting is available with the SDN-PMBRK2 accessory.
What are the required free space clearances for installation?
For proper convection cooling, 70 mm free space is required above and below, 25 mm left and right, and 15 mm in front.
What is the nominal output current and power for this model?
The nominal output current is 5 A, providing 240 W of power.
Does the SDN 5-48-100P have overvoltage protection?
Yes, it has overvoltage protection set at < 60 Vdc with auto-recovery.
What is the warranty period for the SDN 5-48-100P?
The SDN 5-48-100P comes with a 5-year limited warranty.
What safety protections are included in the SDN 5-48-100P?
It is protected against continuous short-circuit, continuous overload, and continuous open circuit. It is Protection Class I and Degree of Protection IP20.
Frequently Asked Questions about SolaHD
What certifications and standards do SolaHD products comply with?
SolaHD power supplies are UL 508 Listed for Industrial Control Equipment and comply with multiple international standards, including UL 60950, CUL/CSA-C22.2 No. 234-M90, and IECEx certifications. Our products meet EMC and Low Voltage Directives, with extensive hazardous location certifications including Class I Zone 2, ATEX, and IECEx, ensuring reliable performance in industrial environments.
What industries and applications are SolaHD products used for?
SolaHD products are used across a wide range of critical industrial applications, including factory automation, process control, machine control, material handling, building automation, and harsh environment installations. Key industries include manufacturing, process industries, semiconductor fabrication, packaging, conveying equipment, instrumentation, and environments requiring UL508 compliance such as water treatment facilities. The products are specifically designed for challenging industrial settings, with certifications for hazardous locations and extreme temperature ranges.
What technical support does SolaHD offer?
SolaHD offers comprehensive technical support through experienced sales representatives available worldwide. Our support includes expert consultation for selecting the right power quality solutions, with award-winning online tools to help customers make precise product selections. Technical support covers the entire range of our industrial power solutions, from service entrance protection to point-of-use equipment, ensuring customers can optimize their facility's power infrastructure.
What are the main product lines offered by SolaHD?
SolaHD offers a comprehensive range of industrial power quality solutions across five primary product lines: Power Supplies, Surge Protection Devices (SPDs), Transformers, Power Conditioning, and Uninterruptible Power Supplies (UPS). Key product series include SDN Power Supplies, STV/STFV Surge Protective Devices, Industrial Control Transformers, MCR Constant Voltage Conditioners, and SDU UPS systems designed for industrial automation, process control, and critical manufacturing environments.
What are the key features of SolaHD products?
SolaHD products offer comprehensive industrial power quality solutions that convert, clean, and maintain electric current throughout manufacturing facilities. Key features include noise and surge protection, voltage regulation, drive protection, and uninterruptible power supplies (UPS). Their product lines cover everything from service entrance to point-of-use, with compact DIN rail mountable options that provide flexible, space-saving power solutions for sensitive industrial equipment like PLCs, networks, and control systems.
What environmental ratings do SolaHD products have?
SolaHD products feature robust environmental ratings including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 classifications, as well as IP66 protection. These ratings ensure comprehensive protection against dust, water, and corrosion in both indoor and outdoor environments, with operating temperatures ranging from -40°C to 130°C.
What accessories are available for SolaHD products?
SolaHD offers a comprehensive range of accessories across multiple product lines, including surge protective devices (SPD), tracking filters, power supplies, UPS systems, and DIN rail mountable components. Key accessories include the STV100K Surge Protective Device, STFV Plus Series Tracking Filters, SDN and SCP Series Power Supplies, SDU Series UPS, and various DIN rail filters and converters that can be integrated into industrial control panels and power systems.
How are SolaHD products typically installed?
SolaHD products are typically installed on DIN rail mounting systems in industrial control panels, with multiple installation options including panel/wall mounting brackets. Most products feature easy-to-wire screw terminations, making them suitable for critical industrial applications like factory automation, PLCs, robotics, and computer-based control systems. The products are designed for flexible installation across various industrial environments, with wide operating temperature ranges from -20°C to +50°C and compact, rugged industrial designs.