Mersen A100C60-30 Medium Voltage Capacitor Fuse 1000VAC 60A Female Stud To L Bracket Visual Indicator…
Alternate Item Number: A100C60-30
UPC: 782001349134
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Medium Voltage Capacitor Fuse (1000VAC, 60A)
- Current-limiting and provides short circuit/overload protection
- Visual indicator for blown-fuse status
- Designed to ANSI C37-41 standards
- Female stud to L bracket mounting configuration
Specifications
AC Voltage Rating | 1000 V |
Amperage Rating | 60 A |
Application | Protection of capacitors Power Factor Correction Equipment Harmonic Filtering Equipment Induction Heating System High Power Drive Welder |
Body Material | GMG |
Brand Name | Mersen |
Connection | Female Stud To L Bracket |
Connection Material | Tin-Plated Brass |
Interrupt Rating | 50 kA |
Interrupt Rating | 40 kA |
Mounting | Direct Mount |
Size | 6.38 x 1.1;162.052 x 27.94 in;mm |
Special Features | High interrupting capacity Current-limiting Blown fuse indicator Direct mounting Clip style mounting Bus mounting Non-venting for silent operation |
Standard | ANSI C37-41 |
Standard | ANSI |
Sub Brand | Amp-Trap® |
Type | Capacitor Protection Fuses |
Type of Indicators | Visual Indicator |
Voltage Rating | 1500 VAC |
Package Dimensions (L x W x H) | 6.38 in x 1.25 in x 1.24 in |
Package Dimensions (L x W x H) | 162.052 mm x 31.75 mm x 31.496 mm |
Package Weight (Imperial) | 0.750 lb |
Package Weight (Metric) | 0.340 kg |

GPM-SRR90
Fuse Block 600VAC 600VDC Class CC 30A 1/4in Quick Connect / Solder 90 angle screw Knob Panel Mount
C331156
Fuse Holder UltraSafe™ 800VAC 1000VDC UL Fuse size 14x51 1-Pole Visual Indicator Microswitch Pressure Plate IP20
LCC5
POWR-JAW clamps improve the contact between fuse and clip. The unnecessary heat from poor contact due to the loss of spring force in the clips can cause nuisance fuse opening and premature aging of surrounding components. High temperature phenolic resin knob designed for the most severe environments 7 sizes to provide effective coverage. Simple design makes installation easy.Frequently Asked Questions
What is the melting I2t for the A100C60-30 fuse?
The melting I2t for the A100C60-30 fuse is 25 kA2s.
What is the maximum clearing I2t for the A100C60-30 fuse?
The maximum clearing I2t for the A100C60-30 fuse is 60 kA2s.
What is the maximum AC voltage for A100C fuses?
The A100C series capacitor fuses have a maximum AC voltage rating of 1000V.
What is the interrupting rating for A100C60-30 fuses?
The A100C60-30 fuse has an interrupting rating of 50 kA at 1000V RMS Sym.
Are Mersen capacitor fuses self-disconnecting?
No, these are non-disconnecting fuses and require the use of a separate disconnect switch.
What protection do these capacitor fuses provide?
They provide both short circuit and overload protection, and protect against capacitor case rupture or dielectric failure.
What are the dimensions of the A100C60-30 fuse?
The A100C60-30 fuse has an overall length of 6.38 inches (162.1 mm) and a body diameter of 1.10 inches (27.9 mm).
Do these fuses operate with noise or discharge?
These fuses are designed for non-venting, silent operation without noise or discharge.
What type of enclosure is suitable for these capacitor fuses?
These fuses can be used indoors in a general purpose enclosure or outdoors in a weatherproof enclosure.
What are the available ampere ratings for A100C fuses?
The A100C series fuses are available in ampere ratings from 25 A to 125 A.
Frequently Asked Questions about Mersen
What industries and applications are Mersen products used for?
Mersen products are used across diverse industrial sectors including solar power, electric vehicles, buildings/construction, industrial automation, power distribution, HVAC, elevators, telecommunications, and specialty manufacturing. Key application areas include circuit protection, surge protection, battery module protection, electrical safety systems, and power management for residential, commercial, and utility-scale installations.
What are the main product lines offered by Mersen?
Mersen offers five primary electrical power product lines: IEC and UL/CSA Fuses and Fusegear, Surge Protection, Low Voltage Disconnect Switches, Power Distribution Blocks, and Engineered Solutions. Their comprehensive range includes specialized components like high-speed fuses, modular fuse holders, surge arresters, and custom-engineered electrical protection systems for industrial and power management applications.
What are the key features of Mersen products?
Mersen products feature advanced electrical protection and power management solutions with key characteristics including finger-safe design, compact modularity, and high-performance safety features. Their product lines span electrical power components like fuses, surge protection, power distribution blocks, and specialized solutions for industrial, solar, and building applications. Critical features include UL/CSA approvals, high short-circuit current ratings, and innovative technologies like the Fuse Control™ program that minimize electrical risks and optimize system performance.
What environmental ratings do Mersen products have?
Mersen products meet rigorous environmental ratings across multiple standards, including UL 508A Type 1, 2, 3, 4, 4X, 12, and 13, CSA Type 1, 2, 3, 4, 4X, 12, and 13, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13. They feature IEC 60529 IP66 protection, with enhanced UV inhibitors for outdoor weathering and operating temperatures ranging from -40°C to 130°C (-40°F to 266°F). These ratings ensure superior protection in wet, corrosive, and challenging industrial environments.
What accessories are available for Mersen products?
Mersen offers multiple accessories for their fuse blocks and systems, including safety pullers (DFC3M and DFC3LP), DIN-rail adapters (DRM), bus bars, auxiliary contacts, and specialized mounting hardware. Key accessories include the DFC3M safety puller for 1-1/2" x 13/32" midget or Class CC fuses, the DRM adapter for mounting 303 series fuse blocks on DIN-rail, and UltraSafe fuse module accessories like bus bars and auxiliary contacts that enable module interconnection and monitoring.
How are Mersen products typically installed?
Mersen products are typically installed in electrical distribution systems, control panels, and industrial automation environments using multiple mounting options. These include service entrance panel mounting, distribution panel installation, control panel DIN rail mounting, and custom engineered solutions like Fused Coordination Panelboards. Installation depends on the specific product type, such as fuses, surge protective devices, or switches, and is designed to provide electrical protection and circuit safety in various industrial and commercial applications.
What certifications and standards do Mersen products comply with?
Mersen products are certified to multiple international standards, including UL (Underwriters Laboratories), CSA (Canadian Standards Association), CCC (China Compulsory Certification), and EAC (Eurasian Conformity). Our products meet rigorous safety and performance standards for industrial applications across North America, China, Russia, and other global markets, ensuring compliance and reliability in electrical power and advanced materials solutions.
What technical support does Mersen offer?
Mersen provides comprehensive technical support through multiple channels, including technical experts located in your time zone who can assist with product selection, application guidance, and troubleshooting. Their Fuse Control™ program offers a free Fuse Inventory Audit & Analysis, and customers can access technical resources through their sales representatives and online platform ep.mersen.com.