Mersen 9F61CGL310 - Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-3D CGL series.
Mersen

9F61CGL310

Alternate Item Number: 9F61CGL310

UPC: 782001398743


Documents & Media
Line Drawing

Contact for Pricing

Overview

The Mersen 9F61CGL310 is an EKO-3D series outdoor fuse support designed for medium voltage applications up to 15.5kV. This non-disconnecting fuse support is primarily utilized in potential transformer circuits or in series with other disconnecting or isolating devices. It is crucial to note that while disconnecting switch devices offer isolation, they are not load-breaking and require the circuit to be open before fuse disconnection. The EKO series is specifically engineered for outdoor installations, providing robust protection in exposed environments. This model accommodates fuses with a 3-inch ferrule diameter and is suitable for vertical or horizontal mounting. The 9F61CGL310 includes live parts for both ends, ensuring secure contact. For applications requiring isolation, Mersen also offers disconnecting switch devices. When selecting a fuse support or disconnect switch, ensure the clip centers and size precisely match the fuse specifications. Mersen's commitment to quality and safety is evident in their comprehensive range of fuse supports and disconnect switches, designed to meet the stringent requirements of medium voltage power systems. This unit is manufactured in the USA.
  • Mersen EKO-3D Series Outdoor Fuse Support
  • Rated for 15.5kV applications
  • Accommodates 3-inch ferrule diameter fuses
  • Suitable for vertical or horizontal mounting
  • Designed for outdoor installations

Specifications

AC Voltage Rating
15.5 kV
Application
Utilities Industrial Plants Hospitals Shopping Centers Schools Office Buildings
Brand Name
Mersen
Connection
Bus
Material
Porcelain
Mounting
Screw
Mounting Type
Vertical or Horizontal
Series
CGL
Size
24 x 4 x 32.5 in
Size
609.6 x 101.6 x 825.5 mm
Type
IEEE MV Fuse Supports
Voltage Rating
15500 VAC
Package Dimensions (L x W x H)
24 in x 4 in x 32.5 in
Package Dimensions (L x W x H)
609.6 mm x 101.6 mm x 825.5 mm
Package Weight (Imperial)
30.000 lb
Package Weight (Metric)
13.608 kg
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-1C CGL series.

9F61CGL209

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-1C CGL series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-1D CGL series.

9F61CGL309

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-1D CGL series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-3C CGL series.

9F61CGL210

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-3C CGL series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-1DD CGL series.

9F61CGL409

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-1DD CGL series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-3DD CGL series.

9F61CGL410

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15500 Volts EKO-3DD CGL series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15550 Volts CGN series.

9F61CGN210

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 15550 Volts CGN series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-1C CEF series.

9F61CEF209

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-1C CEF series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-3C CEF series.

9F61CEF210

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-3C CEF series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-3D CEF series.

9F61CEF310

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-3D CEF series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-3DD CEF series.

9F61CEF410

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-3DD CEF series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-1DD CEF series.

9F61CEF409

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-1DD CEF series.
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-1D CEF series.

9F61CEF309

Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors. 8250 Volts EKO-1D CEF series.

Frequently Asked Questions about Mersen

What industries and applications are Mersen products used for?

Mersen products are used across diverse industrial sectors including solar power, electric vehicles, buildings/construction, industrial automation, power distribution, HVAC, elevators, telecommunications, and specialty manufacturing. Key application areas include circuit protection, surge protection, battery module protection, electrical safety systems, and power management for residential, commercial, and utility-scale installations.

What are the main product lines offered by Mersen?

Mersen offers five primary electrical power product lines: IEC and UL/CSA Fuses and Fusegear, Surge Protection, Low Voltage Disconnect Switches, Power Distribution Blocks, and Engineered Solutions. Their comprehensive range includes specialized components like high-speed fuses, modular fuse holders, surge arresters, and custom-engineered electrical protection systems for industrial and power management applications.

What are the key features of Mersen products?

Mersen products feature advanced electrical protection and power management solutions with key characteristics including finger-safe design, compact modularity, and high-performance safety features. Their product lines span electrical power components like fuses, surge protection, power distribution blocks, and specialized solutions for industrial, solar, and building applications. Critical features include UL/CSA approvals, high short-circuit current ratings, and innovative technologies like the Fuse Control™ program that minimize electrical risks and optimize system performance.

What environmental ratings do Mersen products have?

Mersen products meet rigorous environmental ratings across multiple standards, including UL 508A Type 1, 2, 3, 4, 4X, 12, and 13, CSA Type 1, 2, 3, 4, 4X, 12, and 13, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13. They feature IEC 60529 IP66 protection, with enhanced UV inhibitors for outdoor weathering and operating temperatures ranging from -40°C to 130°C (-40°F to 266°F). These ratings ensure superior protection in wet, corrosive, and challenging industrial environments.

What accessories are available for Mersen products?

Mersen offers multiple accessories for their fuse blocks and systems, including safety pullers (DFC3M and DFC3LP), DIN-rail adapters (DRM), bus bars, auxiliary contacts, and specialized mounting hardware. Key accessories include the DFC3M safety puller for 1-1/2" x 13/32" midget or Class CC fuses, the DRM adapter for mounting 303 series fuse blocks on DIN-rail, and UltraSafe fuse module accessories like bus bars and auxiliary contacts that enable module interconnection and monitoring.

How are Mersen products typically installed?

Mersen products are typically installed in electrical distribution systems, control panels, and industrial automation environments using multiple mounting options. These include service entrance panel mounting, distribution panel installation, control panel DIN rail mounting, and custom engineered solutions like Fused Coordination Panelboards. Installation depends on the specific product type, such as fuses, surge protective devices, or switches, and is designed to provide electrical protection and circuit safety in various industrial and commercial applications.

What certifications and standards do Mersen products comply with?

Mersen products are certified to multiple international standards, including UL (Underwriters Laboratories), CSA (Canadian Standards Association), CCC (China Compulsory Certification), and EAC (Eurasian Conformity). Our products meet rigorous safety and performance standards for industrial applications across North America, China, Russia, and other global markets, ensuring compliance and reliability in electrical power and advanced materials solutions.

What technical support does Mersen offer?

Mersen provides comprehensive technical support through multiple channels, including technical experts located in your time zone who can assist with product selection, application guidance, and troubleshooting. Their Fuse Control™ program offers a free Fuse Inventory Audit & Analysis, and customers can access technical resources through their sales representatives and online platform ep.mersen.com.