Hammond Power TE3A0093NNM - 600V Class Three Phased DOE2016 and NRCan 2019 Compliant Energy Efficient Drive Isolation Transformer 93kVA 575D-575Y/332V CU 60Hz 3R
Hammond Power

TE3A0093NNM

UPC: 803423145507


Documents & Media
BrochureSpecification Sheet

Contact for Pricing

Overview

The Hammond Power TE3A0093NNM is a 93kVA, 600V class, three-phase drive isolation transformer engineered for compliance with DOE2016 and NRCan 2019 energy efficiency standards. This unit features a 575D primary winding and a 575Y/332V secondary winding, operating at a frequency of 60Hz. Its copper-wound construction minimizes energy losses and enhances thermal efficiency, contributing to reduced operational costs. Designed specifically for variable frequency drive (VFD) systems, this transformer provides essential isolation to protect sensitive equipment from harmonic distortions and voltage fluctuations, thereby extending the service life of connected machinery. The transformer is housed in a 3R enclosure, making it suitable for indoor or outdoor installation in non-hazardous locations. Manufactured in the USA, the TE3A0093NNM (SKU: TE3A0093NNM) utilizes UL-listed components to ensure consistent and reliable performance in demanding industrial settings. Its robust design and adherence to stringent energy regulations make it a practical choice for modern industrial power distribution.
  • 93kVA, 600V Class, Three-Phase Drive Isolation Transformer
  • DOE2016 and NRCan 2019 Energy Efficient Compliant
  • 575D Primary to 575Y/332V Secondary Voltage Configuration
  • Copper Wound Construction for Low Losses and High Efficiency
  • 3R Enclosure for Indoor/Outdoor Non-Hazardous Location Use

Specifications

Application
Variable Speed Drives.
Connection Type
575D-575Y/332V
Connection Type
Delta-Wye
Current Rating
93kVA
Efficiency
NRCan 2018 Energy Efficient
Enclosure
DH3-N3R - Indoor or Outdoor
Enclosure Colour
ANSI 61 Grey, UL50
Enclosure Type
3R
Frequency
60Hz
Frequency
60 Hz
Frequency Rating
60 HZ
Height
36 in
Insulation Class
220 Deg C Class
KVA Rating
93 KVA
Length
27 IN
Material
Copper
Material
CU
Mounting
Floor or Wall mount
Mounting Method
Floor
NEMA Frame Size
Type 3R
NEMA Rating
3R
Number Of Phases
3
Phase
3PH
Poles
3
Primary Voltage
575D V
Secondary Voltage
575Y/332V
Series
TE3A
Size
93kVA
Sound Level dBA
Meets NEMA ST-20 standards
Special Features
Meets NRCan 2018 efficiencies and designed to meet rugged demands of both AC and DC variable speed drives and alos to provide the required voltage change. Comes standard in an outdoor enclosure and a thermal warning switch.
Standard
CSA, UL
Temperature Rating
Typical 30 Average/ 40 Maximum Deg C
Temperature Rise
150 °C
Transformer Rating
93kVA
Type
Transformers > Drive Isolation > NRCan 2018 Energy Efficient
Voltage Rating
600V
Voltage Rating
575D-575Y/332V
Wall Mounting
No
Warranty
10 year warranty
Weight
750 L
Width
28.3 IN
Winding
Copper
Package Dimensions (L x W x H)
27 IN x 28.3 IN x 36 IN
Package Dimensions (L x W x H)
68.58 cm x 71.882 cm x 91.44 cm
Package Weight (Imperial)
750.000 L
Package Weight (Metric)
340.200 kg
600V Class Three Phased DOE2016 and NRCan 2019 Compliant Energy Efficient Drive Isolation Transformer 93kVA 480D-380Y/220 V CU 60Hz 3R

TE3A0093KGM

600V Class Three Phased DOE2016 and NRCan 2019 Compliant Energy Efficient Drive Isolation Transformer 93kVA 480D-380Y/220 V CU 60Hz 3R
Drive Isolation Transformer, 93 kVA, Drive Horse Power 75, 460 Delta Primary, 460Y/266 Secondary, 60 HZ , cULus Listed: E7014, UL 506, CSA C22.2No.66, UL Listed E25872, UL1561

DT651H93S

Drive Isolation Transformer, 93 kVA, Drive Horse Power 75, 460 Delta Primary, 460Y/266 Secondary, 60 HZ , cULus Listed: E7014, UL 506, CSA C22.2No.66, UL Listed E25872, UL1561
ABB's Guard I&trade, Noise Isolation Transformers provide common mode noise signal between neutral and ground and transverse mode noise protection. Common mode noise is caused by electromagnetic interference, radio interference and ground loops.

9T10A1004G63

ABB's Guard I&trade, Noise Isolation Transformers provide common mode noise signal between neutral and ground and transverse mode noise protection. Common mode noise is caused by electromagnetic interference, radio interference and ground loops.

Frequently Asked Questions about Hammond Power

What certifications and standards do Hammond Power products comply with?

Hammond Power products are certified to UL (Underwriters Laboratories) and CSA (Canadian Standards Association) standards in North America. Our products meet rigorous safety and performance requirements, with many items classified as UL Listed Products or Recognized Components. We also comply with international certifications including China Compulsory Certification (CCC), C-Tick for Australian EMC requirements, and ANCE for Mexico.

What is Hammond Power's warranty policy?

Hammond Power provides a standard one-year warranty on all products, covering defects in workmanship and materials. Products will be repaired or replaced free of charge if found defective upon factory inspection. The warranty does not cover damage from improper handling, incorrect application, or faulty installation.

What industries and applications are Hammond Power products used for?

Hammond Power products are engineered for critical industrial and commercial applications across multiple sectors, including petrochemical, mining, construction, renewable energy, e-mobility, power storage, and microgrids. Their comprehensive product range of dry-type transformers, power quality solutions, and magnetic components enables electrical distribution and electrification in diverse industrial environments worldwide.

What are the main product lines offered by Hammond Power?

Hammond Power Solutions offers a comprehensive range of dry-type and liquid-filled transformers for industrial and commercial applications. Their primary product lines include power transformers for renewable energy, e-mobility, data centers, microgrids, and industrial settings. The company provides both standard and custom-designed transformer solutions that are critical to electrical distribution networks across multiple industries.

What are the key features of Hammond Power products?

Hammond Power products feature advanced dry-type and liquid-filled transformers engineered for diverse industrial applications, with capabilities spanning renewable energy, e-mobility, data centers, microgrids, and industrial/commercial sectors. Key features include high-performance electrical steel laminations, windings available in copper or aluminum, advanced insulation systems (VPI or Cast Resin), Basic Impulse Level ranges from 10 kV to 250 kV, and custom design capabilities with over 3,000 unique transformer designs engineered annually.

What environmental ratings do Hammond Power products have?

Hammond Power offers industrial enclosures with comprehensive environmental ratings, including UL/cUL 508A ratings of Type 1, 2, 3, 4, 4X, 12, and 13. Their products meet IEC 60529 IP66 standards, providing robust protection against dust, water ingress, and harsh environmental conditions. Specific ratings vary by product series, with options ranging from indoor Type 1 enclosures to outdoor-rated Type 4X enclosures suitable for challenging industrial environments.

What technical support does Hammond Power offer?

Hammond Power Solutions provides comprehensive technical support through multiple channels. Customers can access technical resources via phone support in Canada, the United States, Mexico, and internationally, with toll-free numbers and regional contact points. Their technical team offers personalized assistance for custom design inquiries, helping customers find standard transformer and power solutions or develop specialized electrical products for various industrial applications.

What communication protocols do Hammond Power products support?

Hammond Power products support multiple industrial communication protocols, including Modbus RTU, PROFIBUS DP, PROFINET, EtherNet/IP, and CANopen. These protocols enable flexible connectivity across industrial automation platforms, supporting various network topologies and high-speed data transmission for comprehensive industrial control and monitoring applications.

What accessories are available for Hammond Power products?

Hammond Power offers a comprehensive range of accessories for industrial electrical components, including HME Series handles with key locking and padlocking options, door stop kits, light kit mounting brackets, and standard hardware like mounting screws and washers. These accessories are designed to enhance functionality and installation flexibility across their product lines.

How are Hammond Power products typically installed?

Hammond Power transformers are typically chassis-mounted using precise mounting hole centers and dimensions specific to each product series. Installation involves selecting the appropriate primary voltage configuration, securing the transformer to a mounting surface using the specified mounting holes, and connecting terminals according to the product's schematic. Most Hammond Power transformers feature multiple terminal options like solder or quick-connect terminals, allowing flexible and straightforward installation in industrial control and power distribution applications.