Authorized Hammond Power Distributor
Hammond Power SH3U0150KB3S - 600V Class Three Phase DOE2016 and NRCan 2019 Compliant Energy Efficient Harmonic Mitigating Transformer, 480YD PV, 208Y/120 SV, 150 kVA, 3PH, Aluminum Wound, Shielded, -30 Deg Phase Shift

Hammond Power SH3U0150KB3S 600V Class Three Phase DOE2016 and NRCan 2019 Compliant Energy Efficient Harmonic…

UPC: 803423135065


Documents & Media
BrochureTechnical BulletinSpecification Sheet

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The Hammond Power SH3U0150KB3S is a 150 kVA, three-phase, energy-efficient harmonic mitigating transformer engineered to address power quality challenges in modern industrial and commercial facilities. Primary voltage is rated at 480Y/277 VAC, while the secondary output is configured for 208Y/120V, making it ideal for facilities requiring clean power distribution to sensitive equipment. The transformer features a -30° phase shift, which actively cancels zero-sequence currents and mitigates 5th and 7th harmonics upstream, reducing system stress and preventing issues like overheating, equipment malfunction, and premature failure. Constructed with high-grade, non-aging silicon steel laminations and continuous aluminum windings, the SH3U0150KB3S ensures efficient current transfer and reduced weight compared to copper alternatives. The unit is vacuum pressure impregnated for enhanced durability and insulation integrity, with a temperature rise rating of 150°C and an insulation class of 220°C. Secondary neutral connections are rated at 200% of the rated secondary phase current, providing robust support for unbalanced loads. With in-rush currents limited to 15 times RMS, this transformer minimizes startup stress on electrical systems. Its shielded design further reduces electromagnetic interference (EMI) and noise, ensuring clean power delivery to connected equipment.
  • Typical applications of HPS harmonic mitigating transformers include data centers, internet-service providers, telecom sites, call centers, broadcast centers, etc.
  • Superior to K-rated and conventional transformers in reducing voltage distortion and power losses due to current harmonics created by single-phase, non-linear loads.
  • Combining zero sequence flux cancellation with phase shifting treats 3rd, 5th, 7th, 9th, 15th, 17th and 19th, harmonics within its secondary windings.
  • Secondary neutral rated at 200% of phase current for unbalanced loads
  • Shielded Design with -30 Deg Phase Shift

Specifications

Application
Mitigate and cancel harmonics without filters to improve power quality for non-linear loads.
Cable Entry
Knock Outs
Connection Type
480YD (Primary) / 208Y/120 (Secondary)
Current Rating
416 A
Depth
29.5 IN
Efficiency
DOE 2016 Energy Efficient
Enclosure
DH4-N3R - Indoor or Outdoor
Enclosure Color
ANSI 61 Grey, UL 50
Enclosure Type
Type 3R
Frequency
60 Hz
Frequency Rating
60 HZ
Height
44.5 in
Height
1130.3 mm
Impedance
Typically 1.8% to 7.5%
Insulation Class
220°C
K Factor
13
KVA Rating
150 KVA
Length
29.5 in
Material
Aluminum
Mounting
Floor Mount
Mounting Method
Floor
Number Of Phases
3
Phase
3 Ph PH
Phase
U - 3PH Wye Zig Zag- -30°PH Shift
Primary Voltage
480Y D V
Primary Voltage
480 VAC
Secondary Voltage
208Y/120 V
Series
SH3U
Size
150 kVA
Sound Level dBA
Meets NEMA ST-20 standards
Special Features
Meets current DOE 10 CFR part 431 (2016) and C802.2 efficiencies in an outdoor type enclosure. Smaller kVA sizes have standard input and/or output lugs, knockouts, and wall mounting brackets to save installation costs.
Standard
CSA, UL
Temperature Rating
Typical 30 Average/ 40 Maximum Deg C
Temperature Rise
150°C
Termination
Mechanical Lugs
Transformer Rating
150kVA
Type
Transformer > Distribution > DOE 2016 Energy Efficient > Harmonic Mitigating > Three Phase
Voltage Rating
480Y/277 VAC (Primary) / 208Y/120 VAC (Secondary)
Wall Mounting
No
Warranty
10 year warranty
Weight
985 L
Width
31.5 in
Width
800.1 mm
Winding
Copper
Winding
S - AL + Shield
Package Dimensions (L x W x H)
29.5 IN x 31.5 IN x 44.5 IN
Package Dimensions (L x W x H)
74.93 cm x 80.01 cm x 113.03 cm
Package Weight (Imperial)
1220.000 L
Package Weight (Metric)
553.392 kg
A - 15.0 kV bushing

015J0400AN

A - 15.0 kV bushing
O Plus C - 34.5 kV bushing

034Z3000AW

O Plus C - 34.5 kV bushing

Frequently Asked Questions

What is the primary and secondary voltage rating?

The primary voltage is 480Y/277 VAC and the secondary voltage is 208Y/120V.

What type of windings are used?

The transformer uses continuous aluminum windings for efficient current transfer and reduced weight.

Is the transformer shielded?

Yes, the transformer features a shielded design to minimize electromagnetic interference.

What is the core construction material?

The core is constructed from high-grade, non-aging, fully processed silicon steel laminations.

What is the phase shift of this transformer?

The SH3U0150KB3S has a -30° phase shift, which helps mitigate 5th and 7th harmonics.

What is the secondary neutral connection rating?

The secondary neutral connections are rated at 200% of the rated secondary phase current.

What is the maximum in-rush current?

In-rush currents do not exceed 15 times the RMS current.

What is the temperature rise rating?

The temperature rise rating is 150°C as per NEMA ST 20 standards.

What applications is this transformer suitable for?

It is suitable for facilities with non-linear loads such as VFDs, LED lighting, and switching power supplies.

What is the insulation class?

The insulation class is 220°C, ensuring high thermal endurance.

Frequently Asked Questions about Hammond Power

What certifications and standards do Hammond Power products comply with?

Hammond Power products are certified to UL (Underwriters Laboratories) and CSA (Canadian Standards Association) standards in North America. Our products meet rigorous safety and performance requirements, with many items classified as UL Listed Products or Recognized Components. We also comply with international certifications including China Compulsory Certification (CCC), C-Tick for Australian EMC requirements, and ANCE for Mexico.

What is Hammond Power's warranty policy?

Hammond Power provides a standard one-year warranty on all products, covering defects in workmanship and materials. Products will be repaired or replaced free of charge if found defective upon factory inspection. The warranty does not cover damage from improper handling, incorrect application, or faulty installation.

What industries and applications are Hammond Power products used for?

Hammond Power products are engineered for critical industrial and commercial applications across multiple sectors, including petrochemical, mining, construction, renewable energy, e-mobility, power storage, and microgrids. Their comprehensive product range of dry-type transformers, power quality solutions, and magnetic components enables electrical distribution and electrification in diverse industrial environments worldwide.

What are the main product lines offered by Hammond Power?

Hammond Power Solutions offers a comprehensive range of dry-type and liquid-filled transformers for industrial and commercial applications. Their primary product lines include power transformers for renewable energy, e-mobility, data centers, microgrids, and industrial settings. The company provides both standard and custom-designed transformer solutions that are critical to electrical distribution networks across multiple industries.

What are the key features of Hammond Power products?

Hammond Power products feature advanced dry-type and liquid-filled transformers engineered for diverse industrial applications, with capabilities spanning renewable energy, e-mobility, data centers, microgrids, and industrial/commercial sectors. Key features include high-performance electrical steel laminations, windings available in copper or aluminum, advanced insulation systems (VPI or Cast Resin), Basic Impulse Level ranges from 10 kV to 250 kV, and custom design capabilities with over 3,000 unique transformer designs engineered annually.

What environmental ratings do Hammond Power products have?

Hammond Power offers industrial enclosures with comprehensive environmental ratings, including UL/cUL 508A ratings of Type 1, 2, 3, 4, 4X, 12, and 13. Their products meet IEC 60529 IP66 standards, providing robust protection against dust, water ingress, and harsh environmental conditions. Specific ratings vary by product series, with options ranging from indoor Type 1 enclosures to outdoor-rated Type 4X enclosures suitable for challenging industrial environments.

What technical support does Hammond Power offer?

Hammond Power Solutions provides comprehensive technical support through multiple channels. Customers can access technical resources via phone support in Canada, the United States, Mexico, and internationally, with toll-free numbers and regional contact points. Their technical team offers personalized assistance for custom design inquiries, helping customers find standard transformer and power solutions or develop specialized electrical products for various industrial applications.

What communication protocols do Hammond Power products support?

Hammond Power products support multiple industrial communication protocols, including Modbus RTU, PROFIBUS DP, PROFINET, EtherNet/IP, and CANopen. These protocols enable flexible connectivity across industrial automation platforms, supporting various network topologies and high-speed data transmission for comprehensive industrial control and monitoring applications.

What accessories are available for Hammond Power products?

Hammond Power offers a comprehensive range of accessories for industrial electrical components, including HME Series handles with key locking and padlocking options, door stop kits, light kit mounting brackets, and standard hardware like mounting screws and washers. These accessories are designed to enhance functionality and installation flexibility across their product lines.

How are Hammond Power products typically installed?

Hammond Power transformers are typically chassis-mounted using precise mounting hole centers and dimensions specific to each product series. Installation involves selecting the appropriate primary voltage configuration, securing the transformer to a mounting surface using the specified mounting holes, and connecting terminals according to the product's schematic. Most Hammond Power transformers feature multiple terminal options like solder or quick-connect terminals, allowing flexible and straightforward installation in industrial control and power distribution applications.