Hammond Power DM063JC Drive isolation transformer, three-phase, 63 kVA, 460–230 Volts, aluminum windings.
UPC: 803423003395
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- The separate primary and secondary windings provide electrical isolation between the incoming line and the SCR load.
- The windings are designed to withstand overcurrent of 150% of the rated load for 60 seconds or 200% of the rated load for 30 seconds.
- Designed for AC and DC variable speed drives
- Rugged construction for industrial environments
Specifications
Application | Variable Speed Drives. |
Cooling | Convection cooled |
Enclosure | NH3-N3R - Indoor or Outdoor |
Enclosure Colour | ANSI 61 Grey, UL50 |
Frequency | 60 Hz |
Frequency Rating | 60 HZ |
Height | 38 in |
Height | 965.2 mm |
KVA Rating | 63 KVA |
Length | 21 IN |
Length | 25 in |
Length | 635 mm |
Mounting | Floor Mount |
Mounting Method | Wall and Floor |
Number Of Phases | 3 |
Number Of Taps | ST-20 compliant |
Phase | 3PH |
Primary Voltage | 460 V |
Secondary Voltage | 400 |
Secondary Voltage | 230Y V |
Sound Level dBA | Meets NEMA ST-20 standards |
Special Features | Designed to withstand overcurrent of 150% of the rated load for 60 seconds or 200% of the rated load for 30 seconds. Comes standard in an indoor/outdoor enclosure with a coil mounted thermal warning switch. |
Standard | CSA, UL |
Temperature Rating | Typical 30 Average/ 40 Maximum Deg C |
Temperature Rise | 115 Deg C |
Transformer Rating | 63kVA |
Type | Transformers > Drive Isolation |
Wall Mounting | Yes |
Warranty | 10 year warranty |
Weight | 32 lbs./100ft |
Width | 26 IN |
Width | 660.4 mm |
Winding | Aluminum |
Package Dimensions (L x W x H) | 26 IN x 25 IN x 38 IN |
Package Dimensions (L x W x H) | 66.04 cm x 63.5 cm x 96.52 cm |
Package Weight (Imperial) | 585.000 L |
Package Weight (Metric) | 265.356 kg |
Frequently Asked Questions
What is the typical impedance of the HPS Tribune DM063JC transformer?
The typical impedance for the HPS Tribune DM063JC transformer is 3 to 6%.
What is the insulation system temperature rating for this transformer?
The transformer utilizes a 220°C insulation system with a 150°C temperature rise.
What enclosure type is standard for the DM063JC transformer?
The standard enclosure type is a heavy-duty ventilated type 3R, suitable for indoor or outdoor applications.
Can the DM063JC transformer be mounted on a wall?
Yes, wall mounting is available for the DM063JC transformer, indicated by 'W' in the mounting type column.
What are the dimensions of the DM063JC transformer?
The DM063JC transformer has dimensions of 26.00 inches width, 25.00 inches depth, and 38.00 inches height.
What is the approximate weight of the DM063JC transformer?
The approximate weight of the DM063JC transformer is 530.0 lbs (239.0 kg).
What is the frequency rating for the DM063JC transformer?
The DM063JC transformer is rated for a frequency of 60 Hz.
What is the conductor material used in the DM063JC transformer?
The DM063JC transformer is aluminum wound.
Does the DM063JC transformer have a neutral terminal?
Yes, a neutral terminal is provided for field connection on applicable units.
What is the short circuit withstand capability of this transformer?
The transformer meets UL and CSA short circuit withstand requirements.
Frequently Asked Questions about Hammond Power
What certifications and standards do Hammond Power products comply with?
Hammond Power products are certified to UL (Underwriters Laboratories) and CSA (Canadian Standards Association) standards in North America. Our products meet rigorous safety and performance requirements, with many items classified as UL Listed Products or Recognized Components. We also comply with international certifications including China Compulsory Certification (CCC), C-Tick for Australian EMC requirements, and ANCE for Mexico.
What is Hammond Power's warranty policy?
Hammond Power provides a standard one-year warranty on all products, covering defects in workmanship and materials. Products will be repaired or replaced free of charge if found defective upon factory inspection. The warranty does not cover damage from improper handling, incorrect application, or faulty installation.
What industries and applications are Hammond Power products used for?
Hammond Power products are engineered for critical industrial and commercial applications across multiple sectors, including petrochemical, mining, construction, renewable energy, e-mobility, power storage, and microgrids. Their comprehensive product range of dry-type transformers, power quality solutions, and magnetic components enables electrical distribution and electrification in diverse industrial environments worldwide.
What are the main product lines offered by Hammond Power?
Hammond Power Solutions offers a comprehensive range of dry-type and liquid-filled transformers for industrial and commercial applications. Their primary product lines include power transformers for renewable energy, e-mobility, data centers, microgrids, and industrial settings. The company provides both standard and custom-designed transformer solutions that are critical to electrical distribution networks across multiple industries.
What are the key features of Hammond Power products?
Hammond Power products feature advanced dry-type and liquid-filled transformers engineered for diverse industrial applications, with capabilities spanning renewable energy, e-mobility, data centers, microgrids, and industrial/commercial sectors. Key features include high-performance electrical steel laminations, windings available in copper or aluminum, advanced insulation systems (VPI or Cast Resin), Basic Impulse Level ranges from 10 kV to 250 kV, and custom design capabilities with over 3,000 unique transformer designs engineered annually.
What environmental ratings do Hammond Power products have?
Hammond Power offers industrial enclosures with comprehensive environmental ratings, including UL/cUL 508A ratings of Type 1, 2, 3, 4, 4X, 12, and 13. Their products meet IEC 60529 IP66 standards, providing robust protection against dust, water ingress, and harsh environmental conditions. Specific ratings vary by product series, with options ranging from indoor Type 1 enclosures to outdoor-rated Type 4X enclosures suitable for challenging industrial environments.
What technical support does Hammond Power offer?
Hammond Power Solutions provides comprehensive technical support through multiple channels. Customers can access technical resources via phone support in Canada, the United States, Mexico, and internationally, with toll-free numbers and regional contact points. Their technical team offers personalized assistance for custom design inquiries, helping customers find standard transformer and power solutions or develop specialized electrical products for various industrial applications.
What communication protocols do Hammond Power products support?
Hammond Power products support multiple industrial communication protocols, including Modbus RTU, PROFIBUS DP, PROFINET, EtherNet/IP, and CANopen. These protocols enable flexible connectivity across industrial automation platforms, supporting various network topologies and high-speed data transmission for comprehensive industrial control and monitoring applications.
What accessories are available for Hammond Power products?
Hammond Power offers a comprehensive range of accessories for industrial electrical components, including HME Series handles with key locking and padlocking options, door stop kits, light kit mounting brackets, and standard hardware like mounting screws and washers. These accessories are designed to enhance functionality and installation flexibility across their product lines.
How are Hammond Power products typically installed?
Hammond Power transformers are typically chassis-mounted using precise mounting hole centers and dimensions specific to each product series. Installation involves selecting the appropriate primary voltage configuration, securing the transformer to a mounting surface using the specified mounting holes, and connecting terminals according to the product's schematic. Most Hammond Power transformers feature multiple terminal options like solder or quick-connect terminals, allowing flexible and straightforward installation in industrial control and power distribution applications.