Authorized Hammond Power Distributor
Hammond Power CD1X0022E - dV/dT filter 22 amperes up to 600 volts type 1
More images

Hammond Power CD1X0022E dV/dT filter 22 amperes up to 600 volts type 1

UPC: 803423168131


Documents & Media
BrochureInstallation InstructionsSpecification Sheet

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The Hammond Power HPS Centurion D1 dV/dT filter, SKU CD1X0022E, is a three-phase iron core line reactor with integrated resistors designed to protect motors from damaging voltage spikes in variable frequency drive (VFD)-driven systems. Rated for 22 amperes and up to 600 volts, this Type 1 enclosure filter specifically mitigates high-frequency switching transients generated by pulse-width modulation (PWM)-controlled variable frequency drives. It effectively reduces peak voltages at the motor terminals, preventing insulation stress and premature motor failure, particularly when cable lengths exceed standard recommendations. The filter is optimized for applications with cable runs up to 1000 feet, addressing impedance mismatches between the drive and motor to ensure stable operation. By attenuating dV/dT (rate of voltage rise), it limits voltage spikes to safe levels, thereby extending motor lifespan in demanding industrial environments. Compatible with standard VFD-motor combinations, this component is essential for maintaining operational efficiency in systems where long cable runs are unavoidable, ensuring reliable performance and reduced maintenance costs.
  • The dV/dT filter combines an inductor and parallel resistor network to mitigate both high frequency components and voltage spikes between the VFD and motor.
  • The filter can mitigate the effects of reflected wave voltages greater than what a reactor alone can accomplish.
  • The filter provides protection to the motor by slowing down the rate of voltage increase and minimizes the damaging peak voltages that occur within the motor’s windings and along the length of cables feeding the motor.
  • Three-phase iron core line reactor with integrated resistors
  • Reduces voltage spikes caused by PWM switching and long cable runs

Specifications

Altitude
<1000 m
Ambient Operating Temperature
-25C to 40C (suitable to 50C) Deg C
Application
Designed for applications with long cables between the VFD and the motor
Cooling
Natural Convection
Current Rating
22 A
Enclosure
Type 1
Height
5.5 in
Inverter Operating Frequency
up to 60Hz
Inverter Specification
Switching Frequency: 2kHz - 4kHz, Operating Frequency: up to 60Hz
Inverter Switching Frequency
2kHz - 4kHz
Length
6 IN
Maximum Ambient Temperature
40C (suitable to 50C)
Minimum Ambient Temperature
-25C
Mounting
Wall/Ceiling/Floor Mount
NEC 480 HP
15
NEC 600 HP
20
NEMA Rating
Type 1
Peak Voltage
at Motor: 150% of DC bus voltage
Special Features
Peak Voltage at Motor: 150% of DC bus voltage
Standard
cUL
System Voltage
up to 600V
Voltage Rating
up to 600V
Voltage Rating
600 V
Watts Loss
200
Weight
6 lbs
Width
8 in
Package Dimensions (L x W x H)
6 IN x 8 IN x 5.5 IN
Package Dimensions (L x W x H)
152.4 mm x 203.2 mm x 139.7 mm
Package Weight (Imperial)
6.000 L
Package Weight (Metric)
2.700 kg
dV/dT filter 17 amperes up to 600 volts type 1

CD1X0017E

dV/dT filter 17 amperes up to 600 volts type 1
POE INJECTOR OUTDOOR LORA GTW

48290940

POE INJECTOR OUTDOOR LORA GTW
dV/dT filter 54 amperes up to 600 volts open style

CD1X0054F

dV/dT filter 54 amperes up to 600 volts open style
Passive Harmonic Filters, 7.5 HorsePower, 600 Volts, 8 Amperes, 60 Hertz, Open Style

CP1P6G0008F

Passive Harmonic Filters, 7.5 HorsePower, 600 Volts, 8 Amperes, 60 Hertz, Open Style
dV/dT filter 80 amperes up to 600 volts open style

CD1X0080F

dV/dT filter 80 amperes up to 600 volts open style
Passive Harmonic Filters, 10 HorsePower, 600 Volts, 12 Amperes, 60 Hertz, Open Style

CP1P6G0012F

Passive Harmonic Filters, 10 HorsePower, 600 Volts, 12 Amperes, 60 Hertz, Open Style
Passive Harmonic Filters, 50 HorsePower, 480 Volts, 61 Amperes, 60 Hertz, Open Style

CP1K6G0061F

Passive Harmonic Filters, 50 HorsePower, 480 Volts, 61 Amperes, 60 Hertz, Open Style
AUTO 83KVA 600Y-480Y CU 60HZ for use with Active Harmonic Filter

AHF228795

AUTO 83KVA 600Y-480Y CU 60HZ for use with Active Harmonic Filter

Frequently Asked Questions

What is the system voltage rating for these filters?

The filters are rated for system voltages up to 600V, specifically for 480V and 600V applications.

What is the current rating range for HPS dV/dT filters?

The current ratings range from 2A to 108A, with options for higher ratings available upon consultation with HPS.

What is the inverter switching frequency range?

The inverter switching frequency range is between 2kHz and 4kHz.

What is the maximum motor lead length recommended?

The recommended maximum motor lead length is 600 ft, but consult HPS for longer lengths.

What is the ambient operating temperature range for the filters?

The ambient operating temperature range is -25°C to 40°C, and they are suitable for use up to 50°C.

What is the cooling method for the dV/dT filters?

The filters are cooled by natural convection.

What enclosure types are available for the dV/dT filters?

The filters are available in Open Frame (Type F) and Type 1 (Type E) enclosures.

What are the typical applications for these dV/dT filters?

Typical applications include Oil & Gas Pumps, Wastewater Treatment Plants, HVAC Systems, Pulp & Paper, and Irrigation Fields.

What is the voltage drop across the filter?

The voltage drop across the filter is less than 3%.

What is the purpose of the HPS Centurion D1 dV/dT filter?

The D1 filter mitigates high frequency components and voltage spikes between a VFD and motor, protecting the motor and cables from damage.

How to Install the dV/dT Filter

This guide provides step-by-step instructions for the installation and initial setup of the dV/dT filter, ensuring safe and proper operation.

Estimated time: 45m

Tools needed:

Screwdriver, Wire strippers, Multimeter

Supplies needed:

Mounting screws, Terminal connectors

  1. Inspect the unit

    Immediately after receiving the dV/dT filter, inspect it for any transit damage and verify it against the shipping documents. If any damage is found, do not energize the unit and contact the manufacturer.

  2. Mount the filter

    Secure the dV/dT filter to a suitable mounting surface using the provided mounting screws. Ensure that the unit is level and accessible for future maintenance.

  3. Connect the wiring

    Connect the output phases U, V, and W from the variable frequency drive to terminals A1, B1, and C1 on the filter. Connect terminals A2, B2, and C2 to T1, T2, and T3 of the motor. Ensure all connections are tight and secure.

  4. Ground the unit

    Ensure the dV/dT filter is properly grounded according to local electrical codes. Verify that all ground connections are secure before proceeding.

  5. Verify connections

    Use a multimeter to check the tightness and integrity of all electrical connections. Confirm that there are no loose wires or potential short circuits.

  6. Perform a dry-out if necessary

    If the filter has been exposed to moisture, dry it out by directing warm air through the windings for at least 24 hours before energizing.

  7. Energize the unit

    Once all connections are verified and the unit is dry, restore power to the dV/dT filter. Monitor for any unusual sounds or signs of malfunction.

Frequently Asked Questions about Hammond Power

What certifications and standards do Hammond Power products comply with?

Hammond Power products are certified to UL (Underwriters Laboratories) and CSA (Canadian Standards Association) standards in North America. Our products meet rigorous safety and performance requirements, with many items classified as UL Listed Products or Recognized Components. We also comply with international certifications including China Compulsory Certification (CCC), C-Tick for Australian EMC requirements, and ANCE for Mexico.

What is Hammond Power's warranty policy?

Hammond Power provides a standard one-year warranty on all products, covering defects in workmanship and materials. Products will be repaired or replaced free of charge if found defective upon factory inspection. The warranty does not cover damage from improper handling, incorrect application, or faulty installation.

What industries and applications are Hammond Power products used for?

Hammond Power products are engineered for critical industrial and commercial applications across multiple sectors, including petrochemical, mining, construction, renewable energy, e-mobility, power storage, and microgrids. Their comprehensive product range of dry-type transformers, power quality solutions, and magnetic components enables electrical distribution and electrification in diverse industrial environments worldwide.

What are the main product lines offered by Hammond Power?

Hammond Power Solutions offers a comprehensive range of dry-type and liquid-filled transformers for industrial and commercial applications. Their primary product lines include power transformers for renewable energy, e-mobility, data centers, microgrids, and industrial settings. The company provides both standard and custom-designed transformer solutions that are critical to electrical distribution networks across multiple industries.

What are the key features of Hammond Power products?

Hammond Power products feature advanced dry-type and liquid-filled transformers engineered for diverse industrial applications, with capabilities spanning renewable energy, e-mobility, data centers, microgrids, and industrial/commercial sectors. Key features include high-performance electrical steel laminations, windings available in copper or aluminum, advanced insulation systems (VPI or Cast Resin), Basic Impulse Level ranges from 10 kV to 250 kV, and custom design capabilities with over 3,000 unique transformer designs engineered annually.

What environmental ratings do Hammond Power products have?

Hammond Power offers industrial enclosures with comprehensive environmental ratings, including UL/cUL 508A ratings of Type 1, 2, 3, 4, 4X, 12, and 13. Their products meet IEC 60529 IP66 standards, providing robust protection against dust, water ingress, and harsh environmental conditions. Specific ratings vary by product series, with options ranging from indoor Type 1 enclosures to outdoor-rated Type 4X enclosures suitable for challenging industrial environments.

What technical support does Hammond Power offer?

Hammond Power Solutions provides comprehensive technical support through multiple channels. Customers can access technical resources via phone support in Canada, the United States, Mexico, and internationally, with toll-free numbers and regional contact points. Their technical team offers personalized assistance for custom design inquiries, helping customers find standard transformer and power solutions or develop specialized electrical products for various industrial applications.

What communication protocols do Hammond Power products support?

Hammond Power products support multiple industrial communication protocols, including Modbus RTU, PROFIBUS DP, PROFINET, EtherNet/IP, and CANopen. These protocols enable flexible connectivity across industrial automation platforms, supporting various network topologies and high-speed data transmission for comprehensive industrial control and monitoring applications.

What accessories are available for Hammond Power products?

Hammond Power offers a comprehensive range of accessories for industrial electrical components, including HME Series handles with key locking and padlocking options, door stop kits, light kit mounting brackets, and standard hardware like mounting screws and washers. These accessories are designed to enhance functionality and installation flexibility across their product lines.

How are Hammond Power products typically installed?

Hammond Power transformers are typically chassis-mounted using precise mounting hole centers and dimensions specific to each product series. Installation involves selecting the appropriate primary voltage configuration, securing the transformer to a mounting surface using the specified mounting holes, and connecting terminals according to the product's schematic. Most Hammond Power transformers feature multiple terminal options like solder or quick-connect terminals, allowing flexible and straightforward installation in industrial control and power distribution applications.