ABB Low Voltage Drives P14494-23 Braking Resistor, 80 OHMS, 2400 WATTS, GCE6 Enclosure, 19W x 10D x 5H in, 20 lbs
Alternate Item Number: 3AUA0000015105
UPC: 662348076163
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 80 OHM resistance for effective energy dissipation
- 2400-watt power rating for demanding applications
- GCE6 enclosure for robust protection
- Compact dimensions: 19" W x 10" D x 5" H
- Manufactured in the USA

MPOT-01
Potentiometer with two switches: Start/Stop and Forward/Reverse. Polarity is selected with DIP switches. No external power source is needed for the potentiometer. This option can be used with the Blank Cover, Basic or Advanced Panel.Frequently Asked Questions
What duty cycle is specified for the resistor compatibility tables?
The duty cycles specified are 3sec on/27sec off, 10sec on/50sec off, 30sec on/180sec off, and 60sec on/180sec off.
What are the voltage ranges for the listed ACS drive applications?
Applications include single-phase 100-120V, 200-240V, and three-phase 200-240V, 380-480V, and 575-690V.
Which ABB drives are compatible with Type CR resistors listed?
The listed Type CR resistors are compatible with ACS150, ACS355, ACS250, and ACS550 drive series.
What is the purpose of a braking resistor with variable frequency drives?
Braking resistors dissipate regenerated power to prevent the bus voltage from exceeding the drive's rated limit, especially during faster deceleration or overhauling load conditions.
What is the resistance and wattage for P14494-CR-02 resistor?
The P14494-CR-02 resistor has 200 Ohms and 100 Watts, and is used with various ACS150/355 and ACS250 drives.
What is the resistance and wattage for P14494-19 resistor?
The P14494-19 resistor has 75 Ohms and 300 Watts, and is used with various ACS150/355, ACS250, and ACS550 drives.
What is the role of a braking chopper (module)?
Braking modules monitor the drive's DC bus and activate external braking resistors to manage regenerated power and prevent over-voltage trips.
When should 200ºC rated wire be used with Type ED enclosures?
Use 200ºC rated silicone or Teflon wire when attaching directly to resistor coils if installing without the optional terminal connections.
What is the function of the thermal switch in Type GCE and ED enclosures?
The normally closed thermal switch detects resistor temperature overloads, providing a safety mechanism.
Are brake modules standard on all ACS550 drive sizes?
For ACS550 drives, brake modules are standard up to 10 Hp and optional above 10 Hp for 200-240V applications. For 380-480V, they are standard up to 15 Hp and optional above 15 Hp.