ABB Low Voltage Drives ACS550-U1-059A-4+K451+L511 ACS550 AC Drive, 3-380-480V In, 40HP, 59A, Type 1/IP21, 1.1 overload, Advanced, 27.1 x 8…
Alternate Item Number: 3AUA0000037683
UPC: 662348048528
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 40HP (59A) output at 380-480V AC input
- IP21 and Type 1 (NEMA) enclosure for dust and splash protection
- Wall-mountable design with compact dimensions (27.1 x 8 x 10.3 in)
- DeviceNet communication for automation system integration
- 1.1 overload rating for handling temporary current spikes
Specifications
Control Panel | Advanced |
Frame Size | R4 |
Input Phase | 3-Phase |
IP Rating | IP21 |
Options | DeviceNet Relay output extension |
Output Current | 59 |
Output Phase | 3-Phase |
UL Type | 1 |
Voltage | 480 |
Voltage Range | 380-480 |
Package Dimensions (L x W x H) | 10.3 in x 8 in x 27.1 in |
Package Dimensions (L x W x H) | 26.162 cm x 20.32 cm x 68.834 cm |
Package Weight (Imperial) | 53.000 L |
Package Weight (Metric) | 24.041 kg |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What product compliance approvals does the ACS550 have?
The drives have UL, cUL, CSA, CE, C-TICK, and GOST-R approvals.
What is the power and voltage range for ACS550 drives?
The drives support 3-phase input power from 208 to 600V, with horsepower ratings varying by voltage.
Does the drive have built-in serial communication?
Yes, the drive has built-in RS 485 serial communication with Modbus RTU protocol.
What is the recommended ambient temperature range for operation?
The ambient temperature range for operation is 15 to 40°C (5 to 104° F).
What is the frequency range for motor connection?
The motor connection frequency range is from 0 to 500 Hz.
What are the acceleration and deceleration time limits?
Acceleration and deceleration times can be set between 0.1 to 1800 seconds.
What NEMA enclosure types are available for ACS550 drives?
NEMA 1, 12, and 3R enclosures are available depending on the specific model and configuration.
What types of analog inputs are available?
There are two analog inputs that accept voltage signals (0-10V) or current signals (0-20mA).
What is the auxiliary voltage provided by the drive?
The drive provides an auxiliary voltage of 24 V DC ±10% with a maximum current of 250 mA.
How many digital inputs does the drive have?
The drive is equipped with six digital inputs that operate with 12V to 24V DC.