ABB Low Voltage Drives ACS550-PD-059A-4+K466 GENERAL PURPOSE PACKAGED DRIVE W/ DISCONNECT SWITCH AND FUSES, Product Family: ACS550…
Alternate Item Number: 3AUA0000031117
UPC: 662348044858
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 40 HP, 59A, 480 VAC, 3-Phase Output
- NEMA 1 / UL Type 1 (IP21) Enclosure
- Includes Disconnect Switch and Fuses
- Advanced Control Panel and Ethernet Adapter
- Wall-mounted, Frame R4, Dimensions: 45.2" x 10.2" x 13.1"
Specifications
Package Dimensions (L x W x H) | 58 IN x 14 IN x 19 IN |
Package Dimensions (L x W x H) | 147.32 cm x 35.56 cm x 48.26 cm |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What are the input voltage and frequency ranges for ACS550 drives?
The drives support 3-phase input voltages of 208-240V, 380-480V, or 500-600V, with a frequency range of 48 to 63 Hz.
Does the drive have built-in serial communication capabilities?
Yes, the drive has built-in RS 485 serial communication with Modbus RTU protocol.
What certifications does the ACS550 drive hold?
The drive holds UL, cUL, CSA, CE, C-TICK, and GOST-R approvals.
What is the output frequency range for connected motors?
The motor output frequency can be set from 0 to 500 Hz.
What are the acceleration and deceleration time limits?
Acceleration and deceleration times can be programmed from 0.1 to 1800 seconds.
What types of analog inputs are supported?
The drives support two analog inputs for voltage (0-10V) or current (0-20mA) signals.
What are the specifications for the analog outputs?
There are two analog outputs that support 0-20mA signals with a load of less than 500 Ohms.
How many digital inputs are available on the drive?
The drive is equipped with six digital inputs that accept 12V to 24V DC.
What are the specifications for the relay outputs?
There are three relay outputs with a maximum switching voltage of 250V AC/30V DC and a maximum switching current of 6A.
What are the environmental operating temperature limits?
The ambient temperature range for operation is 5 to 104°F (15 to 40°C), with derating above 104°F.