ABB Low Voltage Drives ACS550-PD-059A-4+B055+K451 GENERAL PURPOSE PACKAGED DRIVE W/ DISCONNECT SWITCH AND FUSES, Product Family: ACS550…
Alternate Item Number: 3AUA0000158248
UPC: 662348044766
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 40 HP / 59A Output Current / 480 VAC Input Voltage
- NEMA 12 / UL Type 12 (IP54) Enclosure for Dust and Moisture Protection
- Wall-mounted design with Advanced Control Panel and DeviceNet Adapter
- Integrated Disconnect Switch and Fuses for Safety and Maintenance
- 3-Phase Input / 3-Phase Output, Frame R4
Specifications
Current Rating | 59 A |
IP Rating | IP54 |
Mounting Type | Wall-mounted |
Nema Rating | Type 12 |
Series | ACS550 |
Voltage Rating | 480 VAC |
Package Dimensions (L x W x H) | 58 IN x 14 IN x 19 IN |
Package Dimensions (L x W x H) | 147.32 cm x 35.56 cm x 48.26 cm |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the input voltage range for ACS550 drives?
The drives support 3-phase input voltages of 208 to 240 V, 380 to 480 V, and 500 to 600 V, with a tolerance of +10/-15%.
What is the operating ambient temperature range?
The drives can operate in ambient temperatures between 15 to 40°C (5 to 104° F).
What certifications do the ACS550 drives hold?
The drives hold UL, cUL, C-Tick, and Gost-R approvals, and are certified to seismic criteria ICC AC-156.
What are the humidity requirements for operation?
The relative humidity must be lower than 95%, and condensation is not allowed.
What is the output frequency range for motors?
The motor output frequency can be set from 0 to 500 Hz.
What communication protocols are supported?
The drives have built-in Modbus RTU protocol and support numerous internally mountable fieldbus adapters.
Are coated boards available for harsh environments?
Yes, the drives are available with coated boards for use in harsh environments.
What protection classes are available for ACS550 drives?
The drives are available in UL Type 1, 12, or 3R (NEMA 1, 12, or 3R) enclosures.
Does the drive have harmonic reduction features?
Yes, it includes a patented swinging choke for superior harmonic reduction and an integral EMC filter as standard.
What is the auxiliary voltage provided by the drive?
The drive provides an auxiliary voltage of 24 V DC ±10% with a maximum current of 250 mA.