ABB Low Voltage Drives ACS550-PD-04A6-2 GENERAL PURPOSE PACKAGED DRIVE W/ DISCONNECT SWITCH AND FUSES, Product Family: ACS550…
Alternate Item Number: 3AUA0000010275
UPC: 662348044674
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 1 HP output power with 4.6A current rating for 240VAC operation
- 208-240VAC input voltage range for flexible power compatibility
- NEMA 1 / UL Type 1 (IP21) enclosure protects against dust and light splashes
- Built-in disconnect switch and fuses for enhanced safety and maintenance
- Wall-mounted design with dimensions 28.7 x 7.8 x 11.2 inches and 33 lbs weight
Specifications
Current Rating | 4.6 A |
IP Rating | IP21 |
Mounting Type | Wall-mounted |
Nema Rating | NEMA 1 / UL Type 1 |
Poles | 3-Phase |
Series | ACS550 |
Size | 28.7 in x 7.8 in x 11.2 in |
Voltage Rating | 240 Vac |
Package Dimensions (L x W x H) | 51 IN x 12 IN x 18 IN |
Package Dimensions (L x W x H) | 129.54 cm x 30.48 cm x 45.72 cm |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the recommended ambient temperature range for operation?
The ambient temperature range for operation is 15 to 40°C (5 to 104°F).
What is the power and voltage range for 3-phase ACS550 drives?
For 3-phase, the voltage ranges are 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What is the operating frequency range for the motor connection?
The motor connection operates at a frequency range of 0 to 500 Hz.
What are the acceleration and deceleration time limits?
Acceleration and deceleration times can be set between 0.1 to 1800 seconds.
What serial communication protocol is built-in?
The drive has a built-in Modbus RTU protocol for serial communication via RS 485.
What product compliance and certifications does the ACS550 have?
The drives have UL, cUL, CSA, CE, C-TICK, and GOST-R approvals, and seismic certification.
What protection classes are available for the ACS550 drives?
Available protection classes are UL Type 1, 12, or 3R (NEMA 1, 12, or 3R).
What analog input signals are supported?
The drive supports voltage signals (0-10V) and current signals (0-20mA).
What is the accuracy of the analog outputs?
The analog outputs have an accuracy of ±3% for 0-20mA signals with a load under 500 Ω.
What is the auxiliary voltage provided by the drive?
The drive provides an auxiliary voltage of 24 V DC ±10% with a maximum current of 250 mA.