ABB Low Voltage Drives ACS550-PD-045A-4 GENERAL PURPOSE PACKAGED DRIVE W/ DISCONNECT SWITCH AND FUSES, Product Family: ACS550…
Alternate Item Number: 3AUA0000016131
UPC: 662348044483
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 30 HP output at 44 A, 380-480V AC input range
- NEMA 1 / UL Type 1 (IP21) enclosure for indoor protection
- Integrated disconnect switch and fuses for safety and simplified installation
- 3-phase input and output for compatibility with standard industrial motors
- Wall-mounted design with advanced control panel for easy operation
Specifications
Package Dimensions (L x W x H) | 58 in x 14 in x 19 in |
Package Dimensions (L x W x H) | 147.32 cm x 35.56 cm x 48.26 cm |
Package Weight (Imperial) | 92.000 L |
Package Weight (Metric) | 41.731 kg |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What are the voltage and power ranges for ACS550 drives?
The drives support 3-phase input power across several ranges: 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What is the operating frequency range for the motor connection?
The motor connection frequency range is from 0 to 500 Hz.
What are the acceleration and deceleration time limits?
Acceleration and deceleration times can be set between 0.1 to 1800 seconds.
What types of analog inputs are available?
There are two analog inputs that accept voltage signals (0-10V) or current signals (0-20mA).
What is the accuracy of the analog outputs?
The analog outputs provide a 0 (4) to 20 mA signal with an accuracy of ±3%.
What is the auxiliary voltage provided by the drive?
The drive provides an auxiliary voltage of 24 V DC ±10%, with a maximum current of 250 mA.
How many digital inputs does the drive have?
The drive is equipped with six digital inputs that accept 12 V to 24 V DC signals.
What are the specifications for the relay outputs?
There are three relay outputs with a maximum switching voltage of 250 V AC/30 V DC and a maximum switching current of 6 A.
Does the drive have built-in serial communication?
Yes, the drive has built-in RS 485 serial communication supporting the Modbus RTU protocol.
What is the recommended ambient temperature range for operation?
The ambient temperature range for operation is 15 to 40°C (5 to 104° F). Operation between 40-50°C requires derating.