Overview
- 10 HP motor power rating
- 30.8 A output current
- 240 VAC, 3-phase input/output
- NEMA 1 / UL Type 1 (IP21) enclosure
- Includes disconnect switch and fuses
Specifications
Connection Type | 3-Phase Input/Output |
Current Rating | 30.8 A |
IP Rating | IP21 |
Mounting Type | Wall-mounted |
Nema Rating | NEMA 1 / UL Type 1 |
Poles | 3-Phase |
Series | ACS550 |
Size | 32.6 in x 7.8 in x 11.6 in |
Voltage Rating | 240 Vac |
Package Dimensions (L x W x H) | 51 IN x 12 IN x 18 IN |
Package Dimensions (L x W x H) | 129.54 cm x 30.48 cm x 45.72 cm |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What are the voltage and power ranges for ACS550 drives?
The drives support 3-phase input power with ranges of 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What serial communication protocol is built-in?
The drives have a built-in RS 485 serial communication port that supports the Modbus RTU protocol.
What is the operating frequency range for the drives?
The input power frequency range is 48 to 63 Hz, and the motor connection frequency range is 0 to 500 Hz.
What are the environmental operating temperature limits?
The ambient temperature range for operation is 15 to 40°C (5 to 104°F), with derating required from 40 to 50°C (104 to 122°F).
What approvals do the ACS550 drives have?
The drives have UL, cUL, CSA, CE, C-TICK, and GOST-R approvals, and are seismically certified to ICC AC-156 criteria.
What types of analog inputs are available?
There are two analog inputs that can accept voltage signals (0-10V) or current signals (0-20mA).
How many digital inputs and relay outputs are provided?
The drives feature six digital inputs and three relay outputs with specified voltage and current switching capabilities.
What NEMA protection classes are available for ACS550 drives?
The drives are available in UL Type 1, 12, or 3R (NEMA 1, 12, or 3R) enclosures depending on the model.
What are the acceleration and deceleration time limits?
Acceleration and deceleration times can be set between 0.1 to 1800 seconds.
What are the specifications for the analog outputs?
Two analog outputs are available, supporting 0-20mA or 4-20mA with a load of less than 500 Ohms.