ABB Low Voltage Drives ACS550-PD-02A7-6 GENERAL PURPOSE PACKAGED DRIVE W/ DISCONNECT SWITCH AND FUSES, Product Family: ACS550…
Alternate Item Number: 3AUA0000010308
UPC: 662348044124
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 2 HP output at 2.7 A with 600 VAC input (500-600V range)
- Integrated disconnect switch and fuses for safety and maintenance
- NEMA 1 / UL Type 1 (IP21) enclosure for dust and splash protection
- Advanced control panel with programmable acceleration/deceleration (0.1-1800s)
- Built-in Modbus RTU communication via RS485 for system integration
Specifications
Package Dimensions (L x W x H) | 51 IN x 12 IN x 18 IN |
Package Dimensions (L x W x H) | 129.54 cm x 30.48 cm x 45.72 cm |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the operating frequency range for the motor connection?
The motor connection supports a frequency range from 0 to 500 Hz.
What are the acceleration and deceleration time limits?
Acceleration and deceleration times can be set between 0.1 to 1800 seconds.
How many digital inputs and relay outputs are provided?
The drives feature six digital inputs and three relay outputs.
What serial communication protocol is built-in?
The drives have a built-in RS 485 serial communication port that supports the Modbus RTU protocol.
What is the power and voltage range for ABB standard drives?
The drives support 3-phase power with ranges of 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What is the auxiliary voltage provided by the drive?
An auxiliary voltage of 24V DC ±10% is provided, with a maximum current of 250 mA.
What is the recommended ambient temperature range for operation?
The drives should be operated in an ambient temperature range of 15 to 40°C (5 to 104°F).
What is the maximum allowable relative humidity for the drives?
The relative humidity should be lower than 95%, without condensation.
What features are included as standard with ABB standard drives?
Standard features include a swinging choke for harmonic reduction, an integral EMC filter, and a control panel for intuitive operation.
What product compliance and certifications does the ACS550 series have?
The drives have UL, cUL, CSA, CE, C-TICK, and GOST-R approvals, and meet seismic certification to ICC AC-156 criteria.