ABB Low Voltage Drives ACS550-PC-414A-4 GENERAL PURPOSE PACKAGED DRIVE W/ CIRCUIT BREAKER DISCONNECT, Product Family: ACS550…
Alternate Item Number: 3AUA0000013676
UPC: 662348043431
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 350 HP / 414A / 480VAC General Purpose Packaged Drive
- NEMA 1 / UL Type 1 (IP21) Enclosure for Standard Environments
- Integrated Circuit Breaker Disconnect for Safety and Maintenance
- Free-Standing Mounting with Advanced Control Panel
- 3-Phase Input and Output for Industrial Machinery

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the voltage and power range for 3-phase input?
The 3-phase input ranges are 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What is the acceptable input frequency range?
The acceptable input frequency range for the drives is 48 to 63 Hz.
What is the power factor of the ABB standard drives?
The power factor for these drives is 0.98.
What is the motor connection frequency range?
The motor connection frequency can range from 0 to 500 Hz.
What are the acceleration and deceleration time limits?
Acceleration and deceleration times can be set between 0.1 to 1800 seconds.
What types of analog inputs are available?
Two analog inputs are available, supporting voltage signals (0-10V) and current signals (0-20mA).
What is the accuracy of the analog outputs?
The analog outputs provide 0 (4) to 20 mA with an accuracy of ±3%.
What is the auxiliary voltage provided by the drive?
The drive provides an auxiliary voltage of 24 V DC ±10% with a maximum current of 250 mA.
How many digital inputs are included?
There are six digital inputs that accept 12 V to 24 V DC with a maximum delay of 5 ms.
What are the specifications for the relay outputs?
Three relay outputs are available with a maximum switching voltage of 250 V AC/30 V DC and a maximum continuous current of 2 A rm.