Authorized ABB Distributor (Low Voltage Drives)
ABB - Low Voltage Drives ACS550-PC-414A-4 - GENERAL PURPOSE PACKAGED DRIVE W/ CIRCUIT BREAKER DISCONNECT, Product Family: ACS550, Horsepower: 350 HP, Output Current: 414 A, Voltage: 480 VAC , Voltage Range: 380-480V, NEMA 1 / UL Type 1 (IP21), Mounting: Free Standing, Advanced Control Panel, 3-Phase Input, 3-Phase Output, Frame: R8, Product HxWxD: 83.7 in x 31.7 in x 25.9 in, Product Weight: 793 lbs

ABB Low Voltage Drives ACS550-PC-414A-4 GENERAL PURPOSE PACKAGED DRIVE W/ CIRCUIT BREAKER DISCONNECT, Product Family: ACS550…

Alternate Item Number: 3AUA0000013676

UPC: 662348043431


Documents & Media
Specification Sheet

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB ACS550-PC-414A-4 is a general-purpose packaged drive designed for robust industrial applications. This unit features a substantial 350 HP motor rating and a 414A output current, operating efficiently within a 380-480V range at 480VAC. Its NEMA 1 / UL Type 1 (IP21) enclosure provides protection suitable for standard industrial environments. The free-standing mounting configuration, coupled with an advanced control panel, simplifies installation and operational management. This drive is engineered for 3-phase input and 3-phase output, making it ideal for powering heavy-duty machinery, pumps, conveyors, and other high-power industrial equipment. A key safety and maintenance feature is the integrated circuit breaker disconnect. The ACS550 series, including this model, is built on ABB's established reputation for reliability, delivering energy efficiency and precise motor control. Its dimensions are 83.7 inches in height, 31.7 inches in width, and 25.9 inches in depth, with a product weight of 793 lbs. The maximum electrical switching frequency for general use is 600 cycles/h, and for motor use, it is 1200 cycles/h. The ACS550-PC-414A-4 is manufactured in Denmark.
  • 350 HP / 414A / 480VAC General Purpose Packaged Drive
  • NEMA 1 / UL Type 1 (IP21) Enclosure for Standard Environments
  • Integrated Circuit Breaker Disconnect for Safety and Maintenance
  • Free-Standing Mounting with Advanced Control Panel
  • 3-Phase Input and Output for Industrial Machinery
600V Class Iron Core Reactor, Core and Coil, 11 Amps, 2.57 Inductance, 60 Hz

CRX0011AC

600V Class Iron Core Reactor, Core and Coil, 11 Amps, 2.57 Inductance, 60 Hz
Double plastic fiber optic, Qty 1, 5 meters long

61059113

Double plastic fiber optic, Qty 1, 5 meters long
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.

FENA-21

The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.
KDR, 208V, 19A, 5HP

KDRB22L

KDR, 208V, 19A, 5HP

Frequently Asked Questions

What is the voltage and power range for 3-phase input?

The 3-phase input ranges are 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).

What is the acceptable input frequency range?

The acceptable input frequency range for the drives is 48 to 63 Hz.

What is the power factor of the ABB standard drives?

The power factor for these drives is 0.98.

What is the motor connection frequency range?

The motor connection frequency can range from 0 to 500 Hz.

What are the acceleration and deceleration time limits?

Acceleration and deceleration times can be set between 0.1 to 1800 seconds.

What types of analog inputs are available?

Two analog inputs are available, supporting voltage signals (0-10V) and current signals (0-20mA).

What is the accuracy of the analog outputs?

The analog outputs provide 0 (4) to 20 mA with an accuracy of ±3%.

What is the auxiliary voltage provided by the drive?

The drive provides an auxiliary voltage of 24 V DC ±10% with a maximum current of 250 mA.

How many digital inputs are included?

There are six digital inputs that accept 12 V to 24 V DC with a maximum delay of 5 ms.

What are the specifications for the relay outputs?

Three relay outputs are available with a maximum switching voltage of 250 V AC/30 V DC and a maximum continuous current of 2 A rm.