Authorized ABB Distributor (Low Voltage Drives)
ABB - Low Voltage Drives ACS550-PC-08A8-4 - GENERAL PURPOSE PACKAGED DRIVE W/ CIRCUIT BREAKER DISCONNECT, Product Family: ACS550, Horsepower: 5 HP, Output Current: 8.8 A, Voltage: 480 VAC , Voltage Range: 380-480V, NEMA 1 / UL Type 1 (IP21), Mounting: Wall-mounted, Advanced Control Panel, 3-Phase Input, 3-Phase Output, Frame: R1, Product HxWxD: 28.7 in x 7.8 in x 11.2 in, Product Weight: 33 lbs

ABB Low Voltage Drives ACS550-PC-08A8-4 GENERAL PURPOSE PACKAGED DRIVE W/ CIRCUIT BREAKER DISCONNECT, Product Family: ACS550…

Alternate Item Number: 3AUA0000010244

UPC: 662348042571


Documents & Media
Specification Sheet

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB ACS550-PC-08A8-4 is a general-purpose packaged drive designed for reliable industrial motor control. This 5 HP drive operates at 480 VAC with a 3-phase input and 3-phase output, delivering an output current of 8.8 A. It is equipped with a circuit breaker disconnect for enhanced operational safety and features an advanced control panel for intuitive user interaction. The enclosure is rated NEMA 1 / UL Type 1 (IP21), providing protection against dust and moisture, making it suitable for various industrial environments. Designed for wall mounting, this drive optimizes space utilization. The product family is ACS550, with frame size R1. Its dimensions are 28.7 inches in height, 7.8 inches in width, and 11.2 inches in depth, with a weight of 33 lbs. The voltage range is 380-480V. This drive is manufactured by ABB Low Voltage Drives and is ideal for applications requiring precise and efficient motor speed regulation. Its robust construction and comprehensive features ensure dependable performance in demanding industrial settings. The ACS550-PC-08A8-4 offers a straightforward solution for motor control needs, backed by ABB's expertise in low-voltage drive technology.
  • 5 HP, 480 VAC, 8.8A, 3-Phase Input/Output
  • Includes Circuit Breaker Disconnect for Safety
  • NEMA 1 / UL Type 1 (IP21) Enclosure
  • Advanced Control Panel for Intuitive Operation
  • Wall-mounted Design for Space Efficiency

Specifications

Package Dimensions (L x W x H)
51 IN x 12 IN x 18 IN
Package Dimensions (L x W x H)
129.54 cm x 30.48 cm x 45.72 cm
600V Class Iron Core Reactor, Core and Coil, 11 Amps, 2.57 Inductance, 60 Hz

CRX0011AC

600V Class Iron Core Reactor, Core and Coil, 11 Amps, 2.57 Inductance, 60 Hz
Double plastic fiber optic, Qty 1, 5 meters long

61059113

Double plastic fiber optic, Qty 1, 5 meters long
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.

FENA-21

The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.
KDR, 208V, 19A, 5HP

KDRB22L

KDR, 208V, 19A, 5HP

Frequently Asked Questions

What is the input voltage range for ACS550 drives?

The drives support 3-phase input voltages of 208 to 240 V, 380 to 480 V, and 500 to 600 V, with a tolerance of +10/-15%.

What is the operating frequency range for motor connection?

The motor connection frequency range is from 0 to 500 Hz.

What serial communication protocol is built-in?

The drives have a built-in RS 485 serial communication with Modbus RTU protocol.

What is the recommended ambient temperature range for operation?

The recommended ambient temperature range is 15 to 40°C (5 to 104°F).

What is the maximum relative humidity for operation?

The relative humidity should be lower than 95%, without condensation.

What are the acceleration and deceleration time limits?

Acceleration and deceleration times can be set between 0.1 to 1800 seconds.

What are the product compliance and certifications for ACS550 drives?

The drives have UL, cUL, CSA, CE, C-TICK, and GOST-R approvals, and are Seismic Certified to ICC AC-156 Criteria.

What are the specifications for analog inputs?

There are two analog inputs supporting 0-10 V voltage signals or 0-20 mA current signals, with an accuracy of ±1%.

What is the auxiliary voltage output?

The auxiliary voltage output is 24 V DC ±10%, with a maximum current of 250 mA.

What are the specifications for the relay outputs?

There are three relay outputs with a maximum switching voltage of 250 V AC/30 V DC and a maximum switching current of 6 A.