ABB Low Voltage Drives ACS550-PC-077A-6 GENERAL PURPOSE PACKAGED DRIVE W/ CIRCUIT BREAKER DISCONNECT, Product Family: ACS550…
Alternate Item Number: 3AUA0000010271
UPC: 662348042458
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 75 HP Motor Rating
- 77A Output Current
- 600 VAC Operating Voltage (500-600V Range)
- NEMA 1 / UL Type 1 (IP21) Enclosure
- Wall-Mounted Design with Advanced Control Panel
Specifications
Connection Type | 3-Phase Input/Output |
Current Rating | 77 A |
IP Rating | IP21 |
Mounting Type | Wall-mounted |
Nema Rating | NEMA 1 / UL Type 1 |
Poles | 3-Phase |
Series | ACS550 |
Size | 47.7 in x 28.1 in x 19 in |
Voltage Rating | 600 VAC |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What is the voltage and power range for 3-phase input?
For 3-phase, the voltage ranges are 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What serial communication protocol is built-in?
The drive has a built-in RS 485 serial communication port that supports the Modbus RTU protocol.
What is the recommended ambient temperature range for operation?
The ambient temperature range for operation is 15 to 40°C (5 to 104°F).
What is the operating frequency range for the drives?
The input power frequency range is 48 to 63 Hz, and the motor connection frequency is 0 to 500 Hz.
How many digital inputs does the drive have?
The drive is equipped with six digital inputs that accept 12V to 24V DC with PNP and NPN compatibility.
What are the product compliance and certifications?
The drives have UL, cUL, CSA, CE, C-TICK, and GOST-R approvals, and seismic certification to ICC AC-156.
What is the auxiliary voltage output specification?
The auxiliary voltage output is 24 V DC ±10%, with a maximum current of 250 mA.
What types of analog inputs are available?
There are two analog inputs that support voltage signals (0-10V) and current signals (0-20mA).
What are the capabilities of the relay outputs?
There are three relay outputs with a maximum switching voltage of 250V AC/30V DC and a maximum switching current of 6A.
What protection classes are available for enclosures?
Enclosures are available in UL Type 1, 12, or 3R (NEMA 1, 12, or 3R) ratings.