ABB Low Voltage Drives ACS550-PC-072A-4 GENERAL PURPOSE PACKAGED DRIVE W/ CIRCUIT BREAKER DISCONNECT, Product Family: ACS550…
Alternate Item Number: 3AUA0000010252
UPC: 662348042311
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 50 HP, 72 A, 480 VAC general-purpose drive with integrated circuit breaker disconnect
- Operates on 3-phase input/output with voltage range of 380–480 VAC
- NEMA 1 / UL Type 1 (IP21) enclosure for dust and light splash protection
- Wall-mounted design with dimensions 45.2 x 10.2 x 13.1 in and weight of 95 lbs
- Advanced control panel for straightforward operation and monitoring
Specifications
Connection Type | 3-Phase Input/Output |
Current Rating | 72 A |
IP Rating | IP21 |
Mounting Type | Wall-mounted |
Nema Rating | NEMA 1 / UL Type 1 |
Poles | 3-Phase |
Series | ACS550 |
Size | 45.2 in x 10.2 in x 13.1 in |
Voltage Rating | 480 VAC |
Package Dimensions (L x W x H) | 58 IN x 14 IN x 19 IN |
Package Dimensions (L x W x H) | 147.32 cm x 35.56 cm x 48.26 cm |

FENA-21
The FENA 21 DualPort module supports Three protocols Modbus-TCP, EtherNet/IP, and the PROFInet IO RT network. The Modbus-TCP protocol is simply the Modbus protocol used on top of Ethernet-TCP/IP. Modbus-TCP is an open Industrial Ethernet network which has been specified by the Modbus-IDA User Organization. EtherNet/IP is based on the Common Industrial Protocol (CIP), which is also the framework for both the ControlNet and DeviceNet network protocols. PROFInet IO RT is an open network based on the PI Organization standard.Frequently Asked Questions
What are the voltage and power ranges for ABB standard drives?
The drives support 3-phase input power with ranges of 208-240V (0.75-100Hp), 380-480V (1-550Hp), and 500-600V (1.5-150Hp).
What certifications do the ACS550 standard drives have?
The drives have UL, cUL, CSA, CE, C-TICK, and GOST-R approvals, and seismic certification to ICC AC-156 criteria.
What is the operating frequency range for the drives?
The input power frequency range is 48 to 63 Hz, and the motor connection frequency can be from 0 to 500 Hz.
What communication protocols are supported?
The drives have a built-in Modbus RTU protocol via RS 485 and support numerous internally mountable fieldbus adapters.
What are the environmental operating temperature limits?
The ambient temperature range is 15 to 40°C (5 to 104°F), and derating is required from 40 to 50°C (104 to 122°F).
What are the specifications for the relay outputs?
There are three relay outputs with a maximum switching voltage of 250V AC/30V DC and a maximum switching current of 6A.
What features are included as standard with ABB standard drives?
Standard features include a swinging choke for harmonic reduction, an integral EMC filter, and a control panel.
What are the specifications for the analog inputs?
There are two analog inputs that accept 0-10V voltage signals or 0-20mA current signals, with an accuracy of ±1%.
What are the specifications for the digital inputs?
There are six digital inputs that accept 12V to 24V DC with an input impedance of 2.4 kΩ and a maximum delay of 5 ms.
What is the auxiliary voltage provided by the drive?
The drive provides an auxiliary voltage of 24 V DC ±10% with a maximum current of 250 mA.