Overview
- Resistance: 4.26 ohms
- Power dissipation: 9872 watts
- Dimensions: 26.5W x 16D x 5H inches
- Weight: 41 lbs
- Compatibility: Designed for ABB VFDs and industrial motor control systems
Specifications
Power Rating | 9872 WATTS |
Resistance | 4.26 OHMS |
Series | GCE15 |
Size | 26.5W x 16D x 5H in |
Weight | 41 lbs |
Frequently Asked Questions
What is the purpose of a braking resistor with variable frequency drives?
Braking resistors increase braking torque capability and dissipate regenerated power to prevent bus voltage from exceeding the drive's rated limit.
What is the primary function of a braking resistor in a variable speed drive system?
It dissipates regenerated power from the motor back into the drive, preventing the DC bus voltage from rising too high.
What is the role of braking modules with AC drives?
Braking modules monitor the drive's DC bus and activate external braking resistors to manage regenerated power and improve performance.
What are the typical applications for braking resistors?
They are used for applications requiring faster deceleration rates or when motor speeds exceed synchronous speed, creating overhauling load conditions.
How are Powerohm Type CR resistors constructed?
They feature a nickel-chromium wire helically wound inside a ceramic fixture, placed in an aluminum case with high-temperature wire leads.
What type of wire should be used when connecting directly to resistors in Type ED enclosures?
If installing without optional terminal connections, use 200ºC rated silicone or Teflon wire.
What is the function of the thermal switch in Type GCE and ED enclosures?
The normally closed thermal switch detects resistor temperature overloads.
What is the conduit knockout size for Type GCE enclosures?
The Type GCE enclosures have removable 1/2 inch conduit knockouts.
What is the purpose of the solid bottom and wiring compartment in Type GCE enclosures?
The solid bottom and built-in wiring compartment separate the wiring from the resistor assembly.
What is the maximum continuous current rating for terminal connections in Type ED enclosures?
Type ED enclosures have terminal connections rated up to 400 amps continuous.