Contact for Pricing
Overview
- 25kV voltage rating for medium-voltage systems
- 900 Amp current rating for high-power applications
- Deadbreak design enables safe, arc-free connections/disconnections
- Reducing tap well allows conductor size transitions
- Includes loose stud for flexible installation
- Compact dimensions: 5.37" L x 3" W (excluding stud/bracket)
Specifications
Connection | Push-In |
Size | 5.37 in |
Special Features | Loose Stud |
Type | Reducing Tap Well |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

J4-6226-15
4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interfaces and one 200 Amp Bushing Well Interface, 15kV, No Tilt Mounting.
J3-626-25-SV-N
3 Point Junction, with one 600 Amp Bushing Interface, one 200 Amp Bushing Well Interface and one 600 Amp Bushing Interface, 25kV, SV - Optional 6-1/2 inch Centers. No Parking Stand
M656I-K0240-S
600 Amp, Separable Cable Joint, 35KV, Separable Straight Joint Package, 2-Way with Test Point, Dead Break, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Cold-Shrinkable Jacket Seal Included.
M656CY-HP-200
600 Amp, Separable Cable Joint, 35KV, Basic Housing Package, Wye Joint with Test Point, 200 KV BIL (basic insulation level)
M655YDR-200
600 Amp, Separable Cable Joints, Insulated Cap with Bail, 35 KV, 200 KV BIL (basic Insulatiion level)Frequently Asked Questions
How do I order the K675RTW product?
To order the 15/25kV, 900A reducing tap well, specify K675RTW.
What is the K675RTW reducing tap well used for?
The K675RTW permits a 200A deadbreak or loadbreak tap-off from a 900A connector.
What type of inserts are compatible with K675RTW?
The K675RTW can be used with 200A Loadbreak or Deadbreak inserts.
What tool is required for K675RTW assembly?
A 600SW spanner wrench is required for the assembly of the K675RTW.
What industry standard does the K675RTW meet?
The K675RTW meets ANSI/IEEE Standard 386, Latest Revision.
What are the 15kV operating voltage limits for K675RTW?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV, and phase-to-phase is 14.4kV.
What is the continuous current rating for K675RTW?
The K675RTW has a continuous current rating of 900 Amps.
What is the impulse withstand rating for 15kV K675RTW?
For the 15kV voltage class, the impulse withstand (BIL) is 95kV (1.2 x 50 microsecond wave).
What are the 28kV operating voltage limits for K675RTW?
For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV, and phase-to-phase is 28kV.
What is the impulse withstand rating for 28kV K675RTW?
For the 28kV voltage class, the impulse withstand (BIL) is 140kV (1.2 x 50 microsecond wave).
How to Install Elastimold 600/900 AMP Deadbreak Plug and Well Products
This guide provides step-by-step instructions for the safe installation and voltage testing of Elastimold 600/900 AMP Deadbreak Plug and Well Products, designed for high voltage power distribution systems.
Estimated time: 1h
Tools needed:
Torque wrench, ELASTIMOLD 600SW spanner wrench, Hotstick, Suitable sensing device (for capacitive test points)
Supplies needed:
Deadbreak Plug or Well product, Elbow or Bushing Extension, Lubricant (supplied with product), Silicone lubricant, Stud (if not pre-installed on mating interface), HV insulated cap(s) or connector(s)
- Prepare for Installation and Safety Checks
Before beginning, ensure all apparatus are de-energized. Inspect all parts for damage, proper rating, and compatibility with mating components. Remove any protective shipping covers and replace them with appropriate HV insulated caps or connectors if the circuit is to be submerged or energized later. Ensure all required tools and the supplied lubricant are at hand, and maintain cleanliness throughout the procedure. This product must only be installed by competent personnel trained in high voltage electrical safety practices.
- Assemble and Lubricate the Plug/Well
Remove protective caps from the plug or well product. If the 600 amp mating interface is not equipped with a stud, hand tighten the stud into the 600 amp interface on the plug or well. Lubricate both the elbow and its mating part thoroughly with the supplied lubricant only. DO NOT SUBSTITUTE other lubricants, as they may harm the product. Ensure all surfaces of the elbow and mating parts remain clean during this process.
- Connect and Torque the Assembly
Carefully push the plug or well into the elbow or bushing extension until the threads engage. Using a torque wrench, tighten the assembly. For insulating plugs, apply 50 to 60 foot-pounds of torque. For connector plugs, tap plugs, or tap wells, use an ELASTIMOLD 600SW spanner wrench with the torque wrench, applying an indicated torque of 40 to 48 foot-pounds. Refer to special instructions IS-0915 for K651 and 750 rubber connecting plugs.
- Install Voltage Detection Cap (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap with silicone lubricant. Place the cap onto the elbow and push down firmly until it snaps securely into place. Proceed to perform the voltage test as described in the following steps.
- Perform Voltage Test
Remove the test point cap using a hotstick, peeling it off at an angle rather than pulling directly in line with the assembly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized. Contamination, moisture, or incorrect equipment can cause false readings. Always treat the elbow as energized until a 'no voltage' indication is confirmed by other means to prevent serious injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.