ABB Installation Products K656LR-H0330 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud…
UPC: 783786461059
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV Voltage Rating
- 600 Amp Continuous Current
- Series Deadbreak Elbow Design
- Includes Test Point, Insulated Plug, Cap, Stud, Lug, and Cable Adapter
- Aluminum Compression Lug for 500-600 kcmil Conductors
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Blue |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | K656LR |
Size | Cable Insulation Diameter 0.850 inch to 1.050 inch, Conductor Size Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300 |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 6.9500 L |
Package Weight (Metric) | 3.1530 kg |

K655SR-J0330
600 Amp, Straight Receptacle with Cable Adapter, Lug and Retaining Ring, DeadBreak, 15/25 KV, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300.
K656LR-K0260
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size Compressed/Stranded 3/0 or Compact/Solid 4/0 or mm2 Compact 95.
K656LR-L0300
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
K656LR-L0320
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 450 or Compact/Solid 500/550.
K656LR-L2290
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Copper Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150.
K656LR-J0230-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size Compressed/Stranded #1 or Compact/Solid 1/0 or mm2 Compact 50. Cold-Shrinkable Jacket Seal Included.
K656LR-H0300
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.Frequently Asked Questions
What is the maximum operating voltage for the K656LR elbow connector?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground and 14.4kV phase-to-phase. For the 28kV voltage class, it is 16.2kV phase-to-ground and 28kV phase-to-phase.
What conductor sizes can the K656LR handle?
The K656LR can be used with conductor sizes from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the continuous current rating for this elbow connector?
The K656LR elbow connector has a continuous current rating of 600 Amps.
What is the impulse withstand rating for the 28kV voltage class?
The impulse withstand rating for the 28kV voltage class is 140kV BIL for a 1.2 x 50 microsecond wave.
What is the AC one-minute withstand voltage for the 15kV class?
The AC one-minute withstand voltage for the 15kV voltage class is 34kV.
What is the corona extinction level for the 28kV voltage class?
The corona extinction level for the 28kV voltage class is 21.5kV AC at 3pC sensitivity.
What cable insulation diameters are supported by the K656LR?
The K656LR supports cable insulation diameters ranging from 0.640 inches to 1.935 inches.
What is the purpose of the test point on the K656LR?
The K656LR features a non-corrosive, capacitive test point for testing purposes.
Are there any recommended safety accessories for this product?
Yes, an ECS cable seal grounding device is highly recommended for safety when used on metallic tape shield or drain wire cable.
How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 600-ampere and 900-ampere deadbreak elbow connectors on 15kV and 25kV class systems. It covers cable preparation, connector assembly, and initial voltage testing. All apparatus must be de-energized during installation by competent personnel.
Estimated time: 1h 30m
Tools needed:
Crimping tool, Wire brush, Hotstick, Suitable sensing device for capacitive test points, Wire strippers
Supplies needed:
Elbow connector, Cable adapter, Compression lug, Insulating plug (if applicable), Lubricant, Threaded stud (if not pre-equipped), Wire with ampacity at least equivalent to No. 14 AWG Copper, Suitable grounding connector, Silicone lubricant
- De-energize Apparatus and Inspect Parts
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. Inspect all parts for damage, proper rating, and compatibility with mating parts before proceeding.
- Check Package Contents and Component Compatibility
Verify that the package contents are complete and undamaged. Check all components to ensure proper fit with the cable and/or mating products. Read the entire installation instructions before starting.
- Assemble Cable and Clean Outer Surface
Assemble the cable in its final position with enough slack to allow for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent back concentric neutral wires.
- Prepare Cable Outer Jacket and Shield
Remove the outer jacket (if applicable) and prepare the cable according to the specific type (e.g., non-jacketed concentric neutral, jacketed shield wires, flat metallic tape shield, fabric tape shield, longitudinally corrugated shield). Refer to specific instructions for 20MA/21MA grounding devices, 600ECS Jacket Cable Seal, or 10TL cable shield adapters if being used.
- Bevel, Clean, Lubricate, and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Remove Protruding Insulation and Verify Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If not, redo the assembly.
- Insert Conductor into Compression Lug and Crimp
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping (should be less than 6-3/8 inches). Crimp the compression lug following the supplied instructions. Wipe all excess inhibitor. The distance from the end of the lug to the cable adapter after crimping should be 6-3/8 inches to 7-1/8 inches (162mm-181mm).
- Lubricate and Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Product for Connection
WARNING: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part if the mating part is not equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Push Elbow onto Mating Part and Align
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place. Follow voltage test directions below.
- Ground the Cable Shield
Insert one end of a wire (at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded either through a grounding device (following its instructions) or an alternate method.
- Waterproof Cable Jacket
It is recommended to waterproof the jacket of the cable at this point to prevent moisture from entering the cable.
- Verify Component Torque
CAUTION: When constructing 600-amp L-Kits, ensure each component is tightened to the specified torque per the instructions provided with those components.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device, made for separable connectors with capacitive test points, to determine if the cable is energized. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury.
- Reinstall Test Point Cap
After voltage detection has been made, clean and lubricate the inside surface of the cap with silicone lubricant and replace it securely on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.