ABB Installation Products K656I-J0260-S 15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point.…
UPC: 075114170772
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15-25kV voltage rating for medium-voltage applications
- Accommodates cable insulation diameters 0.980–1.180 inch
- Aluminum compression lug for secure conductor termination
- Cold-shrinkable jacket seal included for environmental protection
- Integrated test point for safe voltage verification
- 2-way deadbreak design for medium-voltage cable systems
- Part of ABB Installation Products line
Specifications
Amperage Rating | 600 A |
Application | Compact Design is suitable for small vaults and manholes |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Connection Type | Deadbreak Separable |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 37.27 in |
Length | 946.658 mm |
Material | Housing - EPDM-Rubber |
Material | Aluminum, Poly |
Poles | 2-Way |
Series | 600 Series |
Size | 0.980-1.180 inch |
Special Features | Fully Shielded, Fully Submersible, 100 percent Peroxide cured Molded EODM Rubber |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Separable Straight Joint |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15-25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656LR-H0260-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 3/0 or Compact/Solid 4/0 or mm2 Compact 95. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656I-H0280-SG3
5-25kv Straight Joint 600 Amp, Dead Break with Seal. Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed Stranded 250 or Compacted Solid 300
K656I-J0300-SG3
15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656CY-H0280-SG3
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 250 /Compacted Solid 300. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656CY-J0300-SG3
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656YDSR-H0250-S
15-25kV 600 Series Deadbreak Direct Test Straight Receptacle Elbow with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70. Cold-Shrinkable Jacket Seal Included.
K656CY-H0260-S
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95. Cold-Shrinkable Jacket Seal Included.
K655YSR-G2240
600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Solid 2/0Frequently Asked Questions
What are the voltage ratings for the 25kV class?
For the 25kV class, the maximum phase-to-ground operating voltage is 16.2kV and maximum phase-to-phase is 28kV. It has a 140kV BIL impulse withstand.
What standard does the K656I joint meet?
The K656I separable straight joint meets ANSI/IEEE Standard 386, Latest Revision.
Is the K656I joint submersible?
Yes, the K656I separable straight joint is fully submersible.
What components are included in a complete joint package?
A complete joint package includes an insulated bus bar, straight receptacle housing, retaining rings, cable size adapters, lugs, bolts, and washers.
Can the K656I joint be used in direct-buried applications?
Yes, the K656I separable straight joint can be used in direct-buried applications.
Does the joint include a test point?
Yes, the K656I separable straight joint includes an integral capacitive test point.
What material is the joint made from?
The K656I separable straight joint is made from 100% peroxide cured EPDM molded rubber.
What is the momentary current rating?
The momentary current rating for the K656I separable straight joint is 25kA Symmetrical for 10 cycles.
What is the continuous current rating for the joint?
The K656I separable straight joint has a continuous current rating of 600 Amps for both 15kV and 25kV voltage classes.
What is the K656I separable straight joint used for?
The K656I separable straight joint is used to join cables in a disconnectable 2-way joint. It is suitable for small vaults, manholes, and direct-buried applications.
How to Install K656 Deadbreak Receptacles
This guide provides detailed instructions for the installation and wiring of K656CY, K656CH, and K656I deadbreak receptacles, including cable preparation and final assembly.
Estimated time: 2h
Tools needed:
Hex wrench, Torque wrench with 15/16 inch socket, Wire brush (for aluminum cable), 650ATY assembly tool OR 600RRT assembly tool, Wire strippers, Rag
Supplies needed:
K656 Receptacle housings, Cable adapters, Center sections (I, Wye, or H), Aluminum holding collars, Lubricant, Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod, Tape, Approved safety solvent, Conductive copper strip (for flat metallic tape shielded cable), No. 14 AWG copper wire (or equivalent)
- Perform Pre-Installation Checks and Safety Procedures
Before starting, ensure all apparatus is de-energized. Inspect all parts for damage, correct rating, and compatibility. Verify package contents are complete and undamaged. Check component fit with cable and mating products. Read all instructions thoroughly and have required tools ready. Maintain cleanliness throughout the procedure. Failure to follow safety instructions can result in serious injury or product damage.
- Prepare the Cable Outer Jacket and Slide Components
Wipe the outer jacket clean for a distance of 38 inches from the end. Cut the cable end squarely to ensure maximum length for crimp growth. If using an ECS grounding device, slide the ECS tube onto the cable 38 inches. Slide the receptacle housing onto the cable 30 inches.
- Prepare the Cable for Conductor Exposure
Refer to the special cable preparation supplement (Part A for Jacketed Concentric Neutral Cable or Part B for Flat Metallic Tape Shielded Cable with Semi-con Shield) and follow the specific procedure for your cable type. This involves precise jacket, neutral wire, and semi-con shield removal, cleaning, and beveling of the insulation. Ensure the insulation is thoroughly cleaned with an approved safety solvent.
- Install Cable Adapter and Retaining Ring
Remove any protruding cable insulation, cutting it even with the end of the cable adapter. Do not cut or nick the adapter or conductor. The exposed conductor should measure 4 3/4 to 5 inches. Assemble the aluminum retaining ring over the conductor, snugging it firmly against the cable adapter. Hand tighten the socket head screw with the provided hex wrench. Confirm the exposed conductor now measures 4 3/8 to 4 3/4 inches; otherwise, redo the assembly.
- Prepare and Crimp the Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately fully insert it into the crimp connector (which contains inhibitor). Measure the distance from the end of the connector to the holding collar; if over 7 inches, redo previous work. Confirm bolt holes in the crimp connectors align with mating part holes. Crimp the connectors according to their instructions, rotating each crimp 90 or 180 degrees. Re-measure the distance from the end of the connector to the holding collar; if over 7 inches, redo previous work.
- Assemble Washers and Bolts
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten the bolt. The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after bolts are tightened.
- Torque Bolts and Lubricate Components
Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. Apply the supplied or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the splice section, and the inside mating surface of the receptacle housing.
- Slide Receptacle Housing and Insert Venting Rod
Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied) into the assembly.
- Complete Housing Installation Using Assembly Tool
Choose the appropriate assembly tool (650ATY or 600RRT). If using 650ATY, attach the tool with the 'U' shaped yoke over the splice section and the 'C' shaped yoke over the receptacle housing, then slowly raise the handle to slide the housing. If using 600RRT, attach the tool and slide the housing by turning the hex nut. Remove the venting rod after the housing is in place. WARNING: Do not place hand on threaded rod or guide shaft with the assembly tool in place.
- Perform Final Checks and Grounding
Check all cable adapters to ensure they are properly located and remove any vinyl tape markers. Complete the installation of the ECS grounding device according to its instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, making a small loop and twisting tightly without damaging the eye, then connect to ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.