ABB Installation Products K655LR-G0280-SG3 600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786829026
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating for medium-voltage systems
- Cable insulation diameter range: 0.760" to 0.950"
- Accommodates conductors up to 250 kcmil (compressed/stranded) or 300 kcmil (compact/solid)
- Cold shrinkable seal with copper braid and constant force spring for secure termination
- Fully molded rubber housing for submersible protection and dielectric integrity
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 250 kcmil , 300 kcmil |
Connection Type | Deadbreak Elbow |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | EPDM, Aluminum, Copper |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 0.760–0.950 inch, Conductor Size 250 kcmil or 300 kcmil |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

755LRTP-L0280-DRG
600 Amp, 35kV, Stick-Op Connector Kit with Test Point, Insulated Cap and Reducing Tap Plug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 250 or Compacted Solid 300.
K656LR-K0290-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656LR-L0360
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 650 or Compact/Solid 750 or mm2 Compact 400.
K656LR-K5330-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Bi-Metal Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656LR-L2230
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Copper Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded #1 or Compact/Solid 1/0 or mm2 Compact 50.
K656LR-K5330-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Bi-Metal Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300. Cold-Shrinkable Jacket Seal Included.
K656LR-L5330-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Bi-Metal Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656LR-L0360-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 650 or Compact/Solid 750 or mm2 Compact 400. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
What is the maximum operating voltage for the K655LR elbow connector?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground and 14.4kV phase-to-phase. For the 28kV voltage class, it is 16.2kV phase-to-ground and 28kV phase-to-phase.
What conductor sizes can the K655LR handle?
The K655LR can be used with conductor sizes ranging from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the insulation diameter range for this elbow connector?
The K655LR is designed for insulation diameters ranging from 0.640 inches to 1.935 inches.
What is the continuous current rating for the K655LR?
The K655LR has a continuous current rating of 600 Amps.
What is the momentary current rating for the K655LR?
The K655LR has a momentary current rating of 25kA Sym for 10 Cycles.
What is the impulse withstand rating for the 28kV voltage class?
For the 28kV voltage class, the impulse withstand rating is 140kV BIL (1.2 x 50 microsecond wave).
What is the AC one-minute withstand voltage for the 15kV class?
For the 15kV voltage class, the AC one-minute withstand voltage is 34kV.
What is the AC one-minute withstand voltage for the 28kV class?
For the 28kV voltage class, the AC one-minute withstand voltage is 45kV.
What is the corona extinction rating for the 15kV class?
The corona extinction rating for the 15kV voltage class is 11kV AC @ 3pC sensitivity.
What is the corona extinction rating for the 28kV class?
The corona extinction rating for the 28kV voltage class is 21.5kV AC @ 3pC sensitivity.
How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 600-ampere and 900-ampere deadbreak elbow connectors on 15kV and 25kV class systems. Ensure all apparatus are de-energized before beginning.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush, Hotstick, Suitable sensing device, Torque wrench
Supplies needed:
Elbow Connector (655/675LR or K655/K675LR), Cable Adapter, Compression Lug, Insulating Plug, Lubricant (supplied with kit), Threaded Stud (supplied with kit), No. 14 AWG Copper wire (or equivalent), Suitable grounding connector, Silicone lubricant
- De-energize Apparatus and Inspect Parts
Ensure all apparatus are de-energized during installation or removal of parts. Inspect all connector parts for damage, correct rating, and compatibility with mating parts. Failure to follow these instructions will result in damage to the product and serious or fatal injury.
- Prepare Cable for Assembly
Assemble the cable in its final assembled position with enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer surface of the cable a distance of 24” (610mm) or up to the bent back concentric neutral wires.
- Perform Cable Preparation
Follow the specific instructions (A, B, or C) that apply to your cable type for proper preparation. This includes removing the outer jacket (where applicable) and preparing the cable insulation, semi-con shield, and shield wires to the specified dimensions as shown in the diagrams.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean, then lubricate the cable insulation always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of exposed conductor should be between 4-1/4” and 4-9/16” (108mm-116mm). Otherwise, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the “Check Dimension” before crimping (must be less than 6-3/8”). Crimp the compression lug following the instructions supplied with the lug. Wipe all excess inhibitor from the lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-3/8” to 7-1/8” (162mm-181mm). Otherwise, redo the assembly.
- Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until the elbow cannot advance further. Make sure the cable adapter is still flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products
Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part, if the mating part is not equipped with a stud. Clean and lubricate both the elbow and the mating part with the lubricant supplied, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with the mating part.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow. Push down hard until the cap snaps into place. Follow the voltage test directions below.
- Ground the Cable Shield
Insert one end of a piece of wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop. Do not damage the eye. Connect the wire to ground using a suitable connector. The shield of the cable must be grounded according to the instructions supplied with the grounding device or through an alternate method. It is also recommended that the jacket of the cable be waterproofed at this point to prevent moisture from entering the cable.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Use a suitable sensing device made for capacitive test points. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.