Overview
- 15kV Voltage Rating
- Multiple Current Ratings: 200A and 600A Bushing Well Interfaces
- 4-Point Junction Configuration
- Right Parking Stand Mounting Type
- ABB Installation Products Manufacturer
Specifications
Application | Suited for Subsurface, Vault or Padmount Applications and can be used for Sectionalizing, Looping, Tapping and Equipment Bypass |
Connection | Push-In |
Material | EPDM-Rubber and Stainless Steel Mounting Brackets |
Mounting | Right Parking Stand |
Size | Overall Length 20.5 inches, Width 6.75 inches |
Special Features | 4 inch Center Spacing |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Multi-Point Junction - 4 Points |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

J4-6226-15
4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interfaces and one 200 Amp Bushing Well Interface, 15kV, No Tilt Mounting.
J4-6226-15-SV
4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interfaces and one 200 Amp Bushing Well Interface, 15kV, 6-1/2 inch centers. No Tilt Mounting.
J4-2666-15-N
4 Point Junction, with one 200 Amp Bushing Well Interface and three 600 Amp Bushing interfaces, 15kV, No Parking Stand.
J4-2666-25-SV
4 Point Junction, with one 200 Amp Bushing Well Interface and three 600 Amp Bushing interfaces, 15kV, 6-1/2 inch centers. No Tilt Mounting.
J4-6226-15-N
4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interfaces and one 200 Amp Bushing Well Interface, 15kV, No Parking Stand.
J4-6226-15-L
4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interfaces and one 200 Amp Bushing Well Interface, 15kV, Left Parking Stand.
J4-2662-15-N
4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interface and one 200 Amp Bushing Well Interface, 15kV, No Parking Stand.
J4-2662-25-TMA
4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interface and one 200 Amp Bushing Well Interface, 25kV, Tilt Mounting Adapter.Frequently Asked Questions
What are the voltage classes for this junction?
The multipoint junctions are available for 15kV, 25kV, and 35kV voltage classes.
What is included in a standard junction kit?
Each kit contains one basic molded junction, mounting hardware, two tubes of lubricant, installation instructions, and a protective cap.
What are the available interface spacing options?
The units feature modular design flexibility, allowing selection of 4'' standard spacing or optional 6.5'' spacing.
What is the impulse withstand rating for a 35kV junction?
For a 35kV voltage class, the impulse withstand (BIL) is 150kV (1.2 x 50 microsecond wave).
How many points can the junction have?
The junction can be ordered with 2, 3, 4, 5, or 6 points.
What is the maximum operating voltage for a 25kV class junction?
For a 25kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV.
What is the maximum operating voltage for a 35kV class junction?
For a 35kV voltage class, the maximum phase-to-ground operating voltage is 21.1kV.
What is the maximum operating voltage for a 15kV class junction?
For a 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV.
What materials are used in the junction's construction?
The junction features a fully shielded, submersible molded rubber housing with 100% peroxide-cured EPDM materials. Brackets utilize 304 stainless steel.
What types of connectors are compatible?
The junctions provide mating for Elastimold Elbow connectors, both 600 Amp and 200 Amp series.
How to Install a Deadbreak Junction (Universal Mount)
This guide provides step-by-step instructions for installing a two-, three-, or four-point deadbreak junction using the universal mount method, including mounting, assembly, and grounding procedures for models like J4-6226-15-R.
Estimated time: 1h
Tools needed:
Wrench or Socket Set, Marking Tool, Wire Strippers
Supplies needed:
Deadbreak Junction (2-, 3-, or 4-point), Base Bracket, Base Plate, 4 Universal Brackets, Suitable fasteners (user supplied), 3/8” Hex Head Cap Screws, External Tooth Lock Washers (3/8”), 3/8” Hex Nuts, 1/2” Hex Head Cap Screws, 1/2” Split Lock Washers, 1/2” Hex Nuts, Grounding wire (No. 2 solid to 1/0 stranded), HV insulated caps (for unused bushings), ELASTIMOLD approved lubricant
- De-energize and Inspect
DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all parts for damage, correct rating, and compatibility with mating parts before proceeding. Failure to follow these instructions will result in damage to the product and serious or fatal injury.
- Determine Mounting Location and Mark Slots
Select the desired location for the junction assembly. Use the base plate as a template, place it on the mounting surface, and mark the slot locations for drilling or fastener placement.
- Attach Initial Universal Brackets
Secure two (2) universal brackets to the flat mounting surface using suitable fasteners. Tighten them securely to prevent any movement during operation.
- Attach Remaining Universal Brackets
Connect the remaining two (2) universal brackets to the two brackets already mounted on the surface at your desired angle. Use the supplied 3/8” hex head cap screws, external tooth lock washers, and 3/8” hex nuts. Tighten securely.
- Assemble Junction to Base Bracket and Base Plate
Attach the deadbreak junction to the base bracket assembly and base plate. Use two (2) 1/2” hex head cap screws, two (2) 1/2” split lock washers, and two (2) 1/2” hex nuts through the center mounting holes on the bracket assembly. Tighten securely.
- Mount Junction Assembly to Universal Brackets
Secure the assembled deadbreak junction to the universal brackets using the supplied 1/2” hex head cap screws, 1/2” split lock washers, and 1/2” hex nuts. Ensure the parking stand is in the upright position and tighten all hardware securely.
- Ground the Junction Assembly
Connect a grounding wire (No. 2 solid to 1/0 stranded) to the grounding lug provided on the base bracket. Ensure the base bracket assembly and the junction’s black conductive jacket are properly grounded.
- Prepare Operating Interfaces
Remove all protective shipping caps from the operating interfaces. Clean each interface thoroughly and lubricate them with an ELASTIMOLD approved lubricant. DO NOT SUBSTITUTE, as other lubricants may be harmful to this product or its mating product(s).
- Install Insulated Caps on Unused Bushings
If not all operating interfaces will be utilized, install appropriate HV insulated caps or connectors on any unused bushing(s) before energizing the circuit. Do not use the protective shipping caps for this function as they are not insulated.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.