ABB Installation Products 756LR-K0270-S 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786826506
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV class, 900 Amp deadbreak elbow connector with integrated test point
- Accommodates cable insulation diameters from 1.090" to 1.310"
- Compatible with 4/0 AWG stranded, 250 kcmil compacted solid, or 125 mm² compact conductors
- Fully shielded, fully submersible molded rubber housing with 100% peroxide-cured EPDM
- Meets ANSI/IEEE Standard 386, rated for 25kA symmetrical momentary current
- Cold-shrinkable jacket seal for environmental protection
- Includes insulated plug, cap, stud, lug, and cable adapter
- Aluminum construction for corrosion resistance and mechanical strength
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Compression |
Connection Type | Compression Lug |
Current Rating | 900A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | 1.090-1.310 inch (cable insulation diameter) |
Special Features | 35kV, 600 Amp Deadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. S - Cold-Shrinkable Jacket Seal |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Voltage Rating | 35kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

756LRTP-K0270-DRG
600 Amp, 35kV, Deadbreak, Stick-Op Connector Kit, with Capacitive test point, Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. With Insulated Cap.
756LR-J2270-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-M0380-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold-Shrinkable Jacket Seal Included.
756LR-M0300-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold-Shrinkable Jacket Seal Included.
756LR-M0290
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150.
756LR-J2240-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-K0250
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70.
756LR-J0270-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.Frequently Asked Questions
What is the primary application of the 756LR elbow?
The Elastimold 756LR elbow provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What is the Basic Impulse Level (BIL) withstand rating?
The BIL impulse withstand rating is 150kV (1.2 x 50 microsecond wave).
Can the 756LR be connected or disconnected while energized?
No, the 756LR can only be connected or disconnected using standard hand tools and equipment in a de-energized state.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 cycles.
What is the continuous current rating?
The continuous current rating for the 756LR is 600 Amp.
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage is 50kV.
What is the maximum phase-to-ground operating voltage?
For the 35kV voltage class, the maximum phase-to-ground operating voltage is 21.1kV.
What industry standard does the 756LR meet?
The 756LR meets ANSI/IEEE Standard 386, Latest Revision.
What cable insulation diameters does the 756LR support?
The 756LR supports cable insulation diameters ranging from 0.760 inches to 2.120 inches.
What conductor sizes are compatible with the 756LR?
It is compatible with conductor sizes from #2 AWG to 1250 kcmil for aluminum and copper conductors.
How to Install 756/776LR Deadbreak Elbow Connectors
The 756/776LR connectors provide fully shielded, fully submersible deadfront cable connections to high voltage apparatus. This guide details the installation process for these 35kV class deadbreak elbow connectors, including cable preparation, component assembly, and grounding.
Estimated time: 2h
Tools needed:
Wire strippers, Cutting tool, Wire brush, Crimping tool, Torque wrench, Hotstick, Suitable voltage sensing device
Supplies needed:
756LR/776LR Deadbreak Elbow Connector Kit (includes Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), Protective caps, Wire (at least No. 14 AWG Copper), Suitable connector (for grounding wire), Grounding device (optional)
- Position and Cut Cable
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Position the cable in its final assembled location, ensuring enough slack for elbow removal. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm).
- Prepare Cable According to Type
Follow the specific cable preparation instructions based on your cable type. If using a 20MA or 21MA grounding device or 600ECS Jacket Cable Seal, refer to their instructions for jacket removal, shield connection, and grounding. For UNISHIELD* or LEAD SHEATH cable, use a 10TL cable shield adapter and refer to its instructions. For jacketed and non-jacketed cables, remove the outer jacket (if applicable) and prepare the cable as shown in the diagrams, marking the cable insulation, semi-con shield, and outer jacket at the specified lengths (10-3/8 inches, 11-3/8 inches, 13-5/8 inches).
- Bevel, Clean, Lubricate, and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean the cable insulation, then lubricate it, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Remove Protruding Insulation and Verify Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Exercise caution to avoid cutting or nicking the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm). If the length is outside this range, redo the assembly.
- Insert Conductor and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; it must be less than 7 inches (178mm). Crimp the compression lug according to the instructions provided with the lug. After crimping, wipe all excess inhibitor from the compression lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter must be between 6-7/8 inches to 7-5/8 inches (175mm-194mm). If any dimension is incorrect, redo the assembly.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Part and Elbow
WARNING: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud (supplied with the elbow) into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Push Elbow onto Mating Part
Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Clean, Lubricate, and Insert Opposite Mating Part
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its supplied instructions.
- Install Insulating Plug and Voltage Detection Cap (If Used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place. CAUTION: The insulating plug provides a means for detecting system voltage. Follow VOLTAGE TEST directions below.
- Ground the Cable Shield
Insert one end of a wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with a grounding device, or use an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test and Replace Cap
CAUTION: When constructing 600amp L-Kits be sure to tighten each component to specified torque per instructions provided with plug connectors. If the ELASTIMOLD® connector is equipped with an integral capacitance test point, use it to determine if the circuit is energized. Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points and follow its manufacturer's directions. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means, as contamination or incorrect equipment can cause false readings. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.