ABB Installation Products 69TCJN1Q231PQAVNB 69 kv, Transmission Cable Joint, Housing Type - Non-Shieldbreak, Housing Style 1…
UPC: 783786459278
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Factory-molded and 100% factory-tested for maximum reliability
- Non-shieldbreak housing design for simplified installation
- Copper connector (Code 31P) compatible with 0.687–0.745" (17.45–18.92 mm) conductors
- Housing size Q: 1.750" bore diameter, 1.625" heatsink bore for thermal management
- Metallic screen continuity kit (Type V) includes #2 flat braid (6-foot length)
- Outer jacket restoration kit (Type B) uses heat-shrink technology for reliable sealing
- Designed for solid dielectric cables with insulation diameters 36.5–65.5 mm (1.43–2.58")
- No field molding, tape-wrapping, or specialized machinery required
- Fully shielded and submersible for direct burial or vault applications
Specifications
Application | For use on Solid Dielectric Cables - providing permanent, fully-shielded, fully submersible cable joints for direct burial or vault applications |
Color | Black |
Conductor Range | .687 to .745 in |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Special Features | Each Cable Joint is produced exactly to design, producing a quality not possible with field molding equipment or tape. Electrically tested in the factory to ensure consistent quality. Molding is done in the factory, reducing on-site time - no penciling of cable installation required. Easy to learn installation procedure. Field molds, wrapping machines or pre-stretch not required, and a low-cost assembly tool is available. Extended shelf life enables instant availability of spares. Designed with optimized pre-molded stress control and heat transfer capabilities |
Standard | ANSI C119.4, Shield Test IEEE 592 |
Temperature Rating, Maximum | 194 F |
Temperature Rating, Maximum | 90 C |
Temperature Rating, Minimum | 194 F |
Temperature Rating, Minimum | 90 C |
Type | Transmission Cable Joint - Non-Shieldbreak |
Voltage Rating | 69 kV |
Package Dimensions (L x W x H) | 48.62 IN x 11.37 IN x 10.25 IN |
Package Dimensions (L x W x H) | 123.4948 cm x 28.8798 cm x 26.035 cm |
Package Weight (Imperial) | 26.3500 L |
Package Weight (Metric) | 11.9520 kg |

115TCJS32A31POOBNNB
115kV, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 3, Housing Size 2 - Bore Diameter 1.725 inch, Insulation Range 1.967-2.620 inch, Connector Type - Aluminum - No Connector Required, Conductor Code 31P - .687-.745 inch Diameter, Heatsink Size Not Included, Heatsink Bore Diameter Not Included, Type Shield B - Copper Neutral Wire, Metallic Screen Continuity Kit Not Required, Armour Kit - Not Required, Outer Jacket Restoration Kit B - Heat Shrink Standard package.
69TCJN1Q136PNDNNB
69 kv, Transmission Cable Joint, Housing Type - Non-Shieldbreak, Housing Style 1, Housing Size Q Bore Diameter at Jacket/Insulation Transition 1.750. Connector Type - Aluminum, Connector Code 36P - Conductor Diameter Range - .901-.935 inch (22.88-23.75mm), Heatsink Size/Bore - N - 1.500 inch Diameter. Type Shield - D - Copper Tape and Neutral Wire, Metallic Screen Continuity Kit - N - not required, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - HeatShrink
69TCJN1Q
69 kv, Transmission Cable Joint, Housing Type - Non-Shieldbreak, Housing Style 1, Housing Only, Housing Size Q Bore Diameter at Jacket/Insulation Transition 1.750.
69TCJN43246P3LABNN
69 kv, Transmission Cable Joint, Housing Type - Non-Shieldbreak, Housing Style 4, Housing Size 3, Connector type Copper, Connector Code 46P - Conductor Diameter Range - 1.328-1.377 inch (33.73-34.98mm), Heatsink Size 3 - Outside Diameter 2.250 inch ( 57.15mm), Heatsink Bore - L - 1.406 inch Diameter. Type Shield - A - Copper Tape, Metallic Screen Continuity Kit - B -4/0 Bonding Cable 6 foot quantity 2 with Split Bolts quantity 4, Armor Kit - N - not required, Outer Jacket Restoration Kit - N - not required
69TCJS1PB40PNLNNB
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size P Bore Diameter at Jacket/Insulation Transition 1.570. Connector Type - Copper/no connector required, Connector Code 40P - Conductor Diameter Range - 1.036-1.100 inch (26.31-27.94mm), Heatsink Bore - N - 1.500 inch Diameter.. Type Shield - L - Lead and Neutral Wires, Metallic Screen Continuity Kit - N - not required, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - Heat Shrink
69TCJS1NB38PNNNN
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size N Bore Diameter at Jacket/Insulation Transition 1.390. Connector Type - Copper/No connector required, Connector Code 38P - Conductor Diameter Range - .936-1.011 inch (23.77-25.68mm), Heatsink Bore - N - 1.500 inch Diameter.Type Shield - N - Unknown, Metallic Screen Continuity Kit - N - not required, Armor Kit - N - not required
69TCJN1P238PUBANB
69 kv, Transmission Cable Joint, Housing Type - Non-Shieldbreak, Housing Style 1, Housing Size P Bore Diameter at Jacket/Insulation Transition 1.570. Connector Type - Copper, Connector Code 38P - Conductor Diameter Range - .936-1.011 inch (23.77-25.68mm), Heatsink Size/Bore - U - 1.953 inch Diameter. Type Shield - B - Copper 1/3 Neutral Wire, Metallic Screen Continuity Kit - A - 4/0 Bonding Cable 6 foot quantity 1 with split bolts quantity 4, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - HeatShrink
69TCJN1N230PEBNNB
69 kv, Transmission Cable Joint, Housing Type - Non-Shieldbreak, Housing Style 1, Housing Size N Bore Diameter at Jacket/Insulation Transition 1.390. Connector Type - Copper, Connector Code 30P - Conductor Diameter Range - .636-.686 inch (16.15-17.42mm), Heatsink Size/Bore - E - .921 inch Diameter. Type Shield - B - Copper 1/3 Neutral Wire, Metallic Screen Continuity Kit - N - not required, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - HeatShrinkFrequently Asked Questions
How are the joint ends sealed during installation?
The joint ends are sealed with mastic wrap during the installation process.
What are TCJ transmission cable joints used for?
TCJ transmission cable joints are designed for 46 kV through 138 kV class systems on solid dielectric cables. They provide permanent, fully shielded, fully submersible joints for direct-burial or vault applications.
What cable insulation diameters are compatible?
For Style 1 (up to 69 kV), compatible insulation diameters range from 1.43 in to 2.58 in. For Style 4 (up to 138 kV), the range is 2.25 in to 3.62 in.
What is the maximum continuous operating temperature?
The maximum continuous conductor temperature for these cable joints is 90 °C.
What voltage classes do these cable joints support?
TCJ transmission cable joints support nominal system voltages of 69 kV and 138 kV, with maximum system voltages of 72.5 kV and 145 kV respectively.
Are the cable joints factory tested?
Yes, all TCJ transmission cable joints are factory molded and factory tested to ensure maximum reliability and consistent quality.
What type of applications are suitable for these joints?
These cable joints are suitable for direct-burial or vault applications, providing permanent, fully shielded, and fully submersible connections.
What types of conductor connectors are compatible?
Conductors can be joined using compression, welded, or other types of connectors. Splice compression connectors should conform to ANSI C119.4 Class A/class 2.
Is a shield break option available?
Yes, a shield break option is provided for cross bonding purposes on Style 4 joints. Joints may be installed as a standard shield break or non-shield break.
What safety precautions should be taken during installation?
Users must refer to local codes for required Personal Protective Equipment (PPE) during installation.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.