ABB Installation Products 655CK-L5360 600 Amp, 15/25KV, Cam-Op, Size Sensitive Kit, (Cable Adapter, and Lug), Cable Insulation…
UPC: 783786415991
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600A continuous current rating for 15/25kV systems
- Accommodates cable insulation diameters 1.180" to 1.465"
- Bi-metal compression lug for copper conductors (AWG 650 stranded / 750 solid or 400mm²)
- Cam-Op mechanism eliminates need for specialized tools
- Meets ANSI/IEEE Standard 386 with 25kA momentary rating
Specifications
Application | Deadbreak, 600 Amp, 15/25kV |
Connection | Compression |
Connection Type | Cam-Op |
Current Rating | 600 A |
Material | EPDM Cable Adapter |
Material | Bi-Metal (Copper + Aluminum) |
Series | 655CK |
Size | Conductor Size kcmil Compressed/Stranded 650 or Compact/Solid 750 |
Size | 1.180-1.465 inches (cable insulation diameter), AWG 650 (compressed stranded), 750 (solid), 400 mm² |
Standard | ANSI/IEEE 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Cable Adapter and Lug |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.5000 L |
Package Weight (Metric) | 0.6800 kg |

J6-622226-25
6 Point Junction, with one 600 Amp Bushing Interfaces, four 200 Amp Bushing Well Interface and one 600 Amp Bushing Interface, 25kV, No Tilt Mounting.
655CK-H0270-ARR-S
600 Series Straight Receptacle Size Sensitive Kit, 15/25KV, 600 Amp, Dead Break, (Cable Adapter, Retaining Ring and Lug), Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or kcmil Solid 250 or mmSquared 126.67. 200ECS Jacket Seal Included.
655CK-H5240
600 Amp, 15/25KV, Cam-Op, Size Sensitive Kit, (Cable Adapter, and Lug), Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
655CK-K0330-ARR-S
15/25kV, 600 Amp, Deadbreak, Cable Adapter, Lug and Adapter Retaining Ring. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. 200ECS Cold-Shrinkable Jacket Seal Included.
655CK-K0320-ARR-S
15/25kV, 600 Amp, Deadbreak, Cable Adapter, Lug and Adapter Retaining Ring. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 kcmil or Compacted Solid 500/550 kcmil. 200ECS Cold-Shrinkable Jacket Seal Included.
655CK-J0300-ARR
15/25kV, 600 Amp, Deadbreak, Cable Adapter, Lug and Adapter Retaining Ring. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
655CK-G0240-ARR-S
600 Series Straight Receptacle Size Sensitive Kit, 15/25KV, 600 Amp, Dead Break, (Cable Adapter, Retaining Ring and Lug), Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Solid 2/0 or mmSquared 53.49. 200ECS Jacket Seal Included.
675CK-N2380
900 Amp, 15/25kV, Deadbreak, Cable Adapter and Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.Frequently Asked Questions
What conductor materials are compatible?
The kit is compatible with Universal Aluminum, Copper, and Bi-metal conductor materials.
What components are included in each kit?
Each kit contains one copper compression lug (03700XXX), one cable adapter (655CA-W), and one crimp chart (CC-0050).
What materials are used in the kit's construction?
The kit features 100% peroxide-cured construction, including insulation and conductive EPDM materials.
What is the 28kV impulse withstand rating?
For the 28kV voltage class, the impulse withstand (BIL) is 140kV.
What are the 28kV operating voltage limits?
For 28kV, the maximum phase-to-ground operating voltage is 16.2kV and maximum phase-to-phase is 28kV.
What is the 15kV impulse withstand rating?
For the 15kV voltage class, the impulse withstand (BIL) is 95kV.
What is the continuous current rating?
The continuous current rating for both 15kV and 28kV voltage classes is 600 Amps.
What are the 15kV operating voltage limits?
For 15kV, the maximum phase-to-ground operating voltage is 8.3kV and maximum phase-to-phase is 14.4kV.
What standard does the 655CK kit meet?
The 655CK kit meets ANSI/IEEE Standard 386, Latest Revision.
What are the applications of the 655CK kit?
The 655CK kit provides size sensitive components for all 15/25kV, 600 series connectors, except Stick-Op and those needing a retaining ring.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.