ABB Installation Products 655CETP-K0300S 15kv 600 Amp Dead Break Combo T Elbow with 200 Amp Reducing Tap Plug, Stud, Cable…
UPC: 075114274760
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV rated, 600 Amp dead-break combo T elbow with 200 Amp reducing tap plug
- Universal aluminum compression lug for 350 kcmil compressed stranded or 400 kcmil solid compact conductors
- Cable insulation diameter compatibility: 1.090" to 1.310"
- Cold-shrinkable jacket seal for moisture resistance and long-term reliability
- No test point included; designed for dead-break connections in medium-voltage systems
Specifications
Amperage Rating | 600 A |
Application | 600 Amps, 15kV Connector |
Color | Black |
Conductor Range | 350 kcmil , 400 kcmil |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Aluminum |
Series | 655CETP |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Special Features | Reducing Tap Plug with Stud, Cable Adapter, and Lug |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | ComboT Elbow |
Voltage Rating | 15 kV |
Width | 13.31 in |
Width | 338.074 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

656LRTP-J0300
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
K656CETP-N0410-DRG
15/25kV, 600 Amp Base Aluminum, includes test point, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. With Insulated Cap.
655CETP-M0380-S
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug, No Test Point, Aluminum, Cable Insulation Diameter 1.370 inch to 1.630 inch. With Shrink-Fit Jacket Seal Kit. Aluminum Compression Lug, 700/750 kcmil Stranded/Compressed or 900 kcmil Solid/Compact.
655CETPH0270-S
15kV, 600 Amp, Combo T Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit. Cable Insulation .850-1.050 inches. Universal Aluminum Connector Type, Connector Size 4/0 Stranded/Compressed or 250 Compact/Solid. With Shrink-Fit Jacket Seal Kit. No Test Point.
655CETPL5330-DRG
15kV, 600 Amp, Combo T Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit. Cable Insulation 1.180-1.465 inches. Copper/Aluminum Bi-Metal Connector Type, Connector Size 500 Stranded/Compressed or 600 Compact/Solid. With Insulated Cap. No Test Point.
655CETP-G0230-S
15kv, 600 Amp, Combo T Connector with Bus, Stud, Cable Adapter and Aluminum Lug, also includes Sealing Kit, Cable Insulation Diameter .760-.950 inches, Conductor Size #1 Compressed/Stranded or 1/0 Compact/Solid.
755LR-M0320-S
35kv 600 Amp Elbow Deadbreak With Sealing Kit, 600 Series Elbow (with insulating Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation Diameter 1.370-1.630, Aluminum Lug, Conductor 450 Stranded/Compressed or 500 Compact/Solid.Frequently Asked Questions
What do the color-coded interfaces indicate?
Red interfaces are for 15 kV reducing taps, and blue interfaces are for 25 kV reducing taps. This provides better visibility and seating indication.
What is the primary safety precaution for ComboT installation?
The system needs to be de-energized before initiating any ComboT installation. Always refer to the complete instruction sheet.
What torque is required for CCP bus installation?
When installing the CCP bus, insert the 600ATM and torque it to 50 to 60 ft.-lbs. The BIP also requires 50 to 60 ft.-lbs. of torque.
What are the continuous current ratings for CCP/CBW connectors?
CCP and CBW connectors have continuous current ratings of 600 A or 900 A, depending on the specific series.
What are the voltage ratings for the K655K656 CCP series?
The K655K656 CCP series has a max phase-to-ground operating voltage of 16.2 kV and a max phase-to-phase operating voltage of 28.0 kV. Its BIL impulse withstand is 140 kV.
What are the continuous current ratings for CETP connectors?
CETP connectors have continuous current ratings of 600 A for deadbreak and 200 A for loadbreak connections. Some configurations also support 900 A deadbreak.
How much does the ComboT reduce stack height?
Each combination elbow/connecting plug reduces the stack height by 2.67 inches.
What are the voltage ratings for the 15 kV CETP?
The 15 kV CETP has a max phase-to-ground operating voltage of 8.3 kV and a max phase-to-phase operating voltage of 14.4 kV. Its BIL impulse withstand is 95 kV.
How does the 25 kV reducing tap prevent flashover?
The 25 kV reducing tap includes vents to prevent partial-vacuum flashover.
What stud size is used for ComboT assembly?
The ComboT assembly utilizes a standard 5/8 in–11 stud that threads into the equipment bushing.
How to Install 655/656/675/676CETP Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and connection of 655/656/675/676CETP deadbreak elbow connectors on high voltage apparatus, including cable preparation, grounding, and optional voltage testing.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, 600AT assembly tool, 600ATM assembly tool, Hotstick, Suitable voltage sensing device, Wire brush
Supplies needed:
Compression lug, Lubricant, Vinyl plastic tape, Grounding wire (No. 14 AWG Copper or equivalent), Suitable ground connector, Tape marker, Tape retainer, HV insulated cap
- De-energize Apparatus and Inspect Components
DANGER: Ensure all apparatus is de-energized during installation or removal of parts to prevent serious or fatal injury. Inspect all package contents to ensure they are complete and undamaged. Verify all components for proper fit with the cable and/or mating products. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Position Cable and Cut
Position the cable in its final assembled location, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Surface
Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.
- Prepare Cable Outer Jacket and Shield
Remove the cable's outer jacket to the dimension shown in the product diagrams. Fold back shield wires. If using flat metallic tape shield, remove it and secure with vinyl plastic tape to the dimension shown. If using fabric tape shield, remove it and install a tape retainer and tape marker to the dimensions shown. If using longitudinally corrugated shield, remove it and install a tape marker to the dimension shown. If using semi-con shield, remove it and install a tape marker to the dimensions shown, being careful not to cut or nick the cable insulation. For UNISHIELD® or lead sheath cables, refer to the Installation Instructions supplied with the 10TL cable shield adapter.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation (using the supplied lubricant), always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The exposed conductor length should be 4-3/8 to 4-11/16 inches (111mm to 119mm). If not, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 6-1/2 inches (165mm). Crimp the compression lug following the instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be 6-1/2 to 7-1/4 inches (165mm to 184mm). If not, redo the assembly.
- Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance with the supplied lubricant. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products and Stud
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Install the stud into the apparatus by hand until it is fully seated. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part. For products dated September 30, 2013, or earlier, use the 600AT assembly tool to engage the hex broach in the contact assembly, insert it into the elbow interface to engage the stud, and torque until the torque limiter ratchets (19 to 25 foot/pounds). For products dated October 1, 2013, or later, use the 600ATM assembly tool, engage the hex broach, insert the contact assembly, and tighten to 50-60 foot/pounds torque. DO NOT EXCEED 60 FOOT POUNDS TORQUE.
- Ground the Cable Shield
Insert one end of a piece of wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to make a small loop, without damaging the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded according to the instructions supplied with the grounding device, or through an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture entry.
- Install Loadbreak Interface (Optional)
Clean and lubricate the entire loadbreak interface and either a DR(G), ESA, GLR, or LR of the appropriate voltage class with the supplied lubricant. Install the DR(G), ESA, GLR, or LR to the tap plug interface following the instructions supplied with those specific products.
- Verify Seating Indication
Confirm that the assembly of an insulated cap or elbow is complete by ensuring no portion of the colored interface sleeve is visible when viewed from the side.
- Perform Voltage Test (656CETP Only)
For 656CETP connectors, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device and not directly connected to the conductor; do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the meter used, testing with a suitable sensing device made for capacitive test points. Contamination or incorrect equipment can cause a false 'no voltage' indication; treat the elbow as energized until confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.