ABB Installation Products 1150-487-1 Tru-Break Retrofit Kit for MVS3, Includes (3) BIPS, (1) Tru-Break MVS3 Handle, (1)…
UPC: 075114422246
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Includes (3) BIPS units for busbar interruption protection
- Features a Tru-Break MVS3 Handle and interlock linkage for safe operation
- Provides (3) 600 Amp Studs and (3) 600 Amp Voltage Detection Caps with eyelets
- Includes Tru-Break Mounting Clamps Kit and 1-foot #6 AWG cable
- Designed for 3-pole, 600A medium-voltage switchgear retrofits
Specifications
Amperage Rating | 600 A |
Application | For 3-Phase Molded Vacuum Switches |
Cable Size | #6 AWG |
Connection Type | Stud |
Current Rating | 600 A |
Phase | 3 |
Poles | 3 |
Series | Tru-Break |
Type | Tru-Break RetroFit Kit |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

SP282
Wall Plate Screw, #6-32 size, Oval head, 2 in. length, White Switch Plate head color, Slotted drive type, Steel, Zinc Plated finish, 100 per pack
EFDC275NLQ-G
PVC Coated Mounting Body for Control Station, Feed Through, Two Gang, Hub Size 3/4 Inch/21 Metric, Gray
1825190-7
DIP & SIP Switches, Tin, Black, High Temperature Nylon, 8 Switch, -30 – 85 °C, DIP, 2A Contact Current Rating, Alcoswitch DIP
STXRMBK
The most popular range in the STX series offering, the Surge-Trap® Type 1 STXR meets requirements for UL1449 Fourth Edition and is ideal for the replacement of older surge arrestors. The STXR Series SPD feature TPMOV® technology inside making them the safest product available. With a small, compact design and line or load installation flexibility the STXR series is the perfect fit for branch panel and/or individual equipment protection., V, ,Frequently Asked Questions
What is the current rating of this retrofit kit?
The ABB Tru-Break Retrofit Kit for MVS3 is rated for 600 Amps.
What components are included in the Tru-Break Retrofit Kit?
The kit includes (3) BIPS, (1) Tru-Break MVS3 Handle, (1) Tru-Break Interlock Linkage, (3) 600 Amp Studs, (3) 600 Amp Voltage Detection Caps with Eye, (1) Tru-Break Mounting Clamps Kit, and (1 Foot) #6 AWG Cable.
How many poles does this retrofit kit support?
This Tru-Break Retrofit Kit is designed for 3-pole electrical systems.
What type of connections are used with this kit?
The kit utilizes stud connections and includes voltage detection caps with eyelets for monitoring.
What is the material of the studs and voltage detection caps?
The studs and voltage detection caps are rated for 600 Amps and are made from materials suitable for electrical applications.
How to Install the Elastimold Tru-Break Retrofit Kit
This guide provides comprehensive instructions for installing the Elastimold Tru-Break Retrofit Kit, covering handle replacement, module mounting, grounding, and interlock system setup on switchgear.
Estimated time: 2h
Tools needed:
Torque wrench, Lifting eye bolts, Lifting strap, Wire strippers, Standard hand tools (e.g., wrenches, screwdrivers)
Supplies needed:
Elastimold Tru-Break Module, 6 AWG Braided Ground Cable, Interlock Linkage Kit, Mounting Clip Kit, Switchgear Operating Handle for Tru-Break, Basic Insulating Plugs with Caps, 5/8-11 x 2 ¾” Length Studs, Silicone Grease Packets, 3’ Electronic Lockout Cable (if applicable), Customer-supplied ½-13UNC lifting eye bolts
- Prepare for Installation and Safety
De-energize all apparatus in the work area. Inspect all kit contents for completeness, damage, and compatibility with mating parts. Read the entire installation instructions before starting and have all required tools ready.
- Lift and Uncrate Tru-Break Module
Screw customer-supplied lifting eye bolts into the lifting provisions of the Tru-Break module. Optionally, use an additional lifting strap. Ensure the strap is taut and free from slack, then carefully lift the unit and remove it from its crate.
- Prepare Switchgear and Install New Handle
Ensure the switchgear is in the open position and remove any cable accessories from the 600A interfaces. Remove the original switchgear handle (bolt on MVS, pin on MVI), retaining the bolt or pin. Discard the original handle and MVS position indicator. Install the provided Tru-Break operating handle, including the spacer for MVS, and torque the MVS handle bolt to 16-18 Ft-Lbs.
- Mount Tru-Break Module and Grounding
Loosen the ground lug on the existing switchgear, insert the provided 6 AWG braided ground cable, and tighten the lug. Thread the provided studs into the switchgear interfaces (approximately 3 turns). Clean all interfaces and apply the provided silicone grease to both the switchgear and Tru-Break female interfaces. Carefully lift and install the Tru-Break module onto the switchgear in the correct orientation.
- Install Basic Insulating Plugs and Complete Grounding
Hand-install the Basic Insulating Plugs (BIPs) and then torque them to 50-60 Ft-Lbs. Install voltage detection caps onto the BIPs. Feed the ground cable through the Tru-Break mainbodies, insert it into the ground lug on the Tru-Break, and tighten the lug.
- Secure Tru-Break with Mounting Clips
Place the "U"-shaped part of a mounting clip over the flange of the switchgear cover and slide it down onto the Tru-Break cover bolt. Torque the nylon insert locknuts to 50-75 In-Lbs. Install the ¼-28 bolts and torque them to 75-85 In-Lbs. Repeat for all mounting clips.
- Install Interlock Linkage Kit
Rotate the Tru-Break interlock lever towards the front of the cover. Install the appropriate provided linkage kit (MVS or MVI specific) as shown in the figures.
- Connect Motor Operator Cables (If Applicable)
If the switchgear has a motor operator, remove the 12-pin cable from the motor box and connect it to the Tru-Break 12-pin female receptacle. Install the provided 3’ electronic lockout cable from the Tru-Break male receptacle to the motor box receptacle.
- Reinstall Motor Linkage and Cable Accessories
Reinstall the motor linkage to the new switchgear handle. Re-install any cable accessories that were previously on the switchgear to the Tru-Break interfaces.
- Test Interlock Operation
Perform the interlock test: With the switchgear open, verify the Tru-Break handle operates between open and closed. Move the Tru-Break to the open position; verify the switchgear handle cannot close. Move the Tru-Break to the closed position, then close the switchgear; verify the Tru-Break handle cannot open. If a motor operator is present, ensure it does not move the MVS/MVI motor when the Tru-Break is open, and that the Tru-Break handle remains locked when both are closed.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.