Overview

The ABB Installation Products Loadbreak LR Copper Contact (SKU: 02702250) is a medium-voltage electrical component designed for safe loadbreak switching operations in 15-35kV distribution systems. Rated for 200 Amps, this copper contact accommodates 2/0 AWG stranded/compressed or 3/0 AWG solid/compact copper conductors, ensuring reliable electrical conductivity and durability. Engineered for compatibility with ABB’s 161/162LR, 261/262LR, 375/376LR, and 252LR loadbreak elbows, this contact is optimized for copper conductors only. Its design facilitates controlled circuit interruption under load, reducing arc flash risks and enhancing personnel safety in utility and industrial switchgear applications. The copper material selection ensures low resistance and long-term performance in demanding environments. Each kit includes the connector and a crimp chart (CC-0024) for proper installation. This component is essential for medium-voltage distribution networks requiring precise load management and operational reliability.
  • Voltage rating: 15-35kV, current rating: 200 Amps
  • Compatible with 2/0 AWG stranded/compressed or 3/0 AWG solid/compact copper conductors
  • Designed for use with ABB 161/162LR, 261/262LR, 375/376LR, and 252LR loadbreak elbows
  • Copper contact material ensures efficient electrical conductivity and durability
  • Includes crimp chart (CC-0024) for proper installation

Specifications

Application
Loadbreak LR Elbows
Cable Size
2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG
Insulation
No
Material
Copper
Number of Holes
1
Special Features
Copper Conductor Only
Standard
IEEE 386
Stud Size
3/8
Type
Copper Compression Lug
Voltage Rating
15/25/35kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
0.1000 L
Package Weight (Metric)
0.0450 kg
Heat Shrink Ring Terminal 12 10 AWG, 3/8" stud size.

PH10-38R-E

Heat Shrink Ring Terminal 12 10 AWG, 3/8" stud size.
Service Post Connector - Two Wire Type 4 STR Service Post Connectors is used for connecting one or two conductors. Made from high copper content hard-drawn rod. Lay-in feature makes them excellent for continuous loop grounding and bonding. Used to ground to bar or plate. Suitable for direct burial in earth or concrete.

SPM-24L

Service Post Connector - Two Wire Type 4 STR Service Post Connectors is used for connecting one or two conductors. Made from high copper content hard-drawn rod. Lay-in feature makes them excellent for continuous loop grounding and bonding. Used to ground to bar or plate. Suitable for direct burial in earth or concrete.
Copper Blank Tongue Lug, Standard Barrel, Peep Hole, Max 35kV, Wire Size #2 AWG, Tin Plated, Die Code 33, Die Color Code Brown

54143BT

Copper Blank Tongue Lug, Standard Barrel, Peep Hole, Max 35kV, Wire Size #2 AWG, Tin Plated, Die Code 33, Die Color Code Brown
Aluminum H-Tap Connector, Wide Range, Industry Standard Size Code 2, Conductor Range Main ASCR 1/0, #1, #2, Stranded 2/0, 1/0, #1, #2, Solid 3/0, 2/0, 1/0, #1, #2 TAP ASCR #2, #4, #6, Stranded #1, #2, #3, #4, #6, Solid #2, #4, #6, Die O, 25 Pieces

WR189R

Aluminum H-Tap Connector, Wide Range, Industry Standard Size Code 2, Conductor Range Main ASCR 1/0, #1, #2, Stranded 2/0, 1/0, #1, #2, Solid 3/0, 2/0, 1/0, #1, #2 TAP ASCR #2, #4, #6, Stranded #1, #2, #3, #4, #6, Solid #2, #4, #6, Die O, 25 Pieces
15/25kV, 200 Amp, RLR Contact, Replacement Elbow Connector for Aluminum and Copper Conductors, 230 - for Conductor size #1 - Stranded/Compressed, 1/0 Compact/Solid

00400230

15/25kV, 200 Amp, RLR Contact, Replacement Elbow Connector for Aluminum and Copper Conductors, 230 - for Conductor size #1 - Stranded/Compressed, 1/0 Compact/Solid
15-35kV 200 Amp, Loadbreak LR Copper Contact - 3/0 Stranded/Compressed or 4/0 Solid/Compact

02702260

15-35kV 200 Amp, Loadbreak LR Copper Contact - 3/0 Stranded/Compressed or 4/0 Solid/Compact
Aluminum One-Hole Lugs - common die series - straight lugs, conductors - AL or CU, Wire Range 300 Stranded, 300 Compressed, 350 Compact, 266.8 (18/1) ACSR, installing dies 96, 299, 655, 321, 316, 13A, 1 1/8-1, 472, CSA 28. Length 3-41/64 inch. Pad 1-1/4 inch wide x 1-11/32 inch long x 11/32 inch thick. (1) 9/16 inch diameter hole. Barrel 1-19/32 inch. Dual Rated for Aluminum and Copper Conductors

SA 300-48

Aluminum One-Hole Lugs - common die series - straight lugs, conductors - AL or CU, Wire Range 300 Stranded, 300 Compressed, 350 Compact, 266.8 (18/1) ACSR, installing dies 96, 299, 655, 321, 316, 13A, 1 1/8-1, 472, CSA 28. Length 3-41/64 inch. Pad 1-1/4 inch wide x 1-11/32 inch long x 11/32 inch thick. (1) 9/16 inch diameter hole. Barrel 1-19/32 inch. Dual Rated for Aluminum and Copper Conductors
Aluminum Meter Socket Lug - One-Hole - for 1/2 inch bolt, Wire Range #6 Stranded - Compressed, #6 Compact. Installing dies 840, 845, TX, 76, 249, 11A. Length 3-1/8 inch. One Hole Pad 9/16 inch Diameter. Pad 1-9/32 inch long x 1/4 inch thick. Barrel 1-3/4 inch. Oxide Inhibitor. Blue Cap. Dual Rated for Aluminum and Copper Conductors

SAKM 6-48

Aluminum Meter Socket Lug - One-Hole - for 1/2 inch bolt, Wire Range #6 Stranded - Compressed, #6 Compact. Installing dies 840, 845, TX, 76, 249, 11A. Length 3-1/8 inch. One Hole Pad 9/16 inch Diameter. Pad 1-9/32 inch long x 1/4 inch thick. Barrel 1-3/4 inch. Oxide Inhibitor. Blue Cap. Dual Rated for Aluminum and Copper Conductors

Frequently Asked Questions

What is the amperage rating for 02702XXX?

All 02702XXX Loadbreak Copper Contact connectors are rated for 200A.

What conductor material is required for 02702XXX?

The 02702XXX all copper connectors are designed for use on copper conductors only.

Which elbows are compatible with 02702XXX connectors?

02702XXX copper connectors are designed for use with 161/162LR, 261/262LR, 375/376LR, and 252LR elbows.

What items are included in the 02702XXX kit?

Each 02702XXX kit contains one 02702XXX connector and one Crimp Chart CC-0024.

What conductor sizes fit 02702250?

The 02702250 connector is compatible with 2/0 AWG or kcmil for stranded/compressed conductors and 3/0 AWG or kcmil for solid/compressed bi-metal conductors.

What is the 02702250 product?

Product 02702250 is a 200A Loadbreak Copper Contact connector.

What is the amperage rating for 02702XXX?

All 02702XXX Loadbreak Copper Contact connectors are rated for 200A.

What conductor material is required for 02702XXX?

The 02702XXX all copper connectors are designed for use on copper conductors only.

Which elbows are compatible with 02702XXX connectors?

02702XXX copper connectors are designed for use with 161/162LR, 261/262LR, 375/376LR, and 252LR elbows.

What items are included in the 02702XXX kit?

Each 02702XXX kit contains one 02702XXX connector and one Crimp Chart CC-0024.

How to Install the Elastimold 252LR Deadbreak Elbow Connector

This guide provides step-by-step instructions for the safe and proper installation of the Elastimold 252LR Deadbreak Elbow Connector, including cable preparation, elbow assembly, grounding, and connection to a deadbreak bushing.

Estimated time: 1h 30m

Tools needed:

Cable cutter, Wire strippers, Wire brush, Crimp tool, Wrench, Pliers, Hot stick, Suitable voltage sensing device

Supplies needed:

Elastimold 252LR Deadbreak Elbow Connector, UD Cable, Compression Lug, Probe, Lubricant (supplied), Hold-down Bail, No. 14 AWG copper wire, Appropriate ground connector, Cleaning solution, Silicone grease

  1. Prepare for Installation and Safety Checks

    Before starting, ensure all apparatus in the work area are de-energized. Inspect all components of the 252LR Deadbreak Elbow Connector for damage, correct rating, and compatibility with mating parts. Verify the elbow housing cable entrance size and compression lug size match your cable. Test the probe threads by hand-threading into the compression lug; replace any damaged components. Gather all required tools and maintain cleanliness throughout the procedure.

  2. Prepare the UD Cable

    Train the UD cable to ease operation, ensuring a minimum of 20 inches (508mm) extends beyond the end of the cable pad mount transformer. Cut any excess cable squarely at the center line of the bushing. Unwrap and bind the concentric neutral wires 8-1/2 inches (216mm) back from the cable end. Carefully remove the cable shield and insulation, cutting squarely without nicking the conductor. Wire brush the bare aluminum conductors and immediately install the compression lug, rotating it to spread the inhibitor. Position the compression lug so its threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Wipe off any excessive inhibitor from the outside of the lug and cable. Remove the semi-con shield and bevel the insulation end a maximum of 1/8 inch (3.2mm). Thoroughly clean the insulation to remove all traces of conductive residue.

  3. Assemble the Elbow Connector

    Clean and lubricate the cable insulation and the inside of the elbow housing using only the supplied lubricant; do not use substitutes. Slide the elbow connector onto the cable with a back-and-forth twisting motion, then wipe off any excess silicone lubricant. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread. Tighten the probe with the supplied wrench until the wrench bends.

  4. Install the Hold-Down Bail and Grounding

    Place the hold-down bail into the hold-down bracket. Using a separate No. 14 AWG (2.5mm) copper wire, insert one end through the grounding eye on the elbow and twist tightly, ensuring not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector, providing adequate slack for elbow operation.

  5. Connect Elbow to Bushing

    WARNING: Ensure the transformer and elbow are known to be de-energized before proceeding with lubrication and connection. Clean the receptacle portion of the elbow connector and the mating bushing, then lubricate both with the supplied lubricant. Use a fully insulated hot stick to place the elbow onto the bushing; do not operate by hand or attempt to separate if energized.

  6. Secure the Elbow

    Pull the hold-down bail up over the crown or top of the elbow so that the eyebolt on the bail is directly over the operating eye. Tighten down on the elbow locator by turning the eyebolt in a clockwise direction. Adjust the nut on the eyebolt until it allows the eyebolt to seat securely in the locator. The nut should act as a stop to prevent the eyebolt from applying excessive force on the elbow.

  7. Perform Voltage Test (Optional Safety Check)

    WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for separable connectors with capacitive test points and follow its manufacturer's directions. Contamination, moisture, or incorrect equipment can provide a false 'no voltage' indication on an energized elbow. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. To perform the test, remove the test point cap with a hot stick, peeling it off at an angle. Test for voltage using the suitable sensing device. After voltage detection, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.