Contact for Pricing
Overview
- 2000W nominal cooling capacity
- 115V power input
- Slim fit design for space efficiency
- Dust-resistant coils for filterless operation
- Active condensate management
- Easy filter replacement for extremely dusty environments
- Dust resistant coils for filterless operation
- Active condensate management to prevent dripping water
- Energy efficient rotary compressor
- Terminal block power input
Specifications
Application | Controls and Drives; Power Distribution |
Color | Light Gray |
Color Code | RAL 7035 |
Depth | 11.6 in |
Finish | Powder Coated |
Frequency | 50/60Hz |
Height | 1,580 mm |
Material | Mild Steel |
Material | Steel |
Max Current | 41 A |
Mounting Type | Fully recessed, Partial recessed, Surface mount |
Mounting Type | Space-saving mounting options |
NEMA Rating | 12 Indoor, dust-resistant |
Nominal Capacity Btu/h | 6,800 Btu/h |
Nominal Capacity Watts | 2,000 W |
Nominal Voltage | 115 V |
Operating Temperature | 50-131 |
Operating Temperature | 10-55 |
Product Family | SpectraCool Slim Fit |
Protection Rating | NEMA Type 12 |
Remote Access Control | Yes |
Series | SpectraCool Slim Fit |
Size | S16 |
Thickness | 1.21 mm |
Type | Air Conditioners |
Voltage AC | 100-120 V |
Voltage Rating | 115 V |
Weight | 147 lb |
Width | 15.7 in |
Package Dimensions (L x W x H) | 19.75 IN x 16 IN x 64.5 IN |
Package Dimensions (L x W x H) | 50.165 cm x 40.64 cm x 163.83 cm |
Package Weight (Imperial) | 147.000 L |
Package Weight (Metric) | 66.679 kg |
How to Install the S162016G060 Air Conditioner
This guide provides step-by-step instructions for installing and configuring the S162016G060 Air Conditioner, ensuring proper setup and functionality.
Estimated time: 1h
Tools needed:
Screwdriver, Wire strippers, Multimeter
Supplies needed:
Mounting screws, Terminal connectors
- Inspect the Air Conditioner
Check the air conditioner for any visible damage from shipping, including dents or loose assemblies. Report any damage to the carrier within 15 days.
- Position the Air Conditioner
Place the air conditioner in an upright position for at least five minutes before operation to avoid damage to the compressor.
- Wire the Air Conditioner
Connect the air conditioner to a properly grounded power supply using copper conductors. Ensure the circuit is fused with a slow blow or HACR rated circuit breaker.
- Mount the Air Conditioner
Secure the air conditioner to the enclosure using the provided mounting screws. Ensure it is level and firmly attached.
- Test Functionality
Before finalizing the installation, power on the air conditioner to test its functionality. Ensure it operates correctly without any issues.
Frequently Asked Questions about nVent
What industries and applications are nVent products used for?
nVent products are engineered for critical infrastructure and industrial applications across multiple demanding sectors. Key markets include Construction, Data Centers, Defense, Healthcare, Mining, Oil & Gas Refineries, Power Plants, Rail/Transit, Renewable Energy, Security, Ship Building, Steel Mills, Telecom, and Utilities. Their solutions are designed to withstand extreme environmental conditions, with temperature ranges from -55°C to 105°C and specialized features like UV resistance, oil resistance, and flame resistance.
What environmental ratings do nVent products have?
nVent enclosures feature comprehensive environmental ratings, including UL 508A, CSA, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications. They are rated IEC 60529 IP66, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments. These products operate effectively in temperatures ranging from -40°F to 266°F, with enhanced UV inhibitors for outdoor weathering and oil-resistant gaskets for superior sealing.
What accessories are available for nVent products?
nVent offers a comprehensive range of accessories across multiple product lines, including EMC accessories like bonding cable clamps and strain reliefs, inline accessories such as lock inserts and mounting brackets, CONCEPT accessories including panel conversion kits and rack-mount angles, and seismic accessories for specialized mounting requirements. Key accessory categories include grounding kits, DIN rail mounting solutions, panel supports, handles, and various mounting hardware compatible with different enclosure types.
What certifications and standards do nVent products comply with?
nVent products meet critical international certifications including UL (United States), CSA (Canada), CE (European Community), and EAC (Russia). Our products are designed to comply with rigorous industrial standards such as NEMA enclosure ratings, IEC 60529 IP ratings, and international safety standards across multiple industrial markets including oil & gas, power, manufacturing, and infrastructure.
What is nVent's warranty policy?
nVent offers a standard 18-month warranty from invoicing date for most automation products, covering defects in workmanship and materials. The warranty requires proper transportation, handling, storage, and installation within specified environmental conditions. Warranty coverage includes repair or replacement at nVent's discretion, with certain conditions such as authorized service repairs and operation within designed capacity limits.
What technical support does nVent offer?
nVent offers comprehensive technical support through multiple global contact centers across North America, South America, Europe, Middle East, India, and Asia. Customers can reach technical experts by phone at regional numbers, with the North American headquarters in Minneapolis, MN providing primary support at +1.763.421.2240. Additionally, nVent provides online support resources through their website, including CAD drawing downloads and an 'Ask The Expert' feature to assist with product technical inquiries.